Page 318

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20. Terminal Block

DESIGN PRECAUTIONS •

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

DESIGN PRECAUTIONS •

•

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.

INSTALLATION PRECAUTIONS •

312

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock.

Page 319

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

11 High-Speed Counters

INSTALLATION PRECAUTIONS •

•

Terminal block

• • •

13

Install the product on a flat surface. If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities. When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Be sure to remove the dust proof sheet from the PLC's ventilation port when installation work is completed. Failure to do so may cause fire, equipment failures or malfunctions. Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely to their designated connectors. Loose connections may cause malfunctions. Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause device failures or malfunctions. - Peripheral devices, expansion boards, and special adapters - Extension units/blocks and the FX Series terminal block - Battery and memory cassette

14

• •

17

WIRING PRECAUTIONS

• •

Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Do not wire vacant terminals externally. Doing so may damage the product. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.

18 Other Extension Units and Options

•

Extension Power Supply Unit

•

16 Input/Output Extension Blocks

•

Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.

15 Input/Output Powered Extension Units

WIRING PRECAUTIONS

Test Run, Maintenance, Troubleshooting

•

Main unit, FX2N Series I/O extension unit/block, and FX2N/FX3U Series DIN rail or direct mounting special extension block/special adapter

Wiring for Various Uses

•

DIN rail only

12 Output Wiring

•

Use the product within the generic environment specifications described in Section 4.1 of this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions. Install the product securely using a DIN rail or mounting screws.

19 Display Module

20 Terminal Block

313

Page 320

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.1

20.1 Outline

Outline A terminal block is used to convert connector type input/output terminals into a terminal block. Moreover, dedicated input and output terminal blocks (built-in element types) can be used to receive AC input signals for conversion to relay / transistor / triac output types.

Optional cable or user-fabricated cable Terminal block

314

Terminal block

Page 321

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.1 Outline

11

The connection destinations shown below are products which can be connected by "connector connector" cables. An individual-wire type can also be used for wiring to the terminal blocks of PLC-side input/output products.

FX-16E-TB FX-32E-TB

Number of Input Points

Number of Output Points

Function

16 input points or 16 output points

Connects directly to PLC input/output 32 input points, terminals. 32 output points, or 16 input & 16 output points

Connection Destination

Drive Power Supply

FX2N-16EX-C (sink input) FX2N-16EYT-C (sink output)

*1

12 Output Wiring

Model Name

High-Speed Counters

20.1.1 Product configuration

13

16

-

100V AC input type

FX2N-16EX-C (sink input)

*4

FX-16EYR-TB*3

-

16

Relay output type

FX2N-16EYT-C (sink output)

24V DC 80mA

FX-16EYS-TB*3

-

16

Triac output type

FX2N-16EYT-C (sink output)

24V DC 112mA

FX-16EYT-TB*3

-

16

Transistor output (sink) FX2N-16EYT-C (sink output) type

24V DC 112mA

14

FX-16EYT-H-TB*3

-

16

Transistor output (sink) FX2N-16EYT-C (sink output) type

24V DC 112mA

Test Run, Maintenance, Troubleshooting

Wiring for Various Uses

FX-16EX-A1-TB*2

*1.

A power supply for the input circuit is required when connected to the FX2N-16EX-C. The current consumption is shown in the table below.

*2.

Power Supply Voltage

Current Consumption

24V DC

112mA

15 Input/Output Powered Extension Units

FX2N-16EX-C

The applications shown below are not supported. Unsupported Applications High-speed processing

High-speed counter, input interruption, pulse catch, speed detection (SPD) instruction

16

Other

*3.

Input/Output Extension Blocks

Time division Input matrix (MTR) instruction, digital switch (DSW) instruction inputs Absolute current value read (ABS) instruction

The applications shown below are not supported. Unsupported Applications

Time division Input matrix (MTR) instruction, digital switch (DSW) instruction inputs Time division Seven segment with latch (SEGL) instruction output

18 Other Extension Units and Options

*4.

A power supply for the input circuit is required when connected to the FX2N-16EX-C. The current consumption is shown in the table below. FX2N-16EX-C

17 Extension Power Supply Unit

Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation (PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction, Pulse outputs absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction

Power Supply Voltage

Current Consumption

24V DC

160mA

19 Display Module

20 Terminal Block

315

Page 322

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.2

20.2 External Dimensions and Component Names

External Dimensions and Component Names FX-16E-TB

FX-32E-TB 150(5.91") 55(2.17")

FX-16EYR-TB FX-16EYS-TB FX-16EYT-TB, FX-16EYT-H-TB

FX-16EX-A1-TB

150(5.91") 55(2.17")

55(2.17")

150(5.91")

Units: Accessories: No.

316

45(1.78")

55(2.17")

150(5.91")

mm (inches) Input/output No. labels, terminal block arrangement cards

Name

Remarks

[1]

CN1 connector

[2]

CN2 connector

Present at FX-32E-TB.

-

[3]

Operation indicator LED

Present at FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-TB, FX-16EYT-H-TB.

[4]

POWER LED

Present at FX-16EX-A1-TB.

[5]

CN2 terminal block (M3.5 screws)

Present at FX-32E-TB.

[6]

CN1 terminal block (M3.5 screws)

-

[7]

Nameplate

-

[8]

DIN rail mounting groove (DIN rail width: 35mm(1.38"))

-

[9]

DIN rail mounting hook

-

Page 323

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

11

Terminal Layout

High-Speed Counters

20.3

20.3 Terminal Layout

1. FX-16E-TB When connected to the FX2N-16EYT-C

12

1

Higher numbers

13

3 COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM

2

Wiring for Various Uses

0

Output Wiring

Lower numbers

When connected to the FX2N-16EX-C

14 24+ 1 3 24+ 0 2

5

Higher numbers 7

4

Test Run, Maintenance, Troubleshooting

Lower numbers 1

6

3

0

5

2

7

4

6

15

2. FX-32E-TB

Input/Output Powered Extension Units

When connected to the FX2N-16EYT-C Lower numbers CN2

1 0

2

Higher numbers

3 COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM

16 Input/Output Extension Blocks

CN1 CN2

Lower numbers 1 0

2

Extension Power Supply Unit

CN1

17

Higher numbers

3 COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM

When connected to the FX2N-16EX-C Lower numbers 24+ 1 3 24+ 0 2

5 4

7 6

1 0

3 2

5 4

18 7

Other Extension Units and Options

CN2

Higher numbers

6

CN1 CN2

19 CN1

24+ 1 3 24+ 0 2

5 4

Higher numbers 7

6

Display Module

Lower numbers 1 0

3 2

5 4

7 6

20 Terminal Block

317

Page 324

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

20.3 Terminal Layout

3. FX-16EX-A1-TB

Lower numbers

Higher numbers

24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4

4. FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-TB, FX-16EYT-H-TB

Lower numbers

Higher numbers

24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4

318

Page 325

FX3G Series Programmable Controllers

20 Terminal Block

User's Manual - Hardware Edition

11

Installation Work → Refer to Section 8.1 for installation location.

20.4.1 Installation

High-Speed Counters

20.4

20.4 Installation Work

12 Output Wiring

1 Turn OFF all power supplies connected to the PLC, input/output devices, and terminal blocks.

2 Align the top side of the "DIN rail mounting groove"

13 Wiring for Various Uses

(refer to Fig.1 at right) with the DIN rail.

3 Press the product onto the DIN rail (refer to Fig.2 at right).

14 Test Run, Maintenance, Troubleshooting

20.4.2 Removal

1 Turn the power supply OFF. 2 Disconnect the wiring and input/output cables. 3 Place a flathead screwdriver against the DIN rail

15 Input/Output Powered Extension Units mounting hook in the posture shown (refer to Fig.1 at right)

16 Input/Output Extension Blocks

4 Move the flathead screwdriver in direction shown at right (refer to Fig.2) to detach the DIN rail mounting hook from the DIN rail.

5 Remove the product from the DIN rail.

17 Extension Power Supply Unit

20.4.3 Input/output cable connection

18 Other Extension Units and Options

The terminal block's CN1 and CN2 connectors comply with the MIL-83503 standard. → Refer to Subsection 9.2.2 for input/output cable information

19 Display Module

Input/output cable

20 Terminal Block

Terminal block

319