Page 326

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.4 Installation Work

20.4.4 Connection to terminal block 1. Terminal Screw Size The product terminal screws are as shown in the table below. Model Name

Terminal Screw Size

FX-16E-TB, FX-32E-TB FX-16EX-A1-TB FX-16EYR-TB FX-16EYS-TB FX-16EYT-TB, FX-16EYT-H-TB

M3.5

2. Wire end treatment and tightening torque Use solderless terminals of the following size. Tighten the terminals to a torque of 0.5 N•m to 0.8 N•m. • When 1 wire is connected to 1 terminal: Use a crimp terminal of the size shown below, and install it as shown in the lower right figure. Terminal Crimp 3.7(0.15") screw terminal

6.8mm(0.27") or less 3.7(0.15") 6.8mm(0.27") or less

Terminal

• When 2 wires are connected to 1 terminal: Use a crimp terminal of the size shown below, and install it as shown in the lower right figure.

3.7(0.15") 6.8mm(0.27") or less

Terminal Crimp screw terminal

6.0mm(0.24") or more 3.7(0.15")

6.8mm(0.27") or less

320

Terminal

6.0mm(0.24") or more

Page 327

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

11

FX-16E-TB, FX-32E-TB The FX-16E-TB and FX-32E-TB items must be connected using an FX2N series input/output connector type extension block. Input Connector

12

Output Connector

FX2N-16EX-C (sink input)

FX2N-16EYT-C (sink output)

Output Wiring

Connectable models

20.5.1 Internal circuit 0 to

7 (Lower Nos.)

1

*1

0

3 2

5

COM

4

COM

7 (Higher Nos.)

*2

7 6

*2

1

COM

0

COM

*2

3 2

4

COM

*2

13

*2

5

COM

7 6

COM

Wiring for Various Uses

CN2

0 to

*2

*1

COM

*2

*2

*1

14

*2

Test Run, Maintenance, Troubleshooting

15 0

2 1

0

CN1

4 3

2

4 3

7 6

5

7

*1

(20) (10)

*1

*1

*2

1 2

*1

*2

5

COM COM

4

7 6

COM

*2

0 to

*2

1

COM

0

3 2

*2

7 (Lower Nos.)

COM *2

0 to

18

*2

5

COM

4

7 6

COM

Other Extension Units and Options

0

3

17 Extension Power Supply Unit

7 6 5 4 3 2 1 0

FX-16E-TB

COM (19) (9) COM *2 *2

7 (18) (8) 6 (17) (7) 5 (16) (6) 4 (15) (5) 3 (14) (4) 2 (13) (3) 1 (12) (2) 0 (11) (1)

16 Input/Output Extension Blocks

1

6 5

Input/Output Powered Extension Units

(20) (10) COM (19) (9) COM *2 7 (18) (8) 7 6 (17) (7) 6 5 (16) (6) 5 4 (15) (5) 4 3 (14) (4) 3 2 (13) (3) 2 1 (12) (2) 1 0 (11) (1) 0

FX-32E-TB

*1

High-Speed Counters

20.5

20.5 FX-16E-TB, FX-32E-TB

COM *2

7 (Higher Nos.)

*1 "24+" when connected to FX2N-16EX-C. *2 " " when connected to FX2N-16EX-C.

19 Display Module

20 Terminal Block

321

Page 328

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.5 FX-16E-TB, FX-32E-TB

20.5.2 Example of input external wiring

WIRING PRECAUTIONS •

Do not wire vacant terminals externally. Doing so may damage the product.

1. When connected to an FX2N-16EX-C (sink input) input extension block 0 to Input numbers in the FX2N-16EX-C 1 0 24+ 24+

7 (Lower Nos.)

3

7

5

2

4

24+ 1 3 24+ 0 2

0 to

1

6

5

3

0

7

4

5

2

1

6

7 (Higher Nos.)

4

3

0

7 6

5

2

7

4

6

24V DC

20.5.3 Output external wiring WIRING PRECAUTIONS •

Do not wire vacant terminals externally. Doing so may damage the product.

1. When connected to an FX2N-16EYT-C (sink output) output extension block

0 to PLC's output No.

3

0

5

2

1

4

3 2

1

7 6

0

3 2

5 4

7 6

COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM

MC1

322

7 (Higher Nos.)

COM

0

24V DC

0 to

COM 1

Vacant terminal

7 (Lower Nos.)

MC2

Page 329

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

11

FX-16EX-A1-TB

High-Speed Counters

20.6

20.6 FX-16EX-A1-TB

The FX-16EX-A1-TB is used by connecting it to the FX2N series input extension block (24V DC). Input Connector Connectable models

12

FX2N-16EX-C (sink input)

Output Wiring

The applications shown below are not supported. Unsupported Applications High-speed processing

High-speed counter, input interruption, pulse catch, speed detection (SPD) instruction Input matrix (MTR) instruction, digital switch (DSW) instruction

Other

Absolute current value read (ABS) instruction

13 Wiring for Various Uses

Time division inputs

20.6.1 Specifications Item

AC Input Type

14 Test Run, Maintenance, Troubleshooting

0 to 7 Photocoupler 100V AC

CN1 Connector side

Input/output circuitry

COMn Terminal block 100 to 120V AC +10%, -15% 50/60Hz

Input signal current

4.7mA / 100V AC 50Hz 6.2mA / 110V AC 60Hz

Input impedance

Approx. 21k Approx. 18k

/ 50Hz / 60Hz

ON

3.8mA / 80V AC or more

OFF

1.7mA / 30V AC or more 25 to 30ms

Input signal format

Voltage contact

Circuit isolation

Photocoupler isolation

Input operation display

No input LEDs (equipped with 24V power supply LED indicator)

Power consumption

1.2W (48mA 24V DC)*2

*1.

This response time does not include the response delay at the PLC.

*2.

3.9W (160mA, 24V DC) is required when connected to the FX2N-16EX-C.

17 Extension Power Supply Unit

Response time*1

16 Input/Output Extension Blocks

Input sensitivity

15

External wiring

Input/Output Powered Extension Units

Input signal voltage

Fuse

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

323

Page 330

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.6 FX-16EX-A1-TB

20.6.2 Internal circuit

Photocoupler

Photocoupler

COM 7 6 5 4 3 2 1 0

CN1 (20) (10) (19) (9) COM (18) (8) 7 (17) (7) 6 (16) (6) 5 (15) (5) 4 (14) (4) 3 (13) (3) 2 (12) (2) 1 (11) (1) 0

0 to

3

Photocoupler

Photocoupler

4 to

7

0 to

3

4 to

7

24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 0 to

7 Lower numbers

0 to

7 Higher numbers

20.6.3 Example of input external wiring

PLC input No.

0 to

3

4 to

7

0 to

3

4 to

7

Photo-coupler power supply 24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 100 to 120V AC 24V DC

324

Page 331

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.7 FX-16EYR-TB

FX-16EYR-TB

High-Speed Counters

20.7

11

The FX-16EYR-TB is used by connecting it to the FX2N series output extension block (transistor). Output Connector Connectable models

12

FX2N-16EYT-C (sink output)

Output Wiring

The applications shown below are not supported. Unsupported Applications Pulse outputs Time division inputs

Input matrix (MTR) instruction, digital switch (DSW) instruction

Time division output

Seven segment with latch (SEGL) instruction

20.7.1 Specifications

14 Test Run, Maintenance, Troubleshooting

Item

Relay output

24+ Input/output circuitry

24V DC 5mA

0 to 7

15

LED

COMn

Input/Output Powered Extension Units

CN1 Connector side

Fuse

External wiring Load voltage

250V AC or less, 30V DC or less

Min. load Open-circuit current

2A / point The total load current of resistance loads per common terminal should be the following value. • 4 output points/common terminal : 8A or less 80 VA 5V DC, 2mA Reference value leakage

Approx. 10ms

Circuit isolation

Mechanical isolation

Operation indicators

Supplying power to the relay coil will light the LED indicator lamp on panel.

Power consumption

1.92W (80mA 24V DC)

17 Extension Power Supply Unit

Response time*1

*1.

16 Input/Output Extension Blocks

Max. Resistance load load Inductive load

13 Wiring for Various Uses

Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation (PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction

This response time does not include the response delay at the PLC.

18 Other Extension Units and Options

19 Display Module

20 Terminal Block

325

Page 332

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.7 FX-16EYR-TB

20.7.2 Internal circuit

COM 7 6 5 4 3 2 1 0

(20) (10) (19) (9) COM (18) (8) 7 (17) (7) 6 (16) (6) 5 (15) (5) 4 (14) (4) 3 (13) (3) 2 (12) (2) 1 (11) (1) 0

0 1 2 3

4 5 6 7

0 1 2 3

4 5 6 7

24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 0 to

7 Lower numbers

0 to

7 Higher numbers

20.7.3 Example of output external wiring 0 to PLC output No.

0 1 2 3

7 Lower numbers 4 5 6 7

0 to 0 1 2 3

7 Higher numbers 4 5 6 7

Relay power supply 24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4

Fuse 24V DC

326

Fuse

Page 333

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.7 FX-16EYR-TB

11 High-Speed Counters

20.7.4 External wiring precautions 1. Protection circuit for load short-circuits Load

0 to 7

12

Fuse

Output Wiring

A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.

COMn Terminal block

2. Contact protection circuit for inductive loads

1) DC circuit Connect a diode (for commutation) parallel to the load. The diode (for commutation) must comply with the following specifications. Reverse voltage

5 to 10 times of the load voltage

Forward current

Load current or more

PLC output contact

Diode (for commutation)

15 Input/Output Powered Extension Units

2) AC circuit Connect the surge absorber (combined CR components such as a surge killer and spark killer, etc.), parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table

14 inductive load

Test Run, Maintenance, Troubleshooting

Guide inductive load PLC output contact

Surge absorber below for other specifications.

16 Input/Output Extension Blocks

Guide Static electricity capacity

Approx. 0.1 F

Forward current

Approx. 100 to 200

Reference Manufacturer

CR-10201

Manufacturer

17

Model name

Rubycon Corporation

250MCRA104100M B0325

3. Interlock Interlock

Forward limit Forward

PLC output contact Reverse limit

PLC output contact

Reverse

4. In-phase

18 Other Extension Units and Options

For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs as shown to the right.

Extension Power Supply Unit

Okaya Electric Industries Co., Ltd.

Model name

13 Wiring for Various Uses

An internal protection circuit for the relays is not provided for the relay output circuit in the terminal block. It is recommended to use inductive loads with built-in protection circuits. When using loads without built-in protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product life.

19 Display Module

PLC output contacts (*) should be used in an "in-phase" manner.

*

Bad

*

20

*

Terminal Block

Good

*

327