The text of a manual · part 43 of 49

FX3G Series Programmable Controllers User's Manual [Hardware Edition]: 21. Memory Cassette

Pages 341 to 350 of 384, from FX3G Series Programmable Controllers User's Manual [Hardware Edition]

The original document is the PDF (11 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Mitsubishi FX-16EYR

Page 341

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.1 Outline

21 Memory Cassette

21. Memory Cassette

22

• •

Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is attached or detached while the PLC's power is on, the data in the memory may be destroyed, or the memory cassette may be damaged. Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric distributor.

Outline

21.2

Specifications

21.2.1 Electrical specifications

Model Name

Max. Memory Capacity

Memory Type

Max. Allowable Write

PROTECT Switch

Loader Function

Compatible Versions

FX3G-EEPROM-32L

32000 steps (2k/4k/8k/16k selectable)

EEPROM memory

10,000 times

Provided

Provided

1st article (Ver.1.00)

21.2.2 Part names and External dimensions FX3G-EEPROM-32L Units: mm (inches) [8]

[5] 51.2(2.02")

[4] [3] [2] [1]

[7]

[6] 35(1.38")

9.6(0.38")

[1]RD key (Reading: PLC memory cassette) [2]RD LED [3]WR key (writing: memory cassette PLC) [4]WR LED [5]Memory cassette fixing holes (2- 3.2 Mounting holes) [6]PROTECT switch [7]Detachment lever [8]Main unit connector

335

B Instruction List

The memory cassette can be installed at the main unit, and when installed, the memory cassette's internal program is used in place of the internal EEPROM memory. The loader function transfers (reads and writes) programs between the memory cassette and the internal EEPROM.

A Special Devices (M8000-,D8000-)

21.1

Battery

STARTUP AND MAINTENANCE PRECAUTIONS

Page 342

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.3

21.3 Installation

Installation Be sure that the power is OFF when installing the memory cassette.

21.3.1 Installation (when the expansion board/connector conversion adapter is not used together) The FX3G-40MT/ES is used as the main unit in this example.

1 Remove the top cover.

A

Remove the top cover (A in the right figure) as shown in the Top cover(S) right figure. 1

2 Attach the side cover. Attach the side cover (B in the right figure) as shown in the right figure.

B

Caution: - Make sure to attach the side cover before the memory cassette. However, attachment of the side cover is not necessary when using only the loader function and not always connecting the memory cassette. - Attachment of the side cover is not necessary when installing the memory cassette under the top cover (S) of a 40/60-point type main unit.

3 Raise the memory cassette detachment lever. Raise the memory cassette detachment lever ("C").

C

3

4 Attach the memory cassette. Install the memory cassette to the main unit.

4

336

Page 343

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.3 Installation be fixed with provided M3 tapping screws (D in the right figure) to the main unit.This work is not required when fixation is not necessary.

Memory Cassette

5 The memory cassette (E in the right figure) can

21 D

E

22

• Tightening torque : 0.3 to 0.6 N•m

Battery

Caution: - Two types of M3 tapping screws are provided. Use M3 x 8 (shorter) screws. Do not use M3 x 16 (longer) screws because they may damage the main unit.

A

The FX3G-40MT/ES is used as the main unit and the expansion board is used together in this example.

→ For the attachment method, refer to Chapter 8.

Caution: Make sure to attach the expansion board/connector conversion adapter before the memory cassette. Tightening with tapping screws (M3 x 8) is not necessary.

2 Remove the upper connector cover (A in the

A right figure).

2

3 Remove the part B shown in the right figure using snipper, etc.

Caution: Removal of the part B is not necessary when the connector conversion adapter is used together.

4 Raise the memory cassette detachment lever. Raise the memory cassette detachment lever ("C").

B

C 4

337

B Instruction List

1 Attach the expansion board/connector conversion adapter to the main unit.

Special Devices (M8000-,D8000-)

21.3.2 Installation (when the expansion board/connector conversion adapter is used together)

Page 344

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.3 Installation

5 Attach the memory cassette to the option connector of the expansion board/connector conversion adapter. Attach the memory cassette to the option connector (E in the right figure) of the expansion board/connector conversion adapter.

5 E

6 Fix the memory cassette (G in the right figure)

with provided M3 tapping screws (F in the right figure) to the expansion board/connector conversion adapter. • Tightening torque : 0.3 to 0.6 N•m Caution: - Two types of M3 tapping screws are provided. Use M3 x 16 (longer) screws. - Fixation is not necessary when using only the loader function and not always connecting the memory cassette.

338

F G

Page 345

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21

Removal

Memory Cassette

21.4

21.4 Removal

Be sure that the power is OFF when removing the memory cassette.

The FX3G-40MT/ES is used as the main unit in this example.

1 Raise the memory cassette detachment lever. Raise the memory cassette detachment lever ("A").

A B

1

A Special Devices (M8000-,D8000-)

2 Remove the tapping screws (B in the right figure) which fix the memory cassette.

Proceed to the step 3 when the memory cassette is not fixed with tapping screws.

B Instruction List

3 Grasp the detachment lever and pull it. Grasp the detachment lever ("C") and pull it vertically to remove the memory cassette.

C

3

4 Remove the side cover.

D

Remove the side cover (D in the right figure) as shown in the right figure.

4

Caution: The side cover is not attached when the memory cassette is installed under the top cover (S) of a 40/60-point type main unit.

5 Attach the top cover. Attach the top cover (E in the right figure) as shown in the right figure.

22 Battery

21.4.1 Removal (when the expansion board/connector conversion adapter are not used together)

E

339

Page 346

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.4 Removal

21.4.2 Removal (when the expansion board/connector conversion adapter are used together) The FX3G-40MT/ES is used as the main unit and the expansion board is used together in this example.

1 Raise the memory cassette detachment lever. Raise the memory cassette detachment lever ("A").

1

A B

2 Remove the tapping screws (B in the right figure) which fix the memory cassette.

Proceed to the step 3 when the memory cassette is not fixed with tapping screws.

3 Grasp the detachment lever and pull it. Grasp the detachment lever ("D") and pull it vertically to remove the memory cassette.

D

3

4 Attach the upper connector cover (E in the right figure).

E

F

5 Fix the expansion board with the tapping screws (F in the right figure) provided for fixing the memory cassette. • Tightening torque : 0.3 to 0.6 N•m

Caution: - Two types of M3 tapping screws are provided. Use M3 x 8 (shorter) screws. Do not use M3 x 16 (longer) screws removed in the step 2 because they may damage the main unit.

340

Page 347

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21

Saved Data Content

Memory Cassette

21.5

21.5 Saved Data Content

The following data is saved on the memory cassette. Item

Description •

Program Memory

• • •

File registers

Max. 7000 points (0 to 14 blocks, 1 block = 500 points / 500 steps)

Comments and file registers can be created in the memory by setting them in the parameter memory capacity.

• •

Sequence program GX Developer

The maximum number of points for the memory capacity, comments, and file registers, can be specified when the FX3G programming tool is selected. The maximum number of points cannot be specified when a programming tool other than the FX3G is selected.

341

B Instruction List

ER0 to ER23999 (24000 points)

A Special Devices (M8000-,D8000-)

Comments

Extended file registers

*1.

Programming tool *1

Sequence programs User-created sequence programs Max. 3150 points (0 to 63 blocks, 1 block = 50 points / 500 steps)

22 Battery

Parameters

Saving Method

Memory capacity setting - Memory capacity (default setting: 8k steps) 2k/4k/8k/16k/32k steps - Comment capacity - File register capacity Modem initializing settings, Battery mode settings, RUN terminal settings RS/RS2 instructions / computer link function communication settings Positioning settings

Page 348

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.6

21.6 PROTECT Switch

PROTECT Switch

21.6.1 PROTECT switch setting Reading from and writing to memory cassette operations can be performed by using the programming tool. Because sequence programs are written by an electronic format, a special ROM writer and ultraviolet eraser are not required. The PROTECT switch must be turned OFF to enable writing. PROTECT switch

21.6.2 PROTECT switch operation 1. Preparing the operation tools Set the PROTECT switch knob by using the tip of a pair of tweezers, a precision screwdriver, or a tool with a tip width of approx. 0.8mm (0.04"). Do not use objects with round tips, as the round tip can easily slip off the switch knob, possibly resulting in an incorrect setting.

Shape of tool tip

Tool tip

Good Bad

2. Switch operation procedure As shown in the figure below, the switch knob can be "pushed" or "pulled". When setting the switch, do not set it in an intermediate position. Push direction

Switch setting tool Switch knob

OFF ON

Switch case

Pull direction

OFF ON

21.6.3 Precautions when setting and using the switch • Leaving the switch knob at an intermediate position for an extended period can cause an equipment failure.

342

Page 349

FX3G Series Programmable Controllers User's Manual - Hardware Edition

21.7 Memory Cassette <-> PLC (EEPROM Memory) Transfers by Loader Function

21

Memory Cassette <-> PLC (EEPROM Memory) Transfers by Loader Function

Memory Cassette

21.7

21 Memory Cassette

The FX3G-EEPROM-32L loader function ([WR] and [RD] key operation) is explained in this section.

• The loader function is enabled while the PLC is stopped.

21.7.1 Writing (WR: 32L -> PLC) A memory cassette program is written to the PLC's internal EEPROM memory. Required condition: The PLC must be stopped.

(Setting the PROTECT switch to ON (on memory cassette's rear face) prevents accidental overwriting of memory cassette program.) → Refer to Section 21.3 for the installation procedure. • Verify that the PLC power is OFF, then install the memory cassette on the PLC. • Turn the PLC power ON. • Raise the memory cassette's eject lever.

2 Press the [WR] key 1 time.

B Instruction List

1 Install the memory cassette on the main unit.

A Special Devices (M8000-,D8000-)

• When the display module is connected, data can be transferred from the memory cassette by performing the data transfer procedure in the display module. (It is not possible to transfer data from the memory cassette by performing the data transfer procedure in the memory cassette.) → For the data transfer method in the display module, refer to Chapter 20.

22 Battery

• Program transfers (reading/writing) are possible between the memory cassette and the PLC's internal EEPROM memory.

WR LED WR key

The [WR] LED lights, and a preparation status is established. • To cancel, press the [RD] key.

3 Press the [WR] key again. Writing is executed, and the [WR] LED blinks. • It takes several seconds to write data to the built-in EEPROM. The WR LED flickers while data is written.

4 Remove the memory cassette from the main unit. Writing is completed when the [WR] LED goes off. After turning the PLC power OFF, remove the memory cassette from the PLC. → Refer to Section 21.4 for the removal procedure.

343

Page 350

FX3G Series Programmable Controllers

21 Memory Cassette

User's Manual - Hardware Edition

21.8 Operation Precautions

21.7.2 Reading (RD: 32L <- PLC) Programs are read from the PLC's internal RAM memory to the memory cassette. Required condition: The PLC must be stopped, and the PROTECT switch must be OFF.

1 Install the memory cassette on the main unit.

→ Refer to Section 21.3 for the installation procedure.

• Verify that the PLC power is OFF, then install the memory cassette on the PLC. (Set the PROTECT switch to OFF.) • Turn the PLC power ON.

RD LED

• Raise the memory cassette's eject lever.

RD key

2 Press the [RD] key 1 time. The [RD] LED lights, and a preparation status is established. • To cancel, press the [WR] key.

3 Press the [RD] key again. Reading is executed, and the [RD] LED blinks. • It takes several seconds to read data from the built-in EEPROM. The RD LED flickers while data is read.

4 Remove the memory cassette from the main unit. Reading is completed when the [RD] LED goes off. After turning the PLC power OFF, remove the memory cassette from the PLC, then turn the PROTECT switch ON. → Refer to Section 21.4 for the removal procedure.

21.8

Operation Precautions 1. Tapping screws provided for fixing the memory cassette Two types of (longer and shorter) M3 tapping screws are packed together with the memory cassette. Read carefully the installation method described in Section 21.3, and use the proper type.

2. Number of available units Only one memory cassette may be connected to a FX3G main units.

3. EEPROM memory writing count 10,000 writing operations are permitted at the EEPROM memory.

4. Precaution for file register (D) usage Writing to the flash memory occurs at each PLC operation cycle if BMOV instructions are used in a continuous execution format with regard to a file register. To prevent this, be sure to use "pulse execution format" (BMOVP) instructions.

5. Precaution for extended file register (ER) usage Do not use continuous constant-execution RWER instructions with regard to extended file registers. Use the individual instructions only when required.

6. Loader function when the display module is used together When the display module is used together, the loader function is enabled by performing the transfer procedure in the display module. Data is not transferred even if the transfer procedure is performed in the memory cassette. For the data transfer procedure in the display module, refer to Chapter 20.

344