Page 334
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.7 FX-16EYR-TB
20.7.5 Product life of relay contacts The product life of relay contacts varies considerably depending on the load type used. Take care that loads generating reverse electromotive force or rush current may cause poor contact or deposition of contacts which may lead to considerable reduction of the contact product life.
1. Inductive load Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller, the arc energy gets larger. The standard life of contacts used for Inductive loads, such as contactors and solenoid valves, is 500,000 operations at 35VA. The following table shows the approximate life of a relay based on the results of an operation life test. Test condition: 1 sec. ON / 1 sec.OFF Load Capacity 35VA 80VA 120VA
0.35A / 100V AC 0.17A / 200V AC 0.8A / 100V AC 0.4A / 200V AC 1.2A / 100V AC 0.6A / 200V AC
Contact Life 3,000,000 times 1,000,000 times 200,000 times
The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down. → For precautions on using inductive loads, refer to Subsection 20.7.4-2. Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load.
2. Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load.
3. Capacitive load Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load. Capacitive loads such as capacitors may be present in electronic circuit loads including inverters. → For the maximum specified resistance load, refer to Subsection 20.7.1.
328
Page 335
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
11
FX-16EYT-TB, FX-16EYT-H-TB
High-Speed Counters
20.8
20.8 FX-16EYT-TB, FX-16EYT-H-TB
The FX-16EYT(-H)-TB is used by connecting it to the FX2N series output extension block (transistor). Output Connector Connectable models
12
FX2N-16EYT-C (sink output)
Output Wiring
The applications shown below are not supported. Unsupported Applications
Time division inputs
Input matrix (MTR) instruction, digital switch (DSW) instruction
Time division output Seven segment with latch (SEGL) instruction
20.8.1 Specifications
14 FX-16EYT-TB
24+
Photocoupler
Fuse
0 to 7
LED 24V DC 7mA
3.3k
24+ 5 to 30V DC
COMn
CN1 Connector side
Photocoupler
24V DC 7mA
5 to 30V DC
COMn External wiring
5 to 30V DC
0.5A/point 1A/point Resistance The total load current of resistance loads per common The total load current of resistance loads per common load terminal should be the following value. terminal should be the following value. • 4 output points/common terminal: 0.8A or less • 4 output points/common terminal: 3A or less Inductive load
12W/24V DC
Open-circuit leakage current
Output element's ON voltage Circuit isolation
Power consumption
17
0.1mA / 30V DC 0.2ms or less/24V DC
0.3ms or less/24V DC
1.5ms or less/24V DC
4ms or less/24V DC 1.5V
18
Photo-coupler isolation
Other Extension Units and Options
Operation indicators
16
Extension Power Supply Unit
ResOFF ON*1 ponse OFF ON*1 time
*1.
15
Input/Output Extension Blocks
Max. load
0 to 7
LED
External wiring Load voltage
Fuse
Input/Output Powered Extension Units
CN1 Connector side
3.3k
FX-16EYT-H-TB
Test Run, Maintenance, Troubleshooting
Transistor output
Item
Input/output circuitry
13 Wiring for Various Uses
Pulse outputs
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation (PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction
Activation of the photo-coupler will light the LED indicator lamp on panel. 2.7W (112mA 24V DC)
This response time does not include the response delay at the PLC.
19 Display Module
20 Terminal Block
329
Page 336
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.8 FX-16EYT-TB, FX-16EYT-H-TB
20.8.2 Internal circuit
3.3k
3.3k
Photocoupler
COM 7 6 5 4 3 2 1 0
Photocoupler
(20) (10) (19) (9) COM (18) (8) 7 (17) (7) 6 (16) (6) 5 (15) (5) 4 (14) (4) 3 (13) (3) 2 (12) (2) 1 (11) (1) 0
0 to 0 1 2 3
3.3k Photocoupler
3.3k Photocoupler
7 Lower numbers 4 5 6 7
*
*
0 to 0 1 2 3 *
7 Higher numbers 4 5 6 7 *
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 * For the FX-16EYT-H-TB, the output transistor elements are as shown in the figure below.
20.8.3 Example of output external wiring PLC output No.
0 1 2 3
*
4 5 6 7
*
0 1 2 3
*
4 5 6 7
*
Photo-coupler power supply 24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
Fuse
Fuse
24V DC * For the FX-16EYT-H-TB, the output transistor elements are as shown in the figure below.
330
Page 337
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.8 FX-16EYT-TB, FX-16EYT-H-TB
11 High-Speed Counters
20.8.4 External wiring precautions 1. Protection circuit for load short-circuits Load
Load current or more
13
0 to 7
Fuse
COMn Terminal block
14 Test Run, Maintenance, Troubleshooting
5 to 10 times of the load voltage
Forward current inductive load
Wiring for Various Uses
Reverse voltage
12
COMn Terminal block
2. Transistor protection circuit for inductive loads The transistor output circuit in the terminal block is equipped with a Zener diode (50V) for protection. When an inductive load is connected, however, a diode should be connected parallel to the load when required. The diode must comply with the specifications shown below.
0 to 7
Fuse
Output Wiring
A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output. Use a load power supply capacity that is at least 2 times larger than the total rated fuse capacity.
3. Interlock Forward limit
Reverse limit
Interlock
Forward
15
Reverse
Input/Output Powered Extension Units
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs as shown to the right.
PLC output element
16 Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
331
Page 338
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.9 FX-16EYS-TB
20.9
FX-16EYS-TB The FX-16EYS-TB is used by connecting it to the FX2N series output extension block (transistor). Output Connector Connectable models
FX2N-16EYT-C (sink output)
The applications shown below are not supported. Unsupported Applications Pulse outputs
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation (PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction
Time division inputs
Input matrix (MTR) instruction, digital switch (DSW) instruction
Time division output Seven segment with latch (SEGL) instruction
20.9.1 Specifications Item
Triac output
24+
3.3k
7mA
0 to 7
Fuse
2.2 Input/output circuitry
U
CN1 connector side
LED
0.015 F Photothyristor
COMn External wiring
Load voltage
85 to 242V AC
Resistance Max. load load Inductive load
The total load current of resistance loads per common terminal should be the following value. • 4 output points/common terminal: 0.8A or less
0.3A/point*1 15VA/100V AC 36VA/200V AC
Min. load
0.4VA/100V AC 1.6 VA/200V AC
Open-circuit leakage current
1mA/100V AC 2mA/200V AC
Response time*2
2ms or less
Circuit isolation
Photocoupler isolation
Operation indicators
Activation of the photo-thyristor will light the LED indicator lamp on panel.
Power consumption
2.7W (112mA 24V DC)
*1.
In systems where frequent large-load ON/OFF switching occurs due to rush currents, the root mean square current should be 0.2 A or less. <Example> 42
0.02 + 0.42
0.7
0.02 + 0.7 + 10
= 0.2A 0.02 sec
*2.
332
0.4A
4A
0.7 sec
10 sec
This response time does not include the response delay at the PLC.
Page 339
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.9 FX-16EYS-TB
11 High-Speed Counters
20.9.2 Internal circuit
(20) (10) (19) (9) COM (18) (8) 7 (17) (7) 6 (16) (6) 5 (15) (5) 4 (14) (4) 3 (13) (3) 2 (12) (2) 1 (11) (1) 0
Photothyristor 3.3k
Photothyristor
3.3k
13
Photothyristor
7 Lower numbers
0 to
Wiring for Various Uses
Photothyristor 0 to
12
3.3k
Output Wiring
COM 7 6 5 4 3 2 1 0
3.3k
7 Higher numbers
Surge absorbers are connected to each output 0 1 2 3
4 5 6 7
U
14
4 5 6 7
U
Test Run, Maintenance, Troubleshooting
U
0 1 2 3
U
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
15 Input/Output Powered Extension Units
20.9.3 Example of output external wiring
Surge absorbers are connected to each output 0 1 2 3
Photo-coupler power supply
4 5 6 7
U
0 1 2 3
U
16
4 5 6 7
U
Input/Output Extension Blocks
PLC output No.
U
17
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
Extension Power Supply Unit
Load
24V DC Fuse
Fuse
18
Fuse
Other Extension Units and Options
19 Display Module
20 Terminal Block
333
Page 340
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.9 FX-16EYS-TB
20.9.4 External wiring precautions 1. Protection circuit for load short-circuits A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.
Load
0 to 7
Fuse COMn Terminal block
2. Micro current load The PLC's internal Triac output circuit is equipped with a turn-off C-R absorber. When connecting a very low current load of "0.4VA/100V AC or less or 1.6VA/200V AC or less", please connect a surge absorber parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table below for other specifications.
Micro current load
Surge absorber
U
Guide Static electricity capacity
Approx. 0.1 F
Resistance value
Approx. 100 to 200
Reference Manufacturer Okaya Electric Industries Co., Ltd.
Model name CR-10201
Manufacturer
Model name
Rubycon Corporation
250MCRA104100M B0325
3. Interlock For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs as shown to the right.
Interlock
Forward limit
Forward
U
Reverse
Reverse limit U
PLC output element
4. In-phase PLC output contacts (*) should be used in an "in-phase" manner.
*
Bad
U
*
U
*
Good
U
*
U
334