Page 178

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

14.4

14.4 Maintenance and Periodic Inspection

Maintenance and Periodic Inspection This PLC does not incorporate consumable parts that are factors in the reduction of service life. However, the output relays (points of contact) and batteries (option) have a limited life expectancy.

14.4.1 Procedures for checking model name The model name of the main unit can be checked on the nameplate on the right side. After extension devices are connected, the nameplate cannot be seen. Check the model name in the following places. When the top cover is removed

Model name (abbreviation)

Model name

14.4.2 Periodic inspection - battery life, etc. 1. Battery Part Model FX3U-32BL battery

Life Standard life: 5 years (at ambient temperature of 25 C (77 F))

Standard life of FX3U-32BL: 5 years (at ambient temperature of 25 C (77 F)) → For details on the standard life and recommended replacement frequency, refer to Subsection 22.4.1.

2. Other devices When inspecting the battery, check the following points. • Check that the temperature in the panel is not abnormally increased by other heat generating bodies or direct sunlight. • Check that dust or conductive dust has not entered the panel. • Check for loosening of wiring and other abnormalities.

3. Battery Replacement When the battery voltage drops while the PLC power is on, the "ALM" LED on the panel is lit in red, and M8005 and M8006 (latch) are turned on. The memory can be retained for about one month after the lamps turn on. However, the operators may not immediately find the lamps to be on. Prepare a new battery promptly, and replace the battery with the new one. → For details on the specifications and functions of the battery, refer to 22. Battery Caution Select the battery mode using a parameter when using the battery.If the battery mode is not selected, the data is not backed up, and the "ALM" LED on the panel does not light. → For the battery mode setting method, refer to Subsection 22.3.2.

172

Page 179

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

14.4 Maintenance and Periodic Inspection

11

The product life of relay contacts varies considerably depending on the load type used. Take care that loads generating reverse electromotive force or rush current may cause poor contact or deposition of contacts which may lead to considerable reduction of the contact product life. Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller, the arc energy gets larger.

Test condition: 1 sec. ON / 1 sec.OFF Load capacity

35VA 80VA

0.2A/100V AC 0.1A/200V AC 0.35A/100V AC 0.17A/200V AC 0.8A/100V AC 0.4A/200V AC

14

3,000,000 times

Test Run, Maintenance, Troubleshooting

20VA

Contact life

13 Wiring for Various Uses

1) Input/output powered extension units and input/output extension blocks → For the applicable models, refer to Chapter 3. The standard life of contacts used for Inductive loads, such as contactors and solenoid valves, is 500,000 operations at 20VA. The following table shows the approximate life of a relay based on the results of an operation life test.

12 Output Wiring

1. Inductive load

High-Speed Counters

14.4.3 Maintenance - product life of relay contacts

1,000,000 times 200,000 times

15

→ For the applicable models, refer to Chapter 3. The standard life of contacts used for Inductive loads, such as contactors and solenoid valves, is 500,000 operations at 35VA. The following table shows the approximate life of a relay based on the results of an operation life test.

Input/Output Powered Extension Units

2) FX Series terminal blocks

Test condition: 1 sec. ON / 1 sec.OFF

16

35VA 80VA

0.17A/200V AC 0.8A/100V AC 0.4A/200V AC 1.2A/100V AC 0.6A/200V AC

Contact life 3,000,000 times 1,000,000 times

17

200,000 times

18 Other Extension Units and Options

The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down. Please refer to the following measures regarding the inductive load. → For precautions on the main unit, Input/output extension block, refer to Subsection 12.1.3-2. → For precautions on inductive loads for the terminal block, refer to Subsection 20.7.4-2. Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load.

Extension Power Supply Unit

120VA

0.35A/100V AC

Input/Output Extension Blocks

Load capacity

19 Display Module

20 Terminal Block

173

Page 180

FX3G Series Programmable Controllers User's Manual - Hardware Edition

14 Test Operation, Adjustment, Maintenance and Troubleshooting 14.4 Maintenance and Periodic Inspection

2. Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load.

3. Capacitive load Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load. Capacitive loads such as capacitors may be present in electronic circuit loads including inverters. * About the maximum load specifications of the resistance load, refer to the specification for each model. → For specifications on the input/output powered extension units, refer to Chapter 15. → For specifications on the input/output extension blocks, refer to Chapter 16. → For specifications on the terminal block, refer to Chapter 20.

174

Page 181

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

11

Troubleshooting with LEDs

High-Speed Counters

14.5

14.5 Troubleshooting with LEDs

When trouble occurs, check the LEDs on the PLC to identify the problem with the PLC.

14.5.1 POW LED [on/flashing/off]

On

State of PLC

Output Wiring

State of LED

12 Remedies

Power of the specified voltage is being correctly The power supply is normal. supplied to the power supply terminal.

Off

• One of the following problems may have occurred. • The power supply is off. • External wiring is incorrect. • • Power of the specified voltage is not being supplied to the power supply terminal. • The power cable is broken.

If the power is not off, check the power supply and the power supply route. If power is being supplied correctly, consult your local Mitsubishi Electric distributer. After disconnecting the cables other than the power cable, re-apply power to the PLC, and check for changes in the state. If no improvement is obtained, consult your local Mitsubishi Electric distributer.

14

15

14.5.2 ALM LED [on/off]

State of PLC

Remedies

The battery voltage is low.

Off

The battery voltage is higher than the value set Normal with D8006.

Immediately replace the battery. (Refer to Section 22.5.)

16

→ For details on the battery, refer to Chapter 22.

Input/Output Extension Blocks

On

Input/Output Powered Extension Units

This LED is valid when the optional battery is installed and the battery mode is selected using a parameter. State of LED

13

Test Run, Maintenance, Troubleshooting

Check the supply voltage. After disconnecting the cables other than the power cable, re-apply power to the PLC, and check for changes in the state. If no improvement is obtained, consult your local Mitsubishi Electric distributer.

Wiring for Various Uses

Flashing

One of the following problems may have occurred. • • Power of the specified voltage and current is • not being supplied to the power supply terminal. • External wiring is incorrect. • Internal error of PLC

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

175

Page 182

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

14.5 Troubleshooting with LEDs

14.5.3 ERR LED [on/flashing/off] State of LED

State of PLC

Remedies 1)

On

Stop the PLC, and re-apply power. If ERR LED goes off, a watchdog timer error may have occurred. Take any of the following measures. - Review the program. The maximum value (D8012) of the scan time should not exceed the setting (D8000) of the watchdog timer. - Check that the input used for input interruption or pulse catch is not being abnormally turned on and off in one scan. - Check that the frequency of the pulse (duty of 50%) input to the high-speed counter does not exceed the specified range. - Add the WDT instructions. Add some WDT instructions to the program, and reset the watchdog timer several times in one scan. A watchdog timer error may have occurred, or - Change the setting of the watchdog timer. the hardware of the PLC may be damaged. Change the watchdog timer setting (D8000) in the program so that the setting is larger than the maximum value of the scan time (D8012). 2) Remove the PLC and supply power to it from another power supply on a desk. If the ERR LED goes off, noise may have affected the PLC. Take the following measures. - Check the ground wiring, and reexamine the wiring route and installation location. - Fit a noise filter onto the power supply line. 3) If the ERR LED does not go off even after the measures stated in (1) and (2) are taken, consult your local Mitsubishi Electric distributer.

Flashing

One of the following errors has occurred in the PLC. Perform PLC diagnosis and program check with the programming tool. • Parameter error For the remedies, refer to 14.6 Judgment by Error Codes and • Syntax error Representation of Error Codes. • Ladder error

Off

176

No errors that stop the PLC have occurred.

If the operations of the PLC are abnormal, perform PLC diagnosis and program check with the programming tool. An I/O error, Comms.error or Runtime error may have occurred.

Page 183

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

14.6 Judgment by Error Codes and Representation of Error Codes

Judgment by Error Codes and Representation of Error Codes

High-Speed Counters

14.6

11

Error codes can be checked with the programming tool and display module.

14.6.1 Operation and check by GX Developer

12 Output Wiring

1 Connect the personal computer and the PLC. 2 Execute the PLC diagnosis. [PLC diagnostics] on the tool menu, and the diagnosis of PLC will start.

13 Wiring for Various Uses

Click [Diagnostics]

14 Test Run, Maintenance, Troubleshooting

15 Input/Output Powered Extension Units

3 Check the results of diagnosis.

16 Input/Output Extension Blocks

Display the following window to check the errors. Example: one error occurs

17 Open the help window of GX Developer to check the error details.

Extension Power Supply Unit

The LED status of FX PCL is displayed.

18 Other Extension Units and Options

The error in PLC is displayed.

19 Display Module

20 Terminal Block

Example: No error

177

Page 184

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

14.6 Judgment by Error Codes and Representation of Error Codes

14.6.2 Operation and check on display module (FX3G-5DM) 1) Move the cursor to "ErrorCheck" pressing the + or - button on the menu screen (shown right). For the menu structure, refer to Section 19.5. The buttons on the menu screen work as stated below. Button

Operation Description

Mo n i t o r / T e s t E r r o r Ch e c k

The screen returns to the top screen (time display).

L A NGU A G E Co n t r a s t

-

The cursor moves upward. When the button is held for 1 second or more, the cursor moves quickly. When the cursor is in the uppermost position, the button is ineffective.

+

The cursor moves downward. When the button is held for 1 second or more, the cursor moves quickly. When the cursor is in the lowermost position, the button is ineffective.

OK

The flashing item at the cursor is selected.

ESC

2) When the OK button is pressed, an error check is performed. The results are displayed on the error display screen (shown to the right). Pressing the ESC button on the menu screen cancels the operation and returns the screen to the top screen (time display).

C l o c kMe n u Ke ywo r d Ca s s e t t e

When no errors have occurred E r r o r Ch e c k No er ror s

3) If some errors have occurred, the pages can be switched with the + or - button. Button ESC

-

+

Operation Description The screen returns to the Menu screen.

1 error or Ineffective operation less 2 errors or more

The previous page of the error display screen is displayed.

1 error or Ineffective operation less 2 errors or more OK

The following page of the error display screen is displayed. The screen returns to the Menu screen.

When 1 error has occurred E r r o r Ch e c k [1]

M8 0 6 5 Er ror code

6508

[2]

When multiple errors have occurred 1 / 2

E r r o r Ch e c k M8 0 6 0

[3] [1]

Er ror code

1020

[2]

Displayed data Display Content

[1]

Flag of occurred error

[2]

Error code

[3]

Number of simultaneously occurring errors (displayed only when more than one error has occurred)

4) Pressing the ESC button cancels the operation and returns the screen to the Menu screen.

178

-

+

E r r o r Ch e c k

2 / 2

M8 0 6 3 Er ror

[3] [1] code

6301

[2]

Page 185

FX3G Series Programmable Controllers

14 Test Operation, Adjustment, Maintenance and Troubleshooting

User's Manual - Hardware Edition

14.6 Judgment by Error Codes and Representation of Error Codes

11 High-Speed Counters

14.6.3 Representation of errors Errors are represented in this manual, GX Developer as shown in the following table. This manual I/O configuration error

GX Developer English version

12

PLC H/W error

PLC/PP communication error

PLC/PP comm err

Serial communication error 1 [ch1]

Link error

Serial communication error 2 [ch2]

Link error2

Parameter error

Param error

Syntax error

Syntax error Ladder error

Operation error

Operation err

13 Wiring for Various Uses

Circuit error

Output Wiring

PLC hardware error

Special block error

Japanese version

I/O config err

-

-

14 Test Run, Maintenance, Troubleshooting

15 Input/Output Powered Extension Units

16 Input/Output Extension Blocks

17 Extension Power Supply Unit

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

179