Page 355

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

21 Memory Cassette

Appendix A: Special Device List

Operation and function

Corresponding special device

PLC Status [M]8000 RUN monitor NO contact

RUN input

-

M8061 Error occurrence

[M]8002 Initial pulse NO contact

M8000

[M]8003 Initial pulse NC contact

M8002

-

-

M8001

-

M8003 1 scan time ON when either M8060, M8061, M8064, M8065, M8066, or M8067 is ON.

D8004

[M]8005 ON when battery voltage is below Battery voltage low the value set in D8006.

D8005

[M]8006 Battery error latch

D8006

[M]8007 [M]8008 [M]8009 24V DC down

Operation and function

Corresponding special device

Clock

[M]8001 RUN monitor NC contact

[M]8004 Error occurrence

Number and name

It is set when battery voltage low is detected. Not used ON when 24V DC power fails in either input/output powered extension unit or extension power supply unit.

D8009

[M]8010

Not used

-

[M]8011 10ms clock pulse

ON and OFF in 10ms cycle (ON: 5ms, OFF: 5ms)

-

[M]8012 100ms clock pulse

ON and OFF in 100ms cycle (ON: 50ms, OFF: 50ms)

-

[M]8013 1sec clock pulse

ON and OFF in 1sec cycle (ON: 500ms, OFF: 500ms)

-

[M]8014 1min clock pulse

ON and OFF in 1min cycle (ON: 30sec, OFF: 30sec)

-

M 8015

Clock stop and preset For real time clock

-

M 8016

Time read display is stopped For real time clock

-

M 8017

30 seconds correction For real time clock

-

[M]8018

Installation detection (Always ON) For real time clock

-

M 8019

Real time clock (RTC) error For real time clock

-

[M]8020 Zero

ON when the result of addition/ subtraction is 0.

-

[M]8021 Borrow

ON when the result of subtraction is less than the min. negative number.

-

M 8022 Carry

ON when 'carry' occurs as a result of addition or when an overflow occurs as a result of shift operation.

-

[M]8023

Not used

-

M 8024*1

BMOV direction specification (FNC 15)

-

M 8025 to M 8027

Not used

-

M 8028

Interrupt permission during FROM/ TO (FNC 78 and 79) instruction execution.

-

[M]8029 ON when operation such as DSW Instruction (FNC 72) is completed. execution complete

-

Flag

*1.

Cleared when PLC switches from RUN to STOP.

349

B Instruction List

Number and name

A Special Devices (M8000-,D8000-)

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

22 Battery

The device numbers and functions of the special auxiliary relays (indicated as "special M" in tables) and special data registers (indicated as "special D" in tables) are shown below. Note that functions of certain devices vary depending on the series of the PLC. Do not use the undefined / blank special auxiliary relays and special data registers in the sequence program since they are occupied by the CPU. In addition, do not activate or write to the devices with brackets on the first letter such as [M]8000 or [D]8001 in the program. → For detailed explanation, refer to the Programming Manual.

Page 356

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Number and name

Operation and function

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

Corresponding special device

PLC Mode M 8030*1 Battery LED OFF M 8031*1 Non-latch memory all clear

M 8032*1 Latch memory all clear

Number and name

If this special auxiliary relay is activated, the ON/OFF image memory of Y, M, S, T, and C, and present values of T, C, D, special data registers and R are cleared to zero. However, file registers (D) in program memory, and extension file registers (ER) in the memory cassette are not cleared.

-

M8050 (Input interrupt) I00

- disable*4

M8051 (Input interrupt) I10

I20 - disable*4

M8053 (Input interrupt) I30 disable*4

M 8034*1

All external output contacts of PLC are turned OFF.

-

M8055 (Input interrupt)

-

I50

-

M8056 (Timer interrupt)

Refer to Programming Manual for details.

M 8037 Forced STOP signal

M8054 (Input interrupt) I40

I6 -

[M]8038 Parameter setting

Communication parameter setting flag (for N:N network setting)

D8176 to D8180

M 8039 Constant scan mode

When M8039 is ON, PLC waits until scan time specified in D8039 and then executes cyclic operation.

D8039

*1.

•

M8052 (Input interrupt)

-

M 8035 Forced RUN mode

- disable*4

When PLC is switched from RUN to STOP, image memory and data memory are retained.

M 8036 Forced RUN signal

Corresponding special device

Interrupt Disable When M8030 set to ON, LED on PLC is not lit even if low battery voltage is detected.

M 8033 Memory hold STOP All outputs disable

Operation and function disable*4 disable*4 disable*4

M8057 (Timer interrupt) I7 disable*4

M8058 (Timer interrupt) I8

If an input interrupt or timer interrupt occurs while a special auxiliary relay for that interrupt (M8050 - M8058) is OFF, a) The interrupt will be accepted. b) The interrupt routine will be processed promptly if it is permitted by the EI (FNC 04) instruction. However, if the DI (FNC 05) instruction disables interrupts, the interrupt program will not be processed until EI (FNC 04) permits the interrupts.

-

-

-

-

-

-

-

- disable*4

M 8059

Executed at END instruction

•

If an input interrupt or timer interrupt occurs while a special auxiliary relay for that interrupt (M8050 - M8058) is ON, the interrupt will not operate. For example, turning M8050 ON disables the I00 interrupt; hence, the interrupt routine is not processed even in an allowable program area.

*4.

Not used

-

Cleared when PLC switches from RUN to STOP.

Step Ladder and Annunciator M 8040 Transfer disable

While M8040 is turned ON, transfer between states is disabled.

-

Transfer from initial state is enabled in automatic operation mode.

-

[M]8042 Start pulse

Pulse output is given in response to a start input.

-

M 8043*2 Zero return complete

Set this in the last state of zero return mode.

-

M 8044*2 Zero point condition

Set this when machine zero return is detected.

-

*2

[M]8041 Transfer start

Error Detection [M]8060

I/O configuration error

D8060

[M]8061

PLC hardware error

D8061

[M]8062

Serial communication error [ch0]

D8062

[M]8063*5 [M]8064

Serial communication error 1 [ch1]*6 Parameter error

D8064

[M]8065

Syntax error

D8065 D8069 D8314 D8315

[M]8066

Ladder error

D8066 D8069 D8314 D8315

Operation error

D8067 D8069 D8314 D8315 D8068 D8312 D8313

M 8045 All output reset disable

Disables the 'all output reset' function when the operation mode is changed.

[M]8046*3 STL state ON

ON when M8047 is ON and either of S0 to S899 or S1000 to S4095 is active.

M8047

[M]8067*7

M 8047*3 STL monitoring enable

D8040 to D8047 are enabled when M8047 is ON.

D8040 to D8047

M 8068

Operation error latch

M 8069*8

I/O bus check

ON when M8049 is ON and either [M]8048*3 Annunciator operate of S900 to S999 is ON. M 8049*2 Annunciator enable

D8049 is enabled when M8049 is ON.

-

D8049 M8048

-

*5.

Cleared when PLC power supply from OFF to ON.

*6.

Serial communication error 2 [ch2] PLC is detected by M8438.

*2.

Cleared when PLC switches from RUN to STOP.

*7.

Cleared when PLC switches from STOP to RUN.

*3.

Executed at END instruction.

*8.

When M8069 is ON, I/O bus check is executed.

350

D8063

Page 357

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

21 Operation and function

Corresponding special device

Parallel Link

Operation and function

M 8071*1

Parallel link Set M8071 when using slave station.

-

[M]8072

Parallel link ON when operating

-

[M]8073

Parallel link ON when M8070 or M8071 setting is incorrect

-

Cleared when PLC switches from STOP to RUN.

Pulse width/Pulse period measurement function

[M]8120

Not used

-

[M]8121*3

RS (FNC 80) instruction: Send wait flag

-

M 8122*3

RS (FNC 80) instruction: Send request

D8122

M 8123*3

RS (FNC 80) instruction: Receive complete flag

D8123

[M]8124

RS (FNC 80) instruction: Carrier detection flag

-

[M]8125

Not used

-

[M]8126

Computer link [ch1]: Global ON

[M]8127

Computer link [ch1]: On-demand send processing

Special Devices (M8000-,D8000-)

-

M 8128

Computer link [ch1]: On-demand error flag

B

M 8129

Computer link [ch1]: On-demand Word/Byte changeover RS (FNC 80) instruction: Time-out check flag

D8127 D8128 D8129

Pulse width/Pulse period measurement setting flag

[M]8076*2

[X000] Pulse width/Pulse period measurement flag

D8074 to D8079

[M]8077*2

[X001] Pulse width/Pulse period measurement flag

D8080 to D8085

[M]8078*2

[X003] Pulse width/Pulse period measurement flag

D8086 to D8091

*3.

[M]8079*2

[X004] Pulse width/Pulse period measurement flag

D8092 to D8097

Positioning [PLSY, PLSR instruction]

M 8080*2

[X000] Pulse period measurement mode

D8074 to D8079

M 8081*2

[X001] Pulse period measurement mode

M 8082*2 M 8083*2

-

M 8145

[Y000] Pulse output stop command

-

D8080 to D8085

M 8146

[Y001] Pulse output stop command

-

[M]8147

-

[X003] Pulse period measurement mode

D8086 to D8091

[Y000] Pulse output monitor (BUSY/READY)

[M]8148

-

[X004] Pulse period measurement mode

D8092 to D8097

[Y001] Pulse output monitor (BUSY/READY)

Inverter Communication Function

Supported in Ver. 1.10 or later.

Flag [M]8090 to [M]8100 Not used

-

Memory Information [M]8101 [M]8102 [M]8103

Cleared when PLC switches from RUN to STOP or RS instruction is OFF.

Not used

[M]8150

Not used

[M]8151*4

Inverter communication in execution [ch1]

D8151

[M]8152*4

Inverter communication error [ch1]

D8152

[M]8153*4

Inverter communication error latch [ch1]

D8153

-

[M]8154

-

[M]8155

Not used

-

-

-

[M]8156*4

Inverter communication in execution [ch2]

D8156

[M]8105

ON when writing to EEPROM memory

-

[M]8157*4

Inverter communication error [ch2]

D8157

[M]8106

Not used

-

[M]8107

Not used

-

[M]8158*4

Inverter communication error latch [ch2]

D8158

[M]8108

Not used

-

[M]8159

Not used

[M]8104

*4.

Output Refresh Error [M]8109

Output refresh error

[M]8110 to [M]8119 Not used

D8109

-

Cleared when PLC switches from STOP to RUN. Supported in Ver. 1.10 or later.

-

351

A

Instruction List

[M]8075*2

22 Battery

M 8070*1

*2.

Corresponding special device

RS (FNC 80) and Computer Link [ch1] Parallel link Set M8070 when using master station.

*1.

Number and name

Memory Cassette

Number and name

Page 358

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Number and name

Operation and function

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

Corresponding special device

Advanced Function M 8160

Number and name

-

[M]8180

8-bit process mode

-

[M]8181

M 8162

High speed parallel link mode

-

[M]8182

[M]8163

-

M 8164

Not used

-

[M]8166

-

M 8167

-

M 8168*1

SMOV (FNC 13) instruction: HEX data handling function

-

[M]8169

Not used

-

*1. *2.

Corresponding special device

N:N Network Not used

M 8161*1*2

M 8165

Operation and function

Cleared when PLC switches from STOP to RUN. Applicable to RS (FNC 80), ASCI (FNC 82), HEX (FNC 83), and CCD (FNC 84) instructions.

Pulse Catch

Not used

-

[M]8183

Data communication error (Master station)

[M]8184

Data communication error (Slave station No.1)

[M]8185

Data communication error (Slave station No.2)

[M]8186

Data communication error (Slave station No.3)

[M]8187

Data communication error (Slave station No.4)

[M]8188

Data communication error (Slave station No.5)

[M]8189

Data communication error (Slave station No.6)

[M]8190

Data communication error (Slave station No.7)

[M]8191

Data communication in execution

D8201 to D8218

M 8170*3

Input X000 pulse catch

-

M 8171*3

Input X001 pulse catch

-

M 8172*3

Input X002 pulse catch

-

M 8173*3

Input X003 pulse catch

-

M 8174*3

Input X004 pulse catch

-

M 8175*3

Input X005 pulse catch

-

[M]8195

-

[M]8196

-

[M]8197

-

M 8198

-

M 8199

-

M 8176 M 8177

*3.

Not used

Cleared when PLC switches from STOP to RUN.

Communication Port Channel Setting M 8178

Parallel link channel switch (OFF: ch1/ON: ch2)

-

M 8179

N:N network channel switch*4

-

*4.

352

The channel is specified by either creating or not creating M8179 in setting program. ch1: not creating M8179 in setting program ch2: creating M8179 in setting program

[M]8192

-

[M]8193

-

[M]8194

Not used

-

Page 359

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

21 Operation and function

Corresponding special device

Counter Up/down Counter Counting Direction

Number and name

Operation and function

Corresponding special device

High Speed Counter Up/down Counter Monitoring

C200

-

[M]8246

C246

-

M 8201

C201

-

[M]8247

C247

-

M 8202

C202

-

[M]8248

C248

M 8203

C203

-

[M]8249

C249

M 8204

C204

-

[M]8250

C250

M 8205

C205

-

[M]8251

C251

M 8206

C206

-

[M]8252

C252

M 8207

C207

-

[M]8253

C253

M 8208

C208

-

[M]8254

C254

-

M 8209

C209

-

[M]8255

C255

-

M 8210

C210

-

[M]8256 to [M]8259 Not used

M 8211

C211

-

Analog Expansion Board (Refer to Appendix A-3 for details)

M 8212

C212

-

M8260 to M8269*1

M 8213

C213

-

M8270 to M8279*1

M 8214

C214

-

M 8215

C215

M 8216

C216

M 8217

C217

M 8218

C218

M 8219

C219

M 8220

C220

-

M 8221

C221

-

M 8222

C222

-

M 8223

C223

-

M 8224

C224

-

M 8225

C225

-

M 8226

C226

-

M 8227

C227

-

M 8228

C228

-

M 8229

C229

-

M 8230

C230

-

M 8231

C231

-

M 8232

C232

-

M 8233

C233

-

M 8234

C234

-

-

-

-

1st expansion board*2

-

B

2nd expansion board*3

-

Analog Special Adapter (Refer to Appendix A-4 for details) M8280 to M8289

1st special adapter*4

-

M8290 to M8299

2nd special adapter*4

-

*1. *2.

*3.

*4.

Supported in Ver. 1.10 or later. 1st expansion board becomes an expansion board connected to BD connector of main units (14/24 point type), or BD1 connector of main units (40/60 point type). 2nd expansion board becomes an expansion board connected to BD2 connector of main units (40/60 point type). Connected analog special adapters are counted from the main unit side.

Flag [M]8312*5

Real time clock data lost error

-

[M]8313 to [M]8328 Not used

-

[M]8329

-

*5.

Instruction execution abnormal end

Backed up against power interruption, and automatically cleared when M8312 itself is cleared or when the clock data is set again.

High Speed Counter Up/down Counter Counting Direction M 8235

C235

-

M 8236

C236

-

M 8237

C237

-

M 8238

C238

M 8239

C239

M 8240

C240

M 8241

C241

M 8242

C242

M 8243

C243

-

M 8244

C244

-

M 8245

C245

-

When M8 is ON, the corresponding C is changed to down mode. • ON: Down count operation • OFF: Up count operation

A

-

353

Instruction List

-

-

Special Devices (M8000-,D8000-)

When M8 is ON, the corresponding C is changed to down mode. • ON: Down count operation • OFF: Up count operation

When C of 1-phase 2input or 2-phase 2-input counter is in down mode, the corresponding M8 turns ON. • OFF:Down count operation • ON:Up count operation

22 Battery

M 8200

Memory Cassette

Number and name

Page 360

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Number and name

Operation and function

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

Corresponding special device

Positioning

Number and name

Operation and function

Corresponding special device

RS2 (FNC 87) [ch0]

[M]8330 to [M]8337 Not used

-

[M]8370

Not used

PLSV (FNC157) instruction: Acceleration/deceleration operation

-

M 8371*2

RS2 (FNC 87) [ch0] Send wait flag

-

[M]8339

Not used

-

M 8372*2

RS2 (FNC 87) [ch0] Send request

D8372

[M]8340

[Y000] Pulse output monitor (ON: BUSY/ OFF: READY)

-

M 8373*2

RS2 (FNC 87) [ch0] Receive complete flag

D8373

M 8341*1

[Y000] Clear signal output function enable

-

[Y000] Zero return direction specification

-

High Speed Counter Function

[Y000] Forward limit

-

[M]8380 to [M]8387 Not used

M 8338*1

M 8342

*1

M 8343

[M]8374 to [M]8378 Not used

M 8344

[Y000] Reverse limit

-

M 8345*1

[Y000] DOG signal logic reverse

-

M 8346*1

[Y000] Zero point signal logic reverse

-

M 8347

Not used

-

[M]8348

[Y000] Positioning instruction activation

-

RS2 (FNC 87) [ch0] Time-out check flag

M 8379

-

M 8389 to M 8391

Not used

-

M 8392

Function changeover device for C248 and C253

-

[M]8393

Not used

-

[M]8394

Not used

-

[M]8395

Function changeover device for C254

-

-

[M]8350

[Y001] Pulse output monitor (ON: BUSY/ OFF: READY)

-

M 8351*1

[Y001] Clear signal output function enable

-

Ring Counter

M 8352*1

[Y001] Zero return direction specification

-

M 8398

M 8353

[Y001] Forward limit

-

[M]8399

M 8354

[Y001] Reverse limit

-

*2.

M 8355*1

[Y001] DOG signal logic reverse

-

M 8356*1

[Y001] Zero point signal logic reverse

-

M 8357

Not used

-

[M]8358

[Y001] Positioning instruction activation

-

M 8359*1

[Y001] Pulse output stop command

-

[M]8360

[Y002] Pulse output monitor (ON: BUSY/ OFF: READY)

-

M 8361*1

[Y002] Clear signal output function enable

-

M 8362*1

[Y002] Zero return direction specification

-

M 8363

[Y002] Forward limit

-

M 8364

[Y002] Reverse limit

-

M 8365*1

[Y002] DOG signal logic reverse

-

M 8366*1

[Y002] Zero point signal logic reverse

-

M 8409

M 8367

Not used

-

*4.

[M]8368

[Y002] Positioning instruction activation

-

M 8369*1

[Y002] Pulse output stop command

-

354

-

-

[M]8388

[Y000] Pulse output stop command

Cleared when PLC switches from RUN to STOP.

-

Contact for high speed counter function change

M 8349*1

*1.

-

[M]8396

Not used

[M]8397

*3.

Ring counter operation (in units of 1ms, 32 bits)*3 Not used

D8398 D8399 -

Cleared when PLC switches from RUN to STOP or when RS2 instruction [ch0] is OFF. 1ms ring counter (D8399, D8398) will operate after M8398 turns ON.

RS2 (FNC 87) [ch1] [M]8400

Not used

-

[M]8401*4

RS2 (FNC 87) [ch1] Send wait flag

-

*4

RS2 (FNC 87) [ch1] Send request

D8402

M 8403*4

RS2 (FNC 87) [ch1] Receive complete flag

D8403

[M]8404

RS2 (FNC 87) [ch1] Carrier detection flag

-

[M]8405

RS2 (FNC 87) [ch1] Data set ready (DSR) flag

-

M 8402

[M]8406 [M]8407

Not used

[M]8408

-

RS2 (FNC 87) [ch1] Time-out check flag

-

Cleared when PLC switches from RUN to STOP or when RS2 instruction [ch1] is OFF.

Page 361

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Appendix A-1 Special Auxiliary Relay (M8000 to M8511)

21 Operation and function

Memory Cassette

Number and name

Corresponding special device

RS2 (FNC 87) [ch2] and Computer Link [ch2] RS2 (FNC 87) [ch2] Send wait flag

-

M 8422*1

RS2 (FNC 87) [ch2] Send request

D8422

M 8423*1

RS2 (FNC 87) [ch2] Receive complete flag

D8423

[M]8424

RS2 (FNC 87) [ch2] Carrier detection flag

-

[M]8425

RS2 (FNC 87) [ch2] Data set ready (DSR) flag

-

[M]8426

Computer link [ch2] Global ON

[M]8427

Computer link [ch2] On-demand send processing

M 8428

Computer link [ch2] On-demand error flag

M 8429

Computer link [ch2] On-demand Word/Byte changeover RS2 (FNC 87) [ch2] Time-out check flag

A

D8427 D8428 D8429

B Instruction List

*1.

22

Special Devices (M8000-,D8000-)

-

[M]8421*1

Battery

[M]8410 to [M]8420 Not used

Cleared when PLC switches from RUN to STOP or when RS2 instruction [ch2] is OFF.

Error Detection [M]8430 to [M]8437 Not used M 8438*2

Serial communication error 2 [ch2]

[M]8439 to [M]8448 Not used [M]8449

Special block error flag

[M]8450 to [M]8459 Not used

D8438 D8449 -

Positioning M 8460 to M8463

Not used

M 8464

DSZR (FNC150), ZRN (FNC156) instructions [Y000] Clear signal device specification function enabled

D8464

M 8465

DSZR (FNC150), ZRN (FNC156) instructions [Y001] Clear signal device specification function enabled

D8465

M 8466

DSZR (FNC150), ZRN (FNC156) instructions [Y002] Clear signal device specification function enabled

D8466

[M]8467 to [M]8511 Not used

*2.

-

-

Cleared when PLC power supply from OFF to ON.

355

Page 362

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Appendix A-2 Special Data Register (D8000 to D8511)

Appendix A-2 Special Data Register (D8000 to D8511) Number and name

Corresponding special device

Content of register

PLC Status Default value is 200ms (in 1ms steps) (Writes from system ROM at power ON) Value overwritten by program is valid after END or WDT instruction execution.

BCD converted 2 6 1 0 0 value Version 1.00 FX3G Series

[D]8001 PLC type and system version

[D]8002 Memory capacity

[D]8003 Memory type

Accumulated instruction-execution time from 0 step (in units of 0.1ms)

-

Minimum value of scan time (in units of 0.1ms)

-

Maximum value of scan time (in units of 0.1ms)

-

D 8013 Second data

0 to 59 seconds (for real time clock)

-

• • • •

2...2K steps 4...4K steps 8...8K steps If 16K steps or more "K8" is written to D8002 and "16" or "32" is written to D8102.

D 8014 Minute data

0 to 59 minutes (for real time clock)

-

D 8015 Hour data

0 to 23 hours (for real time clock)

-

D 8016 Day data

1 to 31 days (for real time clock)

-

D 8017 Month data

1 to 12 months (for real time clock)

-

D 8018 Year data

2 digits of year data (0 to 99) (for real time clock)

-

D 8019 Day-of-the-week data

0 (Sunday) to 6 (Saturday) (for real time clock)

-

[D]8010 Present scan -

[D]8004 Error number M

[D]8005 Battery voltage

D8101

M8002 D8102

-

M8004

8060 to 8068 (when M8004 is ON) 3 0 BCD converted value (in units of 0.1V) Battery voltage present value (Example: 3.0V)

[D]8007

Not used

-

D 8008

Not used

-

[D]8009 24V DC failed device

Minimum input device number of input/output powered extension unit in which 24V DC has failed.

M8006

M8009

D 8020 Input filter adjustment

Input filter value of X000 to X007 (Default: 10ms)

-

[D]8021

-

[D]8022

-

[D]8023 [D]8024

Not used

-

[D]8025

-

[D]8026

-

[D]8027

-

Index Register Z0 and V0

D8003 becomes the undermentioned content.

02H

Indicated value includes waiting time of constant scan operation (when M8039 is activated).

Input Filter M8005

Default: 2.7V (in units of 0.1V) (Writes from system ROM at power ON)

Type of memory time*2

*2.

[D]8006 Low battery voltage detection level

Present value

[D]8011 Minimum scan [D]8012 Maximum scan

Stores the memory type (built-in EEPROM or memory cassette) and the PROTECT switch ON/OFF

BCD converted 8 0 6 0 value time*2 time*2 status of the memory cassette.*1

356

Corresponding special device

Clock

D 8000 Watchdog timer

*1.

Content of register

Number and name

Protect switch

EEPROM memory cassette

OFF

0AH

EEPROM memory cassette

ON

10H

Built-in memory in PLC

-

[D]8028

Value of Z0 (Z) register*3

-

[D]8029

Value of V0 (V) register*3

-

*3.

The values of Z1 to Z7 and V1 to V7 are stored in D8182 to D8195.

Page 363

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Appendix A-2 Special Data Register (D8000 to D8511)

21 Content of register

Corresponding special device

-

[D]8031

Value of analog volume VR2 (Integer from 0 to 255)

-

D 8068*2 [D]8069*2

-

Default: 0 ms (in 1 ms steps) (Writes from system ROM at power ON) Can be overwritten by program

M8039

*2. *3.

Operation error step number latched

M8068

Error step number of M8065 to M8067

M8065 to M8067

Cleared when PLC power supply from OFF to ON. Cleared when PLC switches from STOP to RUN.

Parallel link error time-out check time: 500ms

[D]8070

Pulse width/Pulse period measurement function D 8074*4

Lower

[D]8041*1

D 8075*4

Upper

D 8076*4

Lower

D 8077*4

Upper

D 8078*4

Lower

D 8079*4

Upper

D 8080*4

Lower

D 8081*4

Upper

D 8082*4

Lower

D 8083*4

Upper

D 8084*4

Lower

D 8085*4

Upper

D 8086*4

Lower

D 8087*4

Upper

D 8088*4

Lower

D 8089*4

Upper

D 8090*4

Lower

D 8091*4

Upper

Error Detection (Refer to Subsection 14.6.3 for details)

D 8092*4

Lower

If the unit or block corresponding to a programmed I/O number is not actually loaded, M8060 is set to ON and the first device number of the erroneous block is written to D8060.

D 8093*4

Upper

D 8094*4

Lower

D 8095*4

Upper

D 8096*4

Lower

Example:If X020 is unconnected. BCD converted 1 0 2 0 value Device number 10 to 177

D 8097*4

Upper

M8047

[D]8046*1 ON state number 7 [D]8047*1 ON state number 8 [D]8048

Not used

-

[D]8049*1 On state minimum number

When M8049 is ON, the smallest number out of active annunciator relay ranging from S900 to S999 is stored in D8049.

D]8050 to [D]8059

Not used

*1.

M8049 -

Executed at END instruction

[D]8060

M8060

*4.

-

[X000] Ring counter value for rising edge (1/6 s unit) [X000] Ring counter value for falling edge (1/6 s unit)

M8076 M8080

[X000] Pulse width/Pulse period (10 s unit) [X001] Ring counter value for rising edge (1/6 s unit) [X001] Ring counter value for falling edge (1/6 s unit)

M8077 M8081

[X001] Pulse width/Pulse period (10 s unit) [X003] Ring counter value for rising edge (1/6 s unit) [X003] Ring counter value for falling edge (1/6 s unit)

M8078 M8082

[X003] Pulse width/Pulse period (10 s unit) [X004] Ring counter value for rising edge (1/6 s unit) [X004] Ring counter value for falling edge (1/6 s unit)

M8079 M8083

[X004] Pulse width/Pulse period (10 s unit)

Cleared when PLC switches from STOP to RUN. Supported in Ver. 1.10 or later.

Memory Information

1: Input X 0: Output Y [D]8061

Error code for PLC hardware error

M8061

[D]8062

Error code for PC/PP communication error or serial communication error 0 [ch0]

M8062

[D]8063*2

Error code for serial communication error 1 [ch1]

M8063

[D]8064

Error code for parameter error

M8064

[D]8065

Error code for syntax error

M8065

[D]8066

Error code for ladder error

M8066

[D]8067*3

Error code for operation error

M8067

[D]8101 PLC type and system version

2 6 1 0 0 FX3G PLC

BCD converted value

-

Version 1.00

[D]8102

2......2K steps 4......4K steps 8......8K steps 16....16K steps 32....32K steps

-

[D]8103 to [D]8107

Not used

-

[D]8108

Number of special function blocks connected

-

357

A

B Instruction List

[D]8040*1 ON state number 1

-

Special Devices (M8000-,D8000-)

[D]8071 to [D]8073 Not used

ON state number 2

22

Parallel Link

Stepladder and Annunciator

[D]8042*1 ON state number 3 The smallest number out of active state ranging from S0 to S899 and [D]8043*1 S1000 to S4095 is stored in D8040 ON state number 4 and the second-smallest state number is stored in D8041. [D]8044*1 ON state number 5 Active state numbers are then sequentially stored in registers up [D]8045*1 to D8047 (Max. 8 points). ON state number 6

Corresponding special device

Battery

[D]8030

Value of analog volume VR1 (Integer from 0 to 255)

D 8039 Constant scan duration

Content of register

Error Detection (Refer to Subsection 14.6.3 for details)

Analog Volume and Constant Scan

[D]8032 to [D]8038 Not used

Number and name

Memory Cassette

Number and name

Page 364

FX3G Series Programmable Controllers

Appendix A: Special Device List

User's Manual - Hardware Edition

Number and name

Content of register

Appendix A-2 Special Data Register (D8000 to D8511)

Corresponding special device

Output Refresh Error [D]8109

Number and name

Corresponding special device

Content of register

Inverter Communication Function

Y number where output refresh error occurs

[D]8110 to [D]8119 Not used

M8109

D 8150*4

Response wait time of inverter communication [ch1]

-

[D]8151*4

Step number of instruction during inverter communication [ch1] Default: -1

M8151

-

RS (FNC 80) and Computer Link [ch1] D 8120*1

RS (FNC 80) instruction and computer link [ch1] Communication format setting

-

[D]8152*3*4

Error code for inverter communication [ch1]

M8152

D 8121*1

Computer link [ch1] Station number setting

-

[D]8153*4

M8153

[D]8122*2

RS (FNC 80) instruction: Remaining points of transmit data

Inverter communication error step number latched [ch1] Default: -1

M8122

[D]8154

Not used

-

M8123

D 8155*4

Response wait time of inverter communication [ch2]

-

[D]8156*4

Step number of instruction during inverter communication [ch2] Default: -1

M8156

[D]8157*3*4

Error code for inverter communication [ch2]

M8157

[D]8158*4

Inverter communication error step number latched [ch2] Default: -1

M8158

[D]8159

Not used

[D]8123*2

RS (FNC 80) instruction: Monitoring receive data points

D 8124

RS (FNC 80) instruction: Header <Default: STX>

-

D 8125

RS (FNC 80) instruction: Terminator <Default: ETX>

-

[D]8126

Not used

-

D 8127

Computer link [ch1] Specification of on-demand head device register

D 8128

Computer link [ch1] Specification of on-demand data length register

D 8129*1

RS (FNC 80) instruction, computer link [ch1] Time-out time setting

*1. *2.

M8126 to M8129

[D]8130 to [D]8135 Not used D 8136

Lower

D 8137

Upper

Lower

D 8141

Upper

D 8143

PLSY (FNC 57), PLSR (FNC 59) instructions: Accumulated total number of pulses output to Y000 and Y001

Lower

Upper

-

Not used

D 8140

D 8142

Accumulated number of pulses output to Y000 for PLSY (FNC 57) and PLSR (FNC 59) instructions, or current address of Y000 for positioning instruction Accumulated number of pulses output to Y001 for PLSY (FNC 57) and PLSR (FNC 59) instructions, or current address of Y001 for positioning instruction

[D]8162

Not used

-

[D]8165

-

[D]8166

-

[D]8167

-

[D]8168 [D]8169

*5.

Access restriction status*5

-

Access restriction status Present value

Access restriction status

H**00*7 2nd keyword is not set

Program

Present Monitor value -ing Read Write change *6

*6

-

-

-

-

H**10*7 Write protection

H**12*7

-

All online operation protection

*6

*6

-

-

-

H**20*7 Keyword cancel

Not used

D 8164

H**11*7 Read / write protection

D 8145

-

D 8148

-

[D]8149

-

358

-

-

-

D 8147

-

[D]8161

-

[D]8144 D 8146

[D]8160

[D]8163

Positioning

[D]8139

Cleared when PLC switches from STOP to RUN. Supported in Ver. 1.10 or later.

Advanced Function

Latch device Cleared when PLC switches from RUN to STOP.

[D]8138

*3. *4.

-

*6. *7.

Accesses are restricted by the keyword setting status. "**" indicates areas used by the system.