FX3G Series Programmable Controllers User's Manual - Hardware Edition • Result and measures to take - The transfer is not executed if a "PLC is running" message appears. In this case, set the PLC to the STOP state, then perform the step 3) operation described above.
- The transfer is not executed if a "Transfer failed" message appears. In this case, turn the power off, check the memory cassette connection, then attempt the operation again from the first step.
19 Display Module(FX3G-5DM) 19.12 Memory Cassette Transfers
PLC i s r unn i ng
Ca s s e t t e
PLC
Tr ans f e r f a i l ed
- A "Transfer completed" message appears when the transfer is completed. When this message appears, press [OK] or [ESC] to display the "memory cassette transfer screen".
Ca s s e t t e Tr ans f e r c omp l e t e d
5) Press [ESC] to display the "menu screen".
294
PLC
Page 301
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.13 System Information (Restrictions From PLC)
11
Some of the display module functions require system information settings in order to enable program control of these functions. Functions which require the use of system information are listed below. • Operation button ON/OFF information → Refer to Section 19.17 for details.
• Screen saver function → Refer to Section 19.15 for details.
• Monitor/test function - For hexadecimal display of current value: → Refer to Section 19.18 for the setting procedure.
• Display screen protect function → Refer to Section 19.16 for details.
1. System signal 1 Special data register
System Information Device type to be displayed
D
For specified device monitor function
Reference Section 19.14
D
+1
Device No. to be displayed
D
+2
Screen saver setting time (Forced display)
Section 19.15
D
+3
Device for display screen protect function
Section 19.16
D
+4
Not used
-
16 Description
Reference
M
Request Edit of displayed device data
Section 19.14
M
+1
Edition completion response
Section 19.14
M
+2
Screen saver function invalid
Section 19.15
M
+3
Not used
M
+4
[ESC] button ON/OFF ON/OFF [-] button ON/OFF
+5
M
+6
M
+7
M
+8
Device for specifying the "Monitor/Test" menu’s current value and setting the value Section 19.18 display format (hexadecimal or decimal).
M
+9
Specified device monitor display status
M
+10 to 14
Not used
Operation button information
[+] button ON/OFF
Section 19.17
[OK] button ON/OFF
Section 19.14 -
19
19.13.2 System information setting program example
M8002 K50
D8300
System information (system No.1) is set at D50 to D54.
MOV
K50
D8301
System information (system No.2) is set at M50 to M64.
Display Module
The following is a program example in which the system information has been assigned to D50 to D54 and M50 to M64. MOV
18 Other Extension Units and Options
M
17 Extension Power Supply Unit
D8301 = K Occupies 15 points
System Information
Input/Output Extension Blocks
2. System signal 2 Special data register
15 Input/Output Powered Extension Units
D8300 = K Occupies 5 points
Description
14 Test Run, Maintenance, Troubleshooting
Special data register D8300 and D8301 devices with first numbers specified are assigned as system information devices (data register, auxiliary relay). The data register (excluding special data register) should be specified at the system information's "system signal 1", and the auxiliary relay (excluding special auxiliary relay) should be specified at the system information's "system signal 2". Both D8300 and D8301 have default settings of "-1". When D8300 is "-1" the screen saver function becomes effective after 10 minutes. → Refer to Section 19.14 to Section 19.18 for explanations of each system signal.
13 Wiring for Various Uses
19.13.1 System information list
12 Output Wiring
• Specified device monitor function → Refer to Section 19.14 for details.
High-Speed Counters
19.13 System Information (Restrictions From PLC)
20
Initial pulse
Terminal Block
END
295
Page 302
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.14 Specified Device Monitor Function
19.14 Specified Device Monitor Function The specified device monitor function can change the top screen to the monitor/test screen for a device specified by the user. For the specified device monitor function, specify the device type to be displayed in "D " of the system information (system signal 1), and specify the device number to be displayed in "D +1" of the system information (system signal 1). It is necessary to turn ON M to enable the test operation on the specified device monitor screen.
19.14.1 System information - specified device monitor function 1. System signal 1 System Information
D
*1.
Description Device type to be displayed
D +1
Device No. to be displayed*1
Maximum or minimum value of the corresponding device if the device number is set outside the allowable range
The table below shows the device type to be displayed in accordance with the numeric value written in D . If any numeric value outside the range from 1 to 10 is written in D , the specified device monitor function is disabled. Device type
Value stored in D 1
Input(X)
2
Output(X)
3
Auxiliary relay(M)
4
State(S)
5
Timer(T)
6
Counter(C)
7
Data register(D)
8
Data register(DD)
9
Extended register(R)
10
Extended register(DR)
others
Not used
2. System signal 2 System Information M
*1.
296
Description Request Edit of displayed device data ON : Enables the test function. OFF : Disables the test function (and enables only monitoring).
M
+1
Edition completion response*1
M
+4
"ESC" key status
M
+5
"-" key status
M
+6
"+" key status
M
+7
"OK" key status
M
+9
Specified device monitor display status ON : The specified device monitor screen is displayed. OFF : Any screen other than the specified device monitor screen is displayed.
Turns ON after completion of a test operation for a specified device monitor (or when the OK or ESC key operated). To turn OFF, the request edit of a specified device monitor is turned off or it is turned off in the user’s program.
Page 303
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.14 Specified Device Monitor Function
11
The figure below shows differences between the specified device monitor screen and the monitor/test screen. → Refer to Subsection 19.14.5 for a display example of the specified device monitor screen. → Refer to Subsection 19.6.3 for a display example of the monitor/test screen. -Specified Device Monitor Screen
-Monitor/Test Screen
D1 0 0 0
When D1000 is monitored
32767
( Spe c i f i ed )
D1 0 0 0
32767
D1 0 0 1
0
D1 0 0 2
0
D1 0 0 3
0
12 Output Wiring
When D1000 is specified
High-Speed Counters
19.14.2 Differences between specified device monitor screen and monitor/test screen
13 Wiring for Various Uses
In the case of a specified device monitor screen "specified" is displayed.
14
19.14.3 Program example1 (when monitoring/testing a timer)
15
MOV
K50
D8300
System information (system No.1) is set at D50 to D54.
MOV
K50
D8301
System information (system No.2) is set at M50 to M64.
MOV
K5
D50
Sets the device type to "Timer".
16
MOV
K10
D50
Sets the device No. to "T10".
Input/Output Extension Blocks
Input/Output Powered Extension Units
M8002
Test Run, Maintenance, Troubleshooting
In this program example, the device type to be displayed on the specified device monitor screen is set to "timer (T)". Sets the device No. to "T10". For testing the timer T10, turn ON M0 to enable the test operation. In this program example, system information is assigned from D50 to D54 and from M50 to M64.
M50
When M0 turns ON, the test operation for T10 is enabled.
Initial pulse
Test operation enable command M0
17 Extension Power Supply Unit
END
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
297
Page 304
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.14 Specified Device Monitor Function
19.14.4 Program example2 (when monitoring consecutive timers using operation keys) In this program example, the device type to be displayed on the specified device monitor screen is set to "timer (T)". The operation keys [+] and [-] in the display module are available to scroll device numbers T0 to T10 during monitoring. In this program example, system information is assigned from D50 to D54 and from M50 to M64. M8002 MOV
K50
D8300
System information (system No.1) is set at D50 to D54.
MOV
K50
D8301
System information (system No.2) is set at M50 to M64.
MOV
K5
D50
Sets the device type to "Timer".
RST
D51
Resets the device number D51.
INCP
D51
Initial pulse
"+" button ON M56
"-" button ON M55
M55
Specified device monitor screen displayed M59
M56
Specified device monitor screen displayed M59
The timer number is scrolled using the [+] or [-] button while the specified device monitor screen is displayed. DECP
D51
=
K11
D51
MOV
K0
D51
=
K-1
D51
MOV
K10
D51 END
298
The device number is specified within the allowable range.
Page 305
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.14 Specified Device Monitor Function
In this program example, the device type to be displayed on the specified device monitor screen is set to "timer (T)". The operation keys [+] and [-] in the display module are available to scroll device numbers T1, T5, T10 and T20 during monitoring. In this program example, system information is assigned from D50 to D54 and from M50 to M64.
K50
D8300
System information (system No.1) is set at D50 to D54.
MOV
K50
D8301
System information (system No.2) is set at M50 to M64.
MOV
K5
D50
Sets the device type to "Timer".
RST
Z0
Resets the index register.
MOV
K1
D100
MOV
K5
D101
MOV
K10
D102
MOV
K20
D103
INCP
Z0
Initial pulse
15
M56
M59 The timer number is scrolled using the [+] or [-] button while the specified device monitor screen is displayed.
Specified device monitor screen displayed M59 Z0
=
K4
Z0
MOV
K0
Z0
=
K-1
Z0
MOV
K3
Z0
M8000
The device number is specified within the allowable range.
17
The device number to be displayed is specified.
Extension Power Supply Unit
MOV D100Z0 D51 RUN monitor
16 Input/Output Extension Blocks
DECP
Input/Output Powered Extension Units
M55
"-" button ON M55
Transfers the timer device numbers to D100 to D103.
Test Run, Maintenance, Troubleshooting
M56
14
Specified device monitor screen displayed
"+" button ON
13 Wiring for Various Uses
MOV
12 Output Wiring
M8002
High-Speed Counters
19.14.5 Program example3 (when monitoring non-consecutive timers using operation keys)
11
END
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
299
Page 306
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.14 Specified Device Monitor Function
19.14.6 Monitor operation on specified device monitor screen The monitor operation on the specified device monitor screen is common for all devices. It is not possible to monitor extension file registers (ER and DER), file registers (D) and index registers (V and Z). → Refer to Subsection 19.14.5 for a display example of the specified device monitor screen. → Refer to Section 19.18 for the procedure used to display the timer, counter, and data register current values as hexadecimal values. 1) Press the [ESC] button to return to the menu screen. D1 0 0 0
32767
( Spe c i f i ed )
Selected Device Type
Button ESC
All devices except
Operation Description Returns to the "menu screen".
-
Disabled
+
Disabled
OK
Disabled
19.14.7 Specified device monitor screen for monitoring → Refer to Section 19.18 for the procedure used to display the current values as hexadecimal values.
1. Data register [D (16-bit)] / extended register [R (16-bit)] D1 0 0 0
32767
( Spe c i f i ed )
2. Data register [DD (32-bit)] / extended register [DR (32-bit)] D1 0 0 1 , 1 0 0 0
File register (D): The file register (D) current value cannot be directly monitored at the display module.
32767 ( Spe c i f i ed )
3. Timer [T] T
0
TS
R
TN
0
TV
1000
( Spe c i f i ed )
4. Counter [C] C0 to C199 C
0
CS
R
CN
0
CV
1000
( Spe c i f i ed ) C200 to C255 C 20 0
CS
R
U
CN
0
CV
1000
( Spe c i f i ed )
300
Page 307
FX3G Series Programmable Controllers User's Manual - Hardware Edition
19 Display Module(FX3G-5DM) 19.14 Specified Device Monitor Function
11 X010
High-Speed Counters
5. Input [X] / Output [Y] / Auxiliary Relay [M] / State [S] . . . 34567
12
( Spe c i f i ed )
. . . 3 4 5 6 7. . .
( Spe c i f i ed )
Output Wiring
M1 0 0 0
13
To perform the test operation on the specified device monitor screen, it is necessary to turn ON M in the system information (system signal 2). The device test operation is same as the operation in the monitor/test mode. → Refer to Subsection 19.6.1 for the operation method.
Wiring for Various Uses
19.14.8 Test operation on specified device monitor screen
14 Test Run, Maintenance, Troubleshooting
15 Input/Output Powered Extension Units
16 Input/Output Extension Blocks
17 Extension Power Supply Unit
18 Other Extension Units and Options
19 Display Module
20 Terminal Block
301
Page 308
FX3G Series Programmable Controllers
19 Display Module(FX3G-5DM)
User's Manual - Hardware Edition
19.15 Screen saver function
19.15 Screen saver function The screen saver function displays the dedicated screen to prevent burning of the screen when a key operation is not given for the specified time in the display module. For the screen saver function, set the screen saver setting time in "D +2" of the system information (system signal 1). The screen saver function is set as 10 minutes as an initial value in D8300, when "-1" or D +2 is "0".
19.15.1 System information - Screen saver function 1. System signal 10 System Information
D
+2
Description Screen saver setting time (in units of min) -1 or less : Forced screen saver function (to always display the dedicated screen) 0 : 10 minutes (initial value) 1 to 240 : Can be set in units of minute within this range 241 or more : 240 minutes
2. System signal 2 System Information M
+2
Description Screen saver function invalid
19.15.2 Screen saver display When a key operation is not given within the specified screen saver setting time, the dedicated screen shown below appears and scrolls from the right to the left and from the top to the bottom. When a key operation is given while the dedicated screen is displayed, the former screen appears. The key operation given for the first time after the dedicated screen appeared resets the screen saver function, and is invalid as a key operation. Display screen example
The dedicated screen appears Sc r e e n saver
The dedicated screen scrolls until a key operation is given n saver
01 . 10 . 08
Sc r
2 3 : 5 9 : 5 9 ( We n )
The former screen appears after a key operation was given
19.15.3 Program example (screen saver time setting) In this program example, the screen saver time is set to "5 minutes". Use this program as a reference when other time settings are specified. In this program example, system information is assigned from D50 to D54 and from M50 to M64. M8002 MOV
K50
D8300
System information (system No.1) is set at D50 to D54.
MOV
K50
D8301
System information (system No.2) is set at M50 to M64.
MOV
K5
D53
Sets the screen save time "5 minutes".
Initial pulse
END