Page 326
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.4 Installation Work
20.4.4 Connection to terminal block 1. Terminal Screw Size The product terminal screws are as shown in the table below. Model Name
Terminal Screw Size
FX-16E-TB, FX-32E-TB FX-16EX-A1-TB FX-16EYR-TB FX-16EYS-TB FX-16EYT-TB, FX-16EYT-H-TB
M3.5
2. Wire end treatment and tightening torque Use solderless terminals of the following size. Tighten the terminals to a torque of 0.5 N•m to 0.8 N•m. • When 1 wire is connected to 1 terminal: Use a crimp terminal of the size shown below, and install it as shown in the lower right figure. Terminal Crimp 3.7(0.15") screw terminal
6.8mm(0.27") or less 3.7(0.15") 6.8mm(0.27") or less
Terminal
• When 2 wires are connected to 1 terminal: Use a crimp terminal of the size shown below, and install it as shown in the lower right figure.
3.7(0.15") 6.8mm(0.27") or less
Terminal Crimp screw terminal
6.0mm(0.24") or more 3.7(0.15")
6.8mm(0.27") or less
320
Terminal
6.0mm(0.24") or more
Page 327
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
11
FX-16E-TB, FX-32E-TB The FX-16E-TB and FX-32E-TB items must be connected using an FX2N series input/output connector type extension block. Input Connector
12
Output Connector
FX2N-16EX-C (sink input)
FX2N-16EYT-C (sink output)
Output Wiring
Connectable models
20.5.1 Internal circuit 0 to
7 (Lower Nos.)
1
*1
0
3 2
5
COM
4
COM
7 (Higher Nos.)
*2
7 6
*2
1
COM
0
COM
*2
3 2
4
COM
*2
13
*2
5
COM
7 6
COM
Wiring for Various Uses
CN2
0 to
*2
*1
COM
*2
*2
*1
14
*2
Test Run, Maintenance, Troubleshooting
15 0
2 1
0
CN1
4 3
2
4 3
7 6
5
7
*1
(20) (10)
*1
*1
*2
1 2
*1
*2
5
COM COM
4
7 6
COM
*2
0 to
*2
1
COM
0
3 2
*2
7 (Lower Nos.)
COM *2
0 to
18
*2
5
COM
4
7 6
COM
Other Extension Units and Options
0
3
17 Extension Power Supply Unit
7 6 5 4 3 2 1 0
FX-16E-TB
COM (19) (9) COM *2 *2
7 (18) (8) 6 (17) (7) 5 (16) (6) 4 (15) (5) 3 (14) (4) 2 (13) (3) 1 (12) (2) 0 (11) (1)
16 Input/Output Extension Blocks
1
6 5
Input/Output Powered Extension Units
(20) (10) COM (19) (9) COM *2 7 (18) (8) 7 6 (17) (7) 6 5 (16) (6) 5 4 (15) (5) 4 3 (14) (4) 3 2 (13) (3) 2 1 (12) (2) 1 0 (11) (1) 0
FX-32E-TB
*1
High-Speed Counters
20.5
20.5 FX-16E-TB, FX-32E-TB
COM *2
7 (Higher Nos.)
*1 "24+" when connected to FX2N-16EX-C. *2 " " when connected to FX2N-16EX-C.
19 Display Module
20 Terminal Block
321
Page 328
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.5 FX-16E-TB, FX-32E-TB
20.5.2 Example of input external wiring
WIRING PRECAUTIONS •
Do not wire vacant terminals externally. Doing so may damage the product.
1. When connected to an FX2N-16EX-C (sink input) input extension block 0 to Input numbers in the FX2N-16EX-C 1 0 24+ 24+
7 (Lower Nos.)
3
7
5
2
4
24+ 1 3 24+ 0 2
0 to
1
6
5
3
0
7
4
5
2
1
6
7 (Higher Nos.)
4
3
0
7 6
5
2
7
4
6
24V DC
20.5.3 Output external wiring WIRING PRECAUTIONS •
Do not wire vacant terminals externally. Doing so may damage the product.
1. When connected to an FX2N-16EYT-C (sink output) output extension block
0 to PLC's output No.
3
0
5
2
1
4
3 2
1
7 6
0
3 2
5 4
7 6
COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM
MC1
322
7 (Higher Nos.)
COM
0
24V DC
0 to
COM 1
Vacant terminal
7 (Lower Nos.)
MC2
Page 329
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
11
FX-16EX-A1-TB
High-Speed Counters
20.6
20.6 FX-16EX-A1-TB
The FX-16EX-A1-TB is used by connecting it to the FX2N series input extension block (24V DC). Input Connector Connectable models
12
FX2N-16EX-C (sink input)
Output Wiring
The applications shown below are not supported. Unsupported Applications High-speed processing
High-speed counter, input interruption, pulse catch, speed detection (SPD) instruction Input matrix (MTR) instruction, digital switch (DSW) instruction
Other
Absolute current value read (ABS) instruction
13 Wiring for Various Uses
Time division inputs
20.6.1 Specifications Item
AC Input Type
14 Test Run, Maintenance, Troubleshooting
0 to 7 Photocoupler 100V AC
CN1 Connector side
Input/output circuitry
COMn Terminal block 100 to 120V AC +10%, -15% 50/60Hz
Input signal current
4.7mA / 100V AC 50Hz 6.2mA / 110V AC 60Hz
Input impedance
Approx. 21k Approx. 18k
/ 50Hz / 60Hz
ON
3.8mA / 80V AC or more
OFF
1.7mA / 30V AC or more 25 to 30ms
Input signal format
Voltage contact
Circuit isolation
Photocoupler isolation
Input operation display
No input LEDs (equipped with 24V power supply LED indicator)
Power consumption
1.2W (48mA 24V DC)*2
*1.
This response time does not include the response delay at the PLC.
*2.
3.9W (160mA, 24V DC) is required when connected to the FX2N-16EX-C.
17 Extension Power Supply Unit
Response time*1
16 Input/Output Extension Blocks
Input sensitivity
15
External wiring
Input/Output Powered Extension Units
Input signal voltage
Fuse
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
323
Page 330
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.6 FX-16EX-A1-TB
20.6.2 Internal circuit
Photocoupler
Photocoupler
COM 7 6 5 4 3 2 1 0
CN1 (20) (10) (19) (9) COM (18) (8) 7 (17) (7) 6 (16) (6) 5 (15) (5) 4 (14) (4) 3 (13) (3) 2 (12) (2) 1 (11) (1) 0
0 to
3
Photocoupler
Photocoupler
4 to
7
0 to
3
4 to
7
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 0 to
7 Lower numbers
0 to
7 Higher numbers
20.6.3 Example of input external wiring
PLC input No.
0 to
3
4 to
7
0 to
3
4 to
7
Photo-coupler power supply 24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 100 to 120V AC 24V DC
324
Page 331
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.7 FX-16EYR-TB
FX-16EYR-TB
High-Speed Counters
20.7
11
The FX-16EYR-TB is used by connecting it to the FX2N series output extension block (transistor). Output Connector Connectable models
12
FX2N-16EYT-C (sink output)
Output Wiring
The applications shown below are not supported. Unsupported Applications Pulse outputs Time division inputs
Input matrix (MTR) instruction, digital switch (DSW) instruction
Time division output
Seven segment with latch (SEGL) instruction
20.7.1 Specifications
14 Test Run, Maintenance, Troubleshooting
Item
Relay output
24+ Input/output circuitry
24V DC 5mA
0 to 7
15
LED
COMn
Input/Output Powered Extension Units
CN1 Connector side
Fuse
External wiring Load voltage
250V AC or less, 30V DC or less
Min. load Open-circuit current
2A / point The total load current of resistance loads per common terminal should be the following value. • 4 output points/common terminal : 8A or less 80 VA 5V DC, 2mA Reference value leakage
Approx. 10ms
Circuit isolation
Mechanical isolation
Operation indicators
Supplying power to the relay coil will light the LED indicator lamp on panel.
Power consumption
1.92W (80mA 24V DC)
17 Extension Power Supply Unit
Response time*1
*1.
16 Input/Output Extension Blocks
Max. Resistance load load Inductive load
13 Wiring for Various Uses
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation (PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction
This response time does not include the response delay at the PLC.
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
325
Page 332
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.7 FX-16EYR-TB
20.7.2 Internal circuit
COM 7 6 5 4 3 2 1 0
(20) (10) (19) (9) COM (18) (8) 7 (17) (7) 6 (16) (6) 5 (15) (5) 4 (14) (4) 3 (13) (3) 2 (12) (2) 1 (11) (1) 0
0 1 2 3
4 5 6 7
0 1 2 3
4 5 6 7
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4 0 to
7 Lower numbers
0 to
7 Higher numbers
20.7.3 Example of output external wiring 0 to PLC output No.
0 1 2 3
7 Lower numbers 4 5 6 7
0 to 0 1 2 3
7 Higher numbers 4 5 6 7
Relay power supply 24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
Fuse 24V DC
326
Fuse
Page 333
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.7 FX-16EYR-TB
11 High-Speed Counters
20.7.4 External wiring precautions 1. Protection circuit for load short-circuits Load
0 to 7
12
Fuse
Output Wiring
A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.
COMn Terminal block
2. Contact protection circuit for inductive loads
1) DC circuit Connect a diode (for commutation) parallel to the load. The diode (for commutation) must comply with the following specifications. Reverse voltage
5 to 10 times of the load voltage
Forward current
Load current or more
PLC output contact
Diode (for commutation)
15 Input/Output Powered Extension Units
2) AC circuit Connect the surge absorber (combined CR components such as a surge killer and spark killer, etc.), parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table
14 inductive load
Test Run, Maintenance, Troubleshooting
Guide inductive load PLC output contact
Surge absorber below for other specifications.
16 Input/Output Extension Blocks
Guide Static electricity capacity
Approx. 0.1 F
Forward current
Approx. 100 to 200
Reference Manufacturer
CR-10201
Manufacturer
17
Model name
Rubycon Corporation
250MCRA104100M B0325
3. Interlock Interlock
Forward limit Forward
PLC output contact Reverse limit
PLC output contact
Reverse
4. In-phase
18 Other Extension Units and Options
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC's internal programs as shown to the right.
Extension Power Supply Unit
Okaya Electric Industries Co., Ltd.
Model name
13 Wiring for Various Uses
An internal protection circuit for the relays is not provided for the relay output circuit in the terminal block. It is recommended to use inductive loads with built-in protection circuits. When using loads without built-in protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product life.
19 Display Module
PLC output contacts (*) should be used in an "in-phase" manner.
*
Bad
*
20
*
Terminal Block
Good
*
327