Page 318
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20. Terminal Block
DESIGN PRECAUTIONS •
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents. 1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits). 2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 3) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case. 4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS •
•
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions. Install module so that excessive force will not be applied to peripheral device connectors. Failure to do so may result in wire damage/breakage or PLC failure.
INSTALLATION PRECAUTIONS •
312
Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock.
Page 319
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
11 High-Speed Counters
INSTALLATION PRECAUTIONS •
•
Terminal block
• • •
13
Install the product on a flat surface. If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities. When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Be sure to remove the dust proof sheet from the PLC's ventilation port when installation work is completed. Failure to do so may cause fire, equipment failures or malfunctions. Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely to their designated connectors. Loose connections may cause malfunctions. Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause device failures or malfunctions. - Peripheral devices, expansion boards, and special adapters - Extension units/blocks and the FX Series terminal block - Battery and memory cassette
14
• •
17
WIRING PRECAUTIONS
• •
Connect the DC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Do not wire vacant terminals externally. Doing so may damage the product. When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions. Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product. - The disposal size of the cable end should follow the dimensions described in this manual. - Tightening torque should be between 0.5 and 0.8 N•m.
18 Other Extension Units and Options
•
Extension Power Supply Unit
•
16 Input/Output Extension Blocks
•
Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out. Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.
15 Input/Output Powered Extension Units
WIRING PRECAUTIONS
Test Run, Maintenance, Troubleshooting
•
Main unit, FX2N Series I/O extension unit/block, and FX2N/FX3U Series DIN rail or direct mounting special extension block/special adapter
Wiring for Various Uses
•
DIN rail only
12 Output Wiring
•
Use the product within the generic environment specifications described in Section 4.1 of this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions. Install the product securely using a DIN rail or mounting screws.
19 Display Module
20 Terminal Block
313
Page 320
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.1
20.1 Outline
Outline A terminal block is used to convert connector type input/output terminals into a terminal block. Moreover, dedicated input and output terminal blocks (built-in element types) can be used to receive AC input signals for conversion to relay / transistor / triac output types.
Optional cable or user-fabricated cable Terminal block
314
Terminal block
Page 321
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.1 Outline
11
The connection destinations shown below are products which can be connected by "connector connector" cables. An individual-wire type can also be used for wiring to the terminal blocks of PLC-side input/output products.
FX-16E-TB FX-32E-TB
Number of Input Points
Number of Output Points
Function
16 input points or 16 output points
Connects directly to PLC input/output 32 input points, terminals. 32 output points, or 16 input & 16 output points
Connection Destination
Drive Power Supply
FX2N-16EX-C (sink input) FX2N-16EYT-C (sink output)
*1
12 Output Wiring
Model Name
High-Speed Counters
20.1.1 Product configuration
13
16
-
100V AC input type
FX2N-16EX-C (sink input)
*4
FX-16EYR-TB*3
-
16
Relay output type
FX2N-16EYT-C (sink output)
24V DC 80mA
FX-16EYS-TB*3
-
16
Triac output type
FX2N-16EYT-C (sink output)
24V DC 112mA
FX-16EYT-TB*3
-
16
Transistor output (sink) FX2N-16EYT-C (sink output) type
24V DC 112mA
14
FX-16EYT-H-TB*3
-
16
Transistor output (sink) FX2N-16EYT-C (sink output) type
24V DC 112mA
Test Run, Maintenance, Troubleshooting
Wiring for Various Uses
FX-16EX-A1-TB*2
*1.
A power supply for the input circuit is required when connected to the FX2N-16EX-C. The current consumption is shown in the table below.
*2.
Power Supply Voltage
Current Consumption
24V DC
112mA
15 Input/Output Powered Extension Units
FX2N-16EX-C
The applications shown below are not supported. Unsupported Applications High-speed processing
High-speed counter, input interruption, pulse catch, speed detection (SPD) instruction
16
Other
*3.
Input/Output Extension Blocks
Time division Input matrix (MTR) instruction, digital switch (DSW) instruction inputs Absolute current value read (ABS) instruction
The applications shown below are not supported. Unsupported Applications
Time division Input matrix (MTR) instruction, digital switch (DSW) instruction inputs Time division Seven segment with latch (SEGL) instruction output
18 Other Extension Units and Options
*4.
A power supply for the input circuit is required when connected to the FX2N-16EX-C. The current consumption is shown in the table below. FX2N-16EX-C
17 Extension Power Supply Unit
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation (PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction, Pulse outputs absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction
Power Supply Voltage
Current Consumption
24V DC
160mA
19 Display Module
20 Terminal Block
315
Page 322
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.2
20.2 External Dimensions and Component Names
External Dimensions and Component Names FX-16E-TB
FX-32E-TB 150(5.91") 55(2.17")
FX-16EYR-TB FX-16EYS-TB FX-16EYT-TB, FX-16EYT-H-TB
FX-16EX-A1-TB
150(5.91") 55(2.17")
55(2.17")
150(5.91")
Units: Accessories: No.
316
45(1.78")
55(2.17")
150(5.91")
mm (inches) Input/output No. labels, terminal block arrangement cards
Name
Remarks
[1]
CN1 connector
[2]
CN2 connector
Present at FX-32E-TB.
-
[3]
Operation indicator LED
Present at FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-TB, FX-16EYT-H-TB.
[4]
POWER LED
Present at FX-16EX-A1-TB.
[5]
CN2 terminal block (M3.5 screws)
Present at FX-32E-TB.
[6]
CN1 terminal block (M3.5 screws)
-
[7]
Nameplate
-
[8]
DIN rail mounting groove (DIN rail width: 35mm(1.38"))
-
[9]
DIN rail mounting hook
-
Page 323
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
11
Terminal Layout
High-Speed Counters
20.3
20.3 Terminal Layout
1. FX-16E-TB When connected to the FX2N-16EYT-C
12
1
Higher numbers
13
3 COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM
2
Wiring for Various Uses
0
Output Wiring
Lower numbers
When connected to the FX2N-16EX-C
14 24+ 1 3 24+ 0 2
5
Higher numbers 7
4
Test Run, Maintenance, Troubleshooting
Lower numbers 1
6
3
0
5
2
7
4
6
15
2. FX-32E-TB
Input/Output Powered Extension Units
When connected to the FX2N-16EYT-C Lower numbers CN2
1 0
2
Higher numbers
3 COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM
16 Input/Output Extension Blocks
CN1 CN2
Lower numbers 1 0
2
Extension Power Supply Unit
CN1
17
Higher numbers
3 COM 5 7 COM 1 3 COM 5 7 COM COM 4 6 COM 0 2 COM 4 6 COM
When connected to the FX2N-16EX-C Lower numbers 24+ 1 3 24+ 0 2
5 4
7 6
1 0
3 2
5 4
18 7
Other Extension Units and Options
CN2
Higher numbers
6
CN1 CN2
19 CN1
24+ 1 3 24+ 0 2
5 4
Higher numbers 7
6
Display Module
Lower numbers 1 0
3 2
5 4
7 6
20 Terminal Block
317
Page 324
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
20.3 Terminal Layout
3. FX-16EX-A1-TB
Lower numbers
Higher numbers
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
4. FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-TB, FX-16EYT-H-TB
Lower numbers
Higher numbers
24+ 1 3 COM1 5 7 COM2 1 3 COM3 5 7 COM4 240 2 COM1 4 6 COM2 0 2 COM3 4 6 COM4
318
Page 325
FX3G Series Programmable Controllers
20 Terminal Block
User's Manual - Hardware Edition
11
Installation Work → Refer to Section 8.1 for installation location.
20.4.1 Installation
High-Speed Counters
20.4
20.4 Installation Work
12 Output Wiring
1 Turn OFF all power supplies connected to the PLC, input/output devices, and terminal blocks.
2 Align the top side of the "DIN rail mounting groove"
13 Wiring for Various Uses
(refer to Fig.1 at right) with the DIN rail.
3 Press the product onto the DIN rail (refer to Fig.2 at right).
14 Test Run, Maintenance, Troubleshooting
20.4.2 Removal
1 Turn the power supply OFF. 2 Disconnect the wiring and input/output cables. 3 Place a flathead screwdriver against the DIN rail
15 Input/Output Powered Extension Units mounting hook in the posture shown (refer to Fig.1 at right)
16 Input/Output Extension Blocks
4 Move the flathead screwdriver in direction shown at right (refer to Fig.2) to detach the DIN rail mounting hook from the DIN rail.
5 Remove the product from the DIN rail.
17 Extension Power Supply Unit
20.4.3 Input/output cable connection
18 Other Extension Units and Options
The terminal block's CN1 and CN2 connectors comply with the MIL-83503 standard. → Refer to Subsection 9.2.2 for input/output cable information
19 Display Module
Input/output cable
20 Terminal Block
Terminal block
319