Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 6 of 49

FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 2. Features and Part Names

Pages 29 to 33 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 29

FX3G Series Programmable Controllers

2 Features and Part Names

User's Manual - Hardware Edition

2.1 Major Features

1

2.1

Major Features 1. Basic functions

[Program memory] The PLC has a 32K-step EEPROM memory.

[Built-in clock function] The PLC has a clock function to control the time.

Signal ON/OFF width

X000, X001, X003, X004

10 s

X002, X005, X006, X007

50 s

6

[Input interruption function] The PLC can process interruption routines with higher priority using external signals whose minimum ON duration or OFF duration is 10 s (X000, X001, X003 and X004) or 50 s (X002 and X005).(The timer interruption function is also provided.) → Refer to 10. Input Wiring Procedures in this manual and Programming Manual. [Pulse width/period measurement function] (Supported in Ver. 1.10 or later) The width/period of pulses from input terminals (X000, X001, X003 and X004) of the main unit can be measured in units of 10 s. → Refer to 10. Input Wiring Procedures and Programming Manual.

7

8 Installation

9 Preparation and Power Supply Wiring

[Programming tool] Use a version of GX Developer applicable to FX3G. → Refer to 5. Version Information and Peripheral Equipment Connectability in this manual. *For peripheral devices not applicable to FX3G Series, specify FX1N Series for model selection, and you can program the sequence. In this case, use instructions and devices within the ranges common to FX 3G Series and the selected model of PLC.

Input terminal

5

Input/Output Nos., Unit Nos.

[Writing during RUN] The programming software for personal computer enables you to modify the program while the PLC is running.

[Pulse catch function] Signals with short ON width or OFF width can be captured without a complicated program. → Refer to 10. Input Wiring Procedures in this manual and Programming Manual.

4

System Configuration

[Built-in Variable analog potentiometers] The PLC has two built-in variable analog potentiometers available for adjusting the timer set time.

[High-speed counter function] Input terminals of main unit - Input of open collector transistor output - 1-phase 60kHz x 4points + 10kHz x 2points - 2-phase 30kHz x 2 points + 5kHz x 1 points → Refer to 11. Use of High-speed Counters in this manual and Programming Manual.

Version and Peripheral Devices

[Built-in RUN/STOP switch] The PLC can be started and stopped with the built-in switch. RUN and STOP commands can be given to the PLC through a general-purpose input terminal or peripheral device.

3

2. Input/output high-speed processing functions of main unit

Specifications

[Built-in USB port] The PLC has a built-in USB port for the programming communication function to enable high-speed communication at 12Mbps.

the RS-232C expansion board and RS-232C communication special adapter.

Product Introduction

[Up to 256 input/output points] The total number of inputs and outputs (128 points maximum) directly connected to the PLC and remote inputs and outputs (128 points maximum) of the CC-Link can be extended to 256 points.

2 Features and Part Names

Features and Part Names

Introduction

2.

10 Input Wiring

[Remote debugging of program] Use of programming software enables you to remotely transfer the program and monitor the PLC operation through a modem connected to

23

Page 30

FX3G Series Programmable Controllers

2 Features and Part Names

User's Manual - Hardware Edition

2.1 Major Features

[Pulse output function] When output terminals in the transistor output type main unit are used, pulses (open collector outputs) of up to 100kHz can be output simultaneously to 3 axes *1 (Y000, Y001 and Y002).

• Inverter communication (Supported in Ver. 1.10 or later) → Refer to Data Communication Edition.

*1.

• Non-protocol communication through built-in RS-422/RS-232C/RS-485 → Refer to Data Communication Edition.

[Various positioning instructions] → Refer to Positioning Control Edition.

• CC-Link - Master station FX2N-16CCL-M - Intelligent device station FX3U-64CCL - Remote device station FX2N-32CCL → Refer to the manual for each product.

2 axes (Y000 and Y001) in 14-point and 24-point type main units Using a number of instructions programming is simplified. → Refer to Positioning Control Edition.

Instruction

Description

DSZR

Mechanical zero return instruction with DOG search function

ABS

Instruction to read the current value from our servo amplifier with absolute position (ABS) detecting function

DRVI

Positioning (relative positioning) to specify the movement from the current position

DRVA

Positioning (absolute positioning) to specify the target position based on the current value 0

PLSV

Instruction to change the pulse train output frequency

TBL

Instruction for positioning based on batch setting of positioning operation, moving distance and speed

3. Display functions (display module) (Supported in Ver. 1.10 or later) FX 3G -5DM Display Module (option) can be incorporated in the PLC. [Monitor/test function] De v i ce s c a n b e mo nit or ed an d t es t ed by operating the buttons on the display module. The button operations can be inhibited by the user program. [Other functions] On the display module, you can set the time, adjust the contrast and display the PLC version and error codes. → Refer to 19. Display Module(FX3G-5DM) in this manual.

4. Communication and network functions The expansion board and special adapter for each communication function can be connected. [Kinds of communication functions] • Programming communication through RS232C, RS-422 and USB → Refer to Data Communication Edition. • N:N Network → Refer to Data Communication Edition. • Parallel link → Refer to Data Communication Edition.

24

• Computer link → Refer to Data Communication Edition.

• CC-Link/LT - Master station : FX2N-64CL-M - Remote I/O station, Remote device station → Refer to the manual for each product.

5. Analog functions The special adapter and special function block for each analog function are connected. → Refer to Analog Control Edition. [Kinds of analog functions] • Voltage/current input • Voltage/current output • Temperature sensor input (thermocouple and platinum resistance thermometer sensor) • Temperature control

Page 31

FX3G Series Programmable Controllers

2 Features and Part Names

User's Manual - Hardware Edition

2.2 Names and Functions of Parts

Names and Functions of Parts

2.2.1

Front Panel

Introduction

2.2

1

2

Factory default configuration (standard) [4]

Features and Part Names

[3]

[5]

[2] [6] [7] [8]

[1]

3 Product Introduction

[9]

[10] [11] The peripheral device connector, variable analog potentiometers and RUN/STOP switch are located under this cover.

[2] Terminal names

The signal names for power supply, input and output terminals are shown.

[3] Top cover(S) (40points, 60points type only)

Mount the expansion board and memory cassette under this cover. Mount the expansion board, display module, memory cassette and battery under this cover.

[5] Terminal block covers

The covers can be opened for wiring. Keep the covers closed while the PLC is running (the unit power is on).

[6] Input display LEDs (red)

When an input terminal (X000 or more) is turned on, the corresponding LED lights.

[7] Extension device connecting connector cover

Connect the extension cables of input/output powered extension unit/block or special function block to the extension device connecting connectors under this cover. FX3U Series extension devices and FX2N Series extension devices can be connected. → For details on the extension devices, refer to Chapter 15, Chapter 16, Chapter 17 and Section 18.1.

[8] Operation status display LEDs

The operation status of the PLC can be checked with the LEDs. The LEDs turn off, light and flash according to the following table. → For details on the operation status, refer to Section 14.5. Display color

Description On while power is on the PLC.

RUN

Green

On while the PLC is running.

Red

Flashing when a program error occurs.

Red

Lights when a CPU error occurs.

Red

Lights when the battery voltage drops. (When the optional battery is used)

ERR ALM

When an output terminal (Y000 or more) is turned on, the corresponding LED lights.

[10] Model name (abbreviation)

The model name of the main unit is indicated. Check the nameplate on the right side for the model name.

[11] DIN rail mounting hooks

The main unit can be installed on DIN46277 rail (35mm (1.38") wide).

8 Installation

[9] Output display LEDs (red)

7 Input/Output Nos., Unit Nos.

Green

6 System Configuration

LED name POW

5 Version and Peripheral Devices

[4] Top cover

4 Specifications

[1] Peripheral device connecting connector cover

9 Preparation and Power Supply Wiring

10 Input Wiring

25

Page 32

FX3G Series Programmable Controllers

2 Features and Part Names

User's Manual - Hardware Edition

2.2 Names and Functions of Parts

When the top covers are open [4]

[5]

[6]

[3]

[7] [8]

[2] [1]

[10]

[9]

[1] Peripheral device connector (USB)

connecting Connect a programming tool(PC) to program a sequence. → For details on applicable peripheral devices, refer to Chapter 5.

[2] Peripheral device connector (RS-422)

connecting Connect a programming tool to program a sequence. → For details on applicable peripheral devices, refer to Chapter 5.

[3] RUN/STOP switch

To stop writing (batch) of the sequence program or operation, set the switch to STOP (slide it downward). To start operation (run the machine), set it to RUN (slide it upward).

[4] Variable analog potentiometers

Two variable analog potentiometers are built in. Upper side : VR1, Lower side : VR2

[5] Optional equipment connector1

Connect the expansion board and memory cassette to the connector.

[6] Optional equipment connector2 (40points, 60points type only)

Connect the expansion board, display module and memory cassette to the connector.

[7] Battery connector

Connect the optional battery to the connector.

[8] Battery holder

This holder accommodates the optional battery.

[9] Optional equipment connecting screw holes2 (2 places) (40points, 60points type only)

These holes are designed to secure the expansion board and memory cassette with screws.

[10] Optional equipment connecting screw holes1 (2 places)

These holes are designed to secure the expansion board and memory cassette with screws.

When the terminal block covers are open [1]

[5]

26

[2] [3]

[4] [2]

[1] Power supply terminal

Connect the power supply to the main unit.

[2] Terminal block mounting screws

If the main unit must be replaced, loosen the screws (slightly loosen the left and right screws), and the upper part of the terminal block can be removed. → For anchoring of the terminal block, refer to Subsection 9.1.2.

[3] Input (X) terminals

Wire switches and sensors to the terminals.

[4] Output (Y) terminals

Wire loads (contactors, solenoid valves, etc.) to be driven to the terminals.

[5] Terminal cover

A protective terminal cover (refer to the following drawing) is fitted to the lower stage of each terminal block. The cover prevents fingers from touching terminals, thereby improving safety.

Page 33

FX3G Series Programmable Controllers

2 Features and Part Names

User's Manual - Hardware Edition

1

Sides

Introduction

2.2.2

2.2 Names and Functions of Parts

Right side

Left side

2 Features and Part Names

[1] [2]

3

[3]

[2] Nameplate

The product model name, control number and power supply specifications are shown.

Example: FX3G-40MT/ES (manufacturer's serial number: 8X0001)

Specifications

MODEL

4

PROGRAMMABLE CONTROLLER

MITSUBISHI

FX3G-40MT/ES 100-240VAC 50/60Hz 37W OUT:5~30VDC 0.5A

SERIAL

8X0001

5 Version and Peripheral Devices

MITSUBISHI ELECTRIC CORPORATION MADE IN JAPAN

8

X

0

0

0

1

The unit can be installed on DIN46277 rail (35 mm (1.38") wide).

6 System Configuration

Control number Month (Example: Oct.):(1 to 9 = January to September, X = October, Y = November, Z = December) Year (Example: 2008): Last digit of year [3] DIN rail mounting groove

Product Introduction

[1] Connector conversion adapter These holes are designed to secure the connector conversion adapter with screws. connecting screw holes1 (2 places)

7 Input/Output Nos., Unit Nos.

8 Installation

9 Preparation and Power Supply Wiring

10 Input Wiring

27