Page 355
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
21 Memory Cassette
Appendix A: Special Device List
Operation and function
Corresponding special device
PLC Status [M]8000 RUN monitor NO contact
RUN input
-
M8061 Error occurrence
[M]8002 Initial pulse NO contact
M8000
[M]8003 Initial pulse NC contact
M8002
-
-
M8001
-
M8003 1 scan time ON when either M8060, M8061, M8064, M8065, M8066, or M8067 is ON.
D8004
[M]8005 ON when battery voltage is below Battery voltage low the value set in D8006.
D8005
[M]8006 Battery error latch
D8006
[M]8007 [M]8008 [M]8009 24V DC down
Operation and function
Corresponding special device
Clock
[M]8001 RUN monitor NC contact
[M]8004 Error occurrence
Number and name
It is set when battery voltage low is detected. Not used ON when 24V DC power fails in either input/output powered extension unit or extension power supply unit.
D8009
[M]8010
Not used
-
[M]8011 10ms clock pulse
ON and OFF in 10ms cycle (ON: 5ms, OFF: 5ms)
-
[M]8012 100ms clock pulse
ON and OFF in 100ms cycle (ON: 50ms, OFF: 50ms)
-
[M]8013 1sec clock pulse
ON and OFF in 1sec cycle (ON: 500ms, OFF: 500ms)
-
[M]8014 1min clock pulse
ON and OFF in 1min cycle (ON: 30sec, OFF: 30sec)
-
M 8015
Clock stop and preset For real time clock
-
M 8016
Time read display is stopped For real time clock
-
M 8017
30 seconds correction For real time clock
-
[M]8018
Installation detection (Always ON) For real time clock
-
M 8019
Real time clock (RTC) error For real time clock
-
[M]8020 Zero
ON when the result of addition/ subtraction is 0.
-
[M]8021 Borrow
ON when the result of subtraction is less than the min. negative number.
-
M 8022 Carry
ON when 'carry' occurs as a result of addition or when an overflow occurs as a result of shift operation.
-
[M]8023
Not used
-
M 8024*1
BMOV direction specification (FNC 15)
-
M 8025 to M 8027
Not used
-
M 8028
Interrupt permission during FROM/ TO (FNC 78 and 79) instruction execution.
-
[M]8029 ON when operation such as DSW Instruction (FNC 72) is completed. execution complete
-
Flag
*1.
Cleared when PLC switches from RUN to STOP.
349
B Instruction List
Number and name
A Special Devices (M8000-,D8000-)
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
22 Battery
The device numbers and functions of the special auxiliary relays (indicated as "special M" in tables) and special data registers (indicated as "special D" in tables) are shown below. Note that functions of certain devices vary depending on the series of the PLC. Do not use the undefined / blank special auxiliary relays and special data registers in the sequence program since they are occupied by the CPU. In addition, do not activate or write to the devices with brackets on the first letter such as [M]8000 or [D]8001 in the program. → For detailed explanation, refer to the Programming Manual.
Page 356
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Number and name
Operation and function
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
Corresponding special device
PLC Mode M 8030*1 Battery LED OFF M 8031*1 Non-latch memory all clear
M 8032*1 Latch memory all clear
Number and name
If this special auxiliary relay is activated, the ON/OFF image memory of Y, M, S, T, and C, and present values of T, C, D, special data registers and R are cleared to zero. However, file registers (D) in program memory, and extension file registers (ER) in the memory cassette are not cleared.
-
M8050 (Input interrupt) I00
- disable*4
M8051 (Input interrupt) I10
I20 - disable*4
M8053 (Input interrupt) I30 disable*4
M 8034*1
All external output contacts of PLC are turned OFF.
-
M8055 (Input interrupt)
-
I50
-
M8056 (Timer interrupt)
Refer to Programming Manual for details.
M 8037 Forced STOP signal
M8054 (Input interrupt) I40
I6 -
[M]8038 Parameter setting
Communication parameter setting flag (for N:N network setting)
D8176 to D8180
M 8039 Constant scan mode
When M8039 is ON, PLC waits until scan time specified in D8039 and then executes cyclic operation.
D8039
*1.
•
M8052 (Input interrupt)
-
M 8035 Forced RUN mode
- disable*4
When PLC is switched from RUN to STOP, image memory and data memory are retained.
M 8036 Forced RUN signal
Corresponding special device
Interrupt Disable When M8030 set to ON, LED on PLC is not lit even if low battery voltage is detected.
M 8033 Memory hold STOP All outputs disable
Operation and function disable*4 disable*4 disable*4
M8057 (Timer interrupt) I7 disable*4
M8058 (Timer interrupt) I8
If an input interrupt or timer interrupt occurs while a special auxiliary relay for that interrupt (M8050 - M8058) is OFF, a) The interrupt will be accepted. b) The interrupt routine will be processed promptly if it is permitted by the EI (FNC 04) instruction. However, if the DI (FNC 05) instruction disables interrupts, the interrupt program will not be processed until EI (FNC 04) permits the interrupts.
-
-
-
-
-
-
-
- disable*4
M 8059
Executed at END instruction
•
If an input interrupt or timer interrupt occurs while a special auxiliary relay for that interrupt (M8050 - M8058) is ON, the interrupt will not operate. For example, turning M8050 ON disables the I00 interrupt; hence, the interrupt routine is not processed even in an allowable program area.
*4.
Not used
-
Cleared when PLC switches from RUN to STOP.
Step Ladder and Annunciator M 8040 Transfer disable
While M8040 is turned ON, transfer between states is disabled.
-
Transfer from initial state is enabled in automatic operation mode.
-
[M]8042 Start pulse
Pulse output is given in response to a start input.
-
M 8043*2 Zero return complete
Set this in the last state of zero return mode.
-
M 8044*2 Zero point condition
Set this when machine zero return is detected.
-
*2
[M]8041 Transfer start
Error Detection [M]8060
I/O configuration error
D8060
[M]8061
PLC hardware error
D8061
[M]8062
Serial communication error [ch0]
D8062
[M]8063*5 [M]8064
Serial communication error 1 [ch1]*6 Parameter error
D8064
[M]8065
Syntax error
D8065 D8069 D8314 D8315
[M]8066
Ladder error
D8066 D8069 D8314 D8315
Operation error
D8067 D8069 D8314 D8315 D8068 D8312 D8313
M 8045 All output reset disable
Disables the 'all output reset' function when the operation mode is changed.
[M]8046*3 STL state ON
ON when M8047 is ON and either of S0 to S899 or S1000 to S4095 is active.
M8047
[M]8067*7
M 8047*3 STL monitoring enable
D8040 to D8047 are enabled when M8047 is ON.
D8040 to D8047
M 8068
Operation error latch
M 8069*8
I/O bus check
ON when M8049 is ON and either [M]8048*3 Annunciator operate of S900 to S999 is ON. M 8049*2 Annunciator enable
D8049 is enabled when M8049 is ON.
-
D8049 M8048
-
*5.
Cleared when PLC power supply from OFF to ON.
*6.
Serial communication error 2 [ch2] PLC is detected by M8438.
*2.
Cleared when PLC switches from RUN to STOP.
*7.
Cleared when PLC switches from STOP to RUN.
*3.
Executed at END instruction.
*8.
When M8069 is ON, I/O bus check is executed.
350
D8063
Page 357
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
21 Operation and function
Corresponding special device
Parallel Link
Operation and function
M 8071*1
Parallel link Set M8071 when using slave station.
-
[M]8072
Parallel link ON when operating
-
[M]8073
Parallel link ON when M8070 or M8071 setting is incorrect
-
Cleared when PLC switches from STOP to RUN.
Pulse width/Pulse period measurement function
[M]8120
Not used
-
[M]8121*3
RS (FNC 80) instruction: Send wait flag
-
M 8122*3
RS (FNC 80) instruction: Send request
D8122
M 8123*3
RS (FNC 80) instruction: Receive complete flag
D8123
[M]8124
RS (FNC 80) instruction: Carrier detection flag
-
[M]8125
Not used
-
[M]8126
Computer link [ch1]: Global ON
[M]8127
Computer link [ch1]: On-demand send processing
Special Devices (M8000-,D8000-)
-
M 8128
Computer link [ch1]: On-demand error flag
B
M 8129
Computer link [ch1]: On-demand Word/Byte changeover RS (FNC 80) instruction: Time-out check flag
D8127 D8128 D8129
Pulse width/Pulse period measurement setting flag
[M]8076*2
[X000] Pulse width/Pulse period measurement flag
D8074 to D8079
[M]8077*2
[X001] Pulse width/Pulse period measurement flag
D8080 to D8085
[M]8078*2
[X003] Pulse width/Pulse period measurement flag
D8086 to D8091
*3.
[M]8079*2
[X004] Pulse width/Pulse period measurement flag
D8092 to D8097
Positioning [PLSY, PLSR instruction]
M 8080*2
[X000] Pulse period measurement mode
D8074 to D8079
M 8081*2
[X001] Pulse period measurement mode
M 8082*2 M 8083*2
-
M 8145
[Y000] Pulse output stop command
-
D8080 to D8085
M 8146
[Y001] Pulse output stop command
-
[M]8147
-
[X003] Pulse period measurement mode
D8086 to D8091
[Y000] Pulse output monitor (BUSY/READY)
[M]8148
-
[X004] Pulse period measurement mode
D8092 to D8097
[Y001] Pulse output monitor (BUSY/READY)
Inverter Communication Function
Supported in Ver. 1.10 or later.
Flag [M]8090 to [M]8100 Not used
-
Memory Information [M]8101 [M]8102 [M]8103
Cleared when PLC switches from RUN to STOP or RS instruction is OFF.
Not used
[M]8150
Not used
[M]8151*4
Inverter communication in execution [ch1]
D8151
[M]8152*4
Inverter communication error [ch1]
D8152
[M]8153*4
Inverter communication error latch [ch1]
D8153
-
[M]8154
-
[M]8155
Not used
-
-
-
[M]8156*4
Inverter communication in execution [ch2]
D8156
[M]8105
ON when writing to EEPROM memory
-
[M]8157*4
Inverter communication error [ch2]
D8157
[M]8106
Not used
-
[M]8107
Not used
-
[M]8158*4
Inverter communication error latch [ch2]
D8158
[M]8108
Not used
-
[M]8159
Not used
[M]8104
*4.
Output Refresh Error [M]8109
Output refresh error
[M]8110 to [M]8119 Not used
D8109
-
Cleared when PLC switches from STOP to RUN. Supported in Ver. 1.10 or later.
-
351
A
Instruction List
[M]8075*2
22 Battery
M 8070*1
*2.
Corresponding special device
RS (FNC 80) and Computer Link [ch1] Parallel link Set M8070 when using master station.
*1.
Number and name
Memory Cassette
Number and name
Page 358
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Number and name
Operation and function
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
Corresponding special device
Advanced Function M 8160
Number and name
-
[M]8180
8-bit process mode
-
[M]8181
M 8162
High speed parallel link mode
-
[M]8182
[M]8163
-
M 8164
Not used
-
[M]8166
-
M 8167
-
M 8168*1
SMOV (FNC 13) instruction: HEX data handling function
-
[M]8169
Not used
-
*1. *2.
Corresponding special device
N:N Network Not used
M 8161*1*2
M 8165
Operation and function
Cleared when PLC switches from STOP to RUN. Applicable to RS (FNC 80), ASCI (FNC 82), HEX (FNC 83), and CCD (FNC 84) instructions.
Pulse Catch
Not used
-
[M]8183
Data communication error (Master station)
[M]8184
Data communication error (Slave station No.1)
[M]8185
Data communication error (Slave station No.2)
[M]8186
Data communication error (Slave station No.3)
[M]8187
Data communication error (Slave station No.4)
[M]8188
Data communication error (Slave station No.5)
[M]8189
Data communication error (Slave station No.6)
[M]8190
Data communication error (Slave station No.7)
[M]8191
Data communication in execution
D8201 to D8218
M 8170*3
Input X000 pulse catch
-
M 8171*3
Input X001 pulse catch
-
M 8172*3
Input X002 pulse catch
-
M 8173*3
Input X003 pulse catch
-
M 8174*3
Input X004 pulse catch
-
M 8175*3
Input X005 pulse catch
-
[M]8195
-
[M]8196
-
[M]8197
-
M 8198
-
M 8199
-
M 8176 M 8177
*3.
Not used
Cleared when PLC switches from STOP to RUN.
Communication Port Channel Setting M 8178
Parallel link channel switch (OFF: ch1/ON: ch2)
-
M 8179
N:N network channel switch*4
-
*4.
352
The channel is specified by either creating or not creating M8179 in setting program. ch1: not creating M8179 in setting program ch2: creating M8179 in setting program
[M]8192
-
[M]8193
-
[M]8194
Not used
-
Page 359
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
21 Operation and function
Corresponding special device
Counter Up/down Counter Counting Direction
Number and name
Operation and function
Corresponding special device
High Speed Counter Up/down Counter Monitoring
C200
-
[M]8246
C246
-
M 8201
C201
-
[M]8247
C247
-
M 8202
C202
-
[M]8248
C248
M 8203
C203
-
[M]8249
C249
M 8204
C204
-
[M]8250
C250
M 8205
C205
-
[M]8251
C251
M 8206
C206
-
[M]8252
C252
M 8207
C207
-
[M]8253
C253
M 8208
C208
-
[M]8254
C254
-
M 8209
C209
-
[M]8255
C255
-
M 8210
C210
-
[M]8256 to [M]8259 Not used
M 8211
C211
-
Analog Expansion Board (Refer to Appendix A-3 for details)
M 8212
C212
-
M8260 to M8269*1
M 8213
C213
-
M8270 to M8279*1
M 8214
C214
-
M 8215
C215
M 8216
C216
M 8217
C217
M 8218
C218
M 8219
C219
M 8220
C220
-
M 8221
C221
-
M 8222
C222
-
M 8223
C223
-
M 8224
C224
-
M 8225
C225
-
M 8226
C226
-
M 8227
C227
-
M 8228
C228
-
M 8229
C229
-
M 8230
C230
-
M 8231
C231
-
M 8232
C232
-
M 8233
C233
-
M 8234
C234
-
-
-
-
1st expansion board*2
-
B
2nd expansion board*3
-
Analog Special Adapter (Refer to Appendix A-4 for details) M8280 to M8289
1st special adapter*4
-
M8290 to M8299
2nd special adapter*4
-
*1. *2.
*3.
*4.
Supported in Ver. 1.10 or later. 1st expansion board becomes an expansion board connected to BD connector of main units (14/24 point type), or BD1 connector of main units (40/60 point type). 2nd expansion board becomes an expansion board connected to BD2 connector of main units (40/60 point type). Connected analog special adapters are counted from the main unit side.
Flag [M]8312*5
Real time clock data lost error
-
[M]8313 to [M]8328 Not used
-
[M]8329
-
*5.
Instruction execution abnormal end
Backed up against power interruption, and automatically cleared when M8312 itself is cleared or when the clock data is set again.
High Speed Counter Up/down Counter Counting Direction M 8235
C235
-
M 8236
C236
-
M 8237
C237
-
M 8238
C238
M 8239
C239
M 8240
C240
M 8241
C241
M 8242
C242
M 8243
C243
-
M 8244
C244
-
M 8245
C245
-
When M8 is ON, the corresponding C is changed to down mode. • ON: Down count operation • OFF: Up count operation
A
-
353
Instruction List
-
-
Special Devices (M8000-,D8000-)
When M8 is ON, the corresponding C is changed to down mode. • ON: Down count operation • OFF: Up count operation
When C of 1-phase 2input or 2-phase 2-input counter is in down mode, the corresponding M8 turns ON. • OFF:Down count operation • ON:Up count operation
22 Battery
M 8200
Memory Cassette
Number and name
Page 360
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Number and name
Operation and function
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
Corresponding special device
Positioning
Number and name
Operation and function
Corresponding special device
RS2 (FNC 87) [ch0]
[M]8330 to [M]8337 Not used
-
[M]8370
Not used
PLSV (FNC157) instruction: Acceleration/deceleration operation
-
M 8371*2
RS2 (FNC 87) [ch0] Send wait flag
-
[M]8339
Not used
-
M 8372*2
RS2 (FNC 87) [ch0] Send request
D8372
[M]8340
[Y000] Pulse output monitor (ON: BUSY/ OFF: READY)
-
M 8373*2
RS2 (FNC 87) [ch0] Receive complete flag
D8373
M 8341*1
[Y000] Clear signal output function enable
-
[Y000] Zero return direction specification
-
High Speed Counter Function
[Y000] Forward limit
-
[M]8380 to [M]8387 Not used
M 8338*1
M 8342
*1
M 8343
[M]8374 to [M]8378 Not used
M 8344
[Y000] Reverse limit
-
M 8345*1
[Y000] DOG signal logic reverse
-
M 8346*1
[Y000] Zero point signal logic reverse
-
M 8347
Not used
-
[M]8348
[Y000] Positioning instruction activation
-
RS2 (FNC 87) [ch0] Time-out check flag
M 8379
-
M 8389 to M 8391
Not used
-
M 8392
Function changeover device for C248 and C253
-
[M]8393
Not used
-
[M]8394
Not used
-
[M]8395
Function changeover device for C254
-
-
[M]8350
[Y001] Pulse output monitor (ON: BUSY/ OFF: READY)
-
M 8351*1
[Y001] Clear signal output function enable
-
Ring Counter
M 8352*1
[Y001] Zero return direction specification
-
M 8398
M 8353
[Y001] Forward limit
-
[M]8399
M 8354
[Y001] Reverse limit
-
*2.
M 8355*1
[Y001] DOG signal logic reverse
-
M 8356*1
[Y001] Zero point signal logic reverse
-
M 8357
Not used
-
[M]8358
[Y001] Positioning instruction activation
-
M 8359*1
[Y001] Pulse output stop command
-
[M]8360
[Y002] Pulse output monitor (ON: BUSY/ OFF: READY)
-
M 8361*1
[Y002] Clear signal output function enable
-
M 8362*1
[Y002] Zero return direction specification
-
M 8363
[Y002] Forward limit
-
M 8364
[Y002] Reverse limit
-
M 8365*1
[Y002] DOG signal logic reverse
-
M 8366*1
[Y002] Zero point signal logic reverse
-
M 8409
M 8367
Not used
-
*4.
[M]8368
[Y002] Positioning instruction activation
-
M 8369*1
[Y002] Pulse output stop command
-
354
-
-
[M]8388
[Y000] Pulse output stop command
Cleared when PLC switches from RUN to STOP.
-
Contact for high speed counter function change
M 8349*1
*1.
-
[M]8396
Not used
[M]8397
*3.
Ring counter operation (in units of 1ms, 32 bits)*3 Not used
D8398 D8399 -
Cleared when PLC switches from RUN to STOP or when RS2 instruction [ch0] is OFF. 1ms ring counter (D8399, D8398) will operate after M8398 turns ON.
RS2 (FNC 87) [ch1] [M]8400
Not used
-
[M]8401*4
RS2 (FNC 87) [ch1] Send wait flag
-
*4
RS2 (FNC 87) [ch1] Send request
D8402
M 8403*4
RS2 (FNC 87) [ch1] Receive complete flag
D8403
[M]8404
RS2 (FNC 87) [ch1] Carrier detection flag
-
[M]8405
RS2 (FNC 87) [ch1] Data set ready (DSR) flag
-
M 8402
[M]8406 [M]8407
Not used
[M]8408
-
RS2 (FNC 87) [ch1] Time-out check flag
-
Cleared when PLC switches from RUN to STOP or when RS2 instruction [ch1] is OFF.
Page 361
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Appendix A-1 Special Auxiliary Relay (M8000 to M8511)
21 Operation and function
Memory Cassette
Number and name
Corresponding special device
RS2 (FNC 87) [ch2] and Computer Link [ch2] RS2 (FNC 87) [ch2] Send wait flag
-
M 8422*1
RS2 (FNC 87) [ch2] Send request
D8422
M 8423*1
RS2 (FNC 87) [ch2] Receive complete flag
D8423
[M]8424
RS2 (FNC 87) [ch2] Carrier detection flag
-
[M]8425
RS2 (FNC 87) [ch2] Data set ready (DSR) flag
-
[M]8426
Computer link [ch2] Global ON
[M]8427
Computer link [ch2] On-demand send processing
M 8428
Computer link [ch2] On-demand error flag
M 8429
Computer link [ch2] On-demand Word/Byte changeover RS2 (FNC 87) [ch2] Time-out check flag
A
D8427 D8428 D8429
B Instruction List
*1.
22
Special Devices (M8000-,D8000-)
-
[M]8421*1
Battery
[M]8410 to [M]8420 Not used
Cleared when PLC switches from RUN to STOP or when RS2 instruction [ch2] is OFF.
Error Detection [M]8430 to [M]8437 Not used M 8438*2
Serial communication error 2 [ch2]
[M]8439 to [M]8448 Not used [M]8449
Special block error flag
[M]8450 to [M]8459 Not used
D8438 D8449 -
Positioning M 8460 to M8463
Not used
M 8464
DSZR (FNC150), ZRN (FNC156) instructions [Y000] Clear signal device specification function enabled
D8464
M 8465
DSZR (FNC150), ZRN (FNC156) instructions [Y001] Clear signal device specification function enabled
D8465
M 8466
DSZR (FNC150), ZRN (FNC156) instructions [Y002] Clear signal device specification function enabled
D8466
[M]8467 to [M]8511 Not used
*2.
-
-
Cleared when PLC power supply from OFF to ON.
355
Page 362
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Appendix A-2 Special Data Register (D8000 to D8511)
Appendix A-2 Special Data Register (D8000 to D8511) Number and name
Corresponding special device
Content of register
PLC Status Default value is 200ms (in 1ms steps) (Writes from system ROM at power ON) Value overwritten by program is valid after END or WDT instruction execution.
BCD converted 2 6 1 0 0 value Version 1.00 FX3G Series
[D]8001 PLC type and system version
[D]8002 Memory capacity
[D]8003 Memory type
Accumulated instruction-execution time from 0 step (in units of 0.1ms)
-
Minimum value of scan time (in units of 0.1ms)
-
Maximum value of scan time (in units of 0.1ms)
-
D 8013 Second data
0 to 59 seconds (for real time clock)
-
• • • •
2...2K steps 4...4K steps 8...8K steps If 16K steps or more "K8" is written to D8002 and "16" or "32" is written to D8102.
D 8014 Minute data
0 to 59 minutes (for real time clock)
-
D 8015 Hour data
0 to 23 hours (for real time clock)
-
D 8016 Day data
1 to 31 days (for real time clock)
-
D 8017 Month data
1 to 12 months (for real time clock)
-
D 8018 Year data
2 digits of year data (0 to 99) (for real time clock)
-
D 8019 Day-of-the-week data
0 (Sunday) to 6 (Saturday) (for real time clock)
-
[D]8010 Present scan -
[D]8004 Error number M
[D]8005 Battery voltage
D8101
M8002 D8102
-
M8004
8060 to 8068 (when M8004 is ON) 3 0 BCD converted value (in units of 0.1V) Battery voltage present value (Example: 3.0V)
[D]8007
Not used
-
D 8008
Not used
-
[D]8009 24V DC failed device
Minimum input device number of input/output powered extension unit in which 24V DC has failed.
M8006
M8009
D 8020 Input filter adjustment
Input filter value of X000 to X007 (Default: 10ms)
-
[D]8021
-
[D]8022
-
[D]8023 [D]8024
Not used
-
[D]8025
-
[D]8026
-
[D]8027
-
Index Register Z0 and V0
D8003 becomes the undermentioned content.
02H
Indicated value includes waiting time of constant scan operation (when M8039 is activated).
Input Filter M8005
Default: 2.7V (in units of 0.1V) (Writes from system ROM at power ON)
Type of memory time*2
*2.
[D]8006 Low battery voltage detection level
Present value
[D]8011 Minimum scan [D]8012 Maximum scan
Stores the memory type (built-in EEPROM or memory cassette) and the PROTECT switch ON/OFF
BCD converted 8 0 6 0 value time*2 time*2 status of the memory cassette.*1
356
Corresponding special device
Clock
D 8000 Watchdog timer
*1.
Content of register
Number and name
Protect switch
EEPROM memory cassette
OFF
0AH
EEPROM memory cassette
ON
10H
Built-in memory in PLC
-
[D]8028
Value of Z0 (Z) register*3
-
[D]8029
Value of V0 (V) register*3
-
*3.
The values of Z1 to Z7 and V1 to V7 are stored in D8182 to D8195.
Page 363
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Appendix A-2 Special Data Register (D8000 to D8511)
21 Content of register
Corresponding special device
-
[D]8031
Value of analog volume VR2 (Integer from 0 to 255)
-
D 8068*2 [D]8069*2
-
Default: 0 ms (in 1 ms steps) (Writes from system ROM at power ON) Can be overwritten by program
M8039
*2. *3.
Operation error step number latched
M8068
Error step number of M8065 to M8067
M8065 to M8067
Cleared when PLC power supply from OFF to ON. Cleared when PLC switches from STOP to RUN.
Parallel link error time-out check time: 500ms
[D]8070
Pulse width/Pulse period measurement function D 8074*4
Lower
[D]8041*1
D 8075*4
Upper
D 8076*4
Lower
D 8077*4
Upper
D 8078*4
Lower
D 8079*4
Upper
D 8080*4
Lower
D 8081*4
Upper
D 8082*4
Lower
D 8083*4
Upper
D 8084*4
Lower
D 8085*4
Upper
D 8086*4
Lower
D 8087*4
Upper
D 8088*4
Lower
D 8089*4
Upper
D 8090*4
Lower
D 8091*4
Upper
Error Detection (Refer to Subsection 14.6.3 for details)
D 8092*4
Lower
If the unit or block corresponding to a programmed I/O number is not actually loaded, M8060 is set to ON and the first device number of the erroneous block is written to D8060.
D 8093*4
Upper
D 8094*4
Lower
D 8095*4
Upper
D 8096*4
Lower
Example:If X020 is unconnected. BCD converted 1 0 2 0 value Device number 10 to 177
D 8097*4
Upper
M8047
[D]8046*1 ON state number 7 [D]8047*1 ON state number 8 [D]8048
Not used
-
[D]8049*1 On state minimum number
When M8049 is ON, the smallest number out of active annunciator relay ranging from S900 to S999 is stored in D8049.
D]8050 to [D]8059
Not used
*1.
M8049 -
Executed at END instruction
[D]8060
M8060
*4.
-
[X000] Ring counter value for rising edge (1/6 s unit) [X000] Ring counter value for falling edge (1/6 s unit)
M8076 M8080
[X000] Pulse width/Pulse period (10 s unit) [X001] Ring counter value for rising edge (1/6 s unit) [X001] Ring counter value for falling edge (1/6 s unit)
M8077 M8081
[X001] Pulse width/Pulse period (10 s unit) [X003] Ring counter value for rising edge (1/6 s unit) [X003] Ring counter value for falling edge (1/6 s unit)
M8078 M8082
[X003] Pulse width/Pulse period (10 s unit) [X004] Ring counter value for rising edge (1/6 s unit) [X004] Ring counter value for falling edge (1/6 s unit)
M8079 M8083
[X004] Pulse width/Pulse period (10 s unit)
Cleared when PLC switches from STOP to RUN. Supported in Ver. 1.10 or later.
Memory Information
1: Input X 0: Output Y [D]8061
Error code for PLC hardware error
M8061
[D]8062
Error code for PC/PP communication error or serial communication error 0 [ch0]
M8062
[D]8063*2
Error code for serial communication error 1 [ch1]
M8063
[D]8064
Error code for parameter error
M8064
[D]8065
Error code for syntax error
M8065
[D]8066
Error code for ladder error
M8066
[D]8067*3
Error code for operation error
M8067
[D]8101 PLC type and system version
2 6 1 0 0 FX3G PLC
BCD converted value
-
Version 1.00
[D]8102
2......2K steps 4......4K steps 8......8K steps 16....16K steps 32....32K steps
-
[D]8103 to [D]8107
Not used
-
[D]8108
Number of special function blocks connected
-
357
A
B Instruction List
[D]8040*1 ON state number 1
-
Special Devices (M8000-,D8000-)
[D]8071 to [D]8073 Not used
ON state number 2
22
Parallel Link
Stepladder and Annunciator
[D]8042*1 ON state number 3 The smallest number out of active state ranging from S0 to S899 and [D]8043*1 S1000 to S4095 is stored in D8040 ON state number 4 and the second-smallest state number is stored in D8041. [D]8044*1 ON state number 5 Active state numbers are then sequentially stored in registers up [D]8045*1 to D8047 (Max. 8 points). ON state number 6
Corresponding special device
Battery
[D]8030
Value of analog volume VR1 (Integer from 0 to 255)
D 8039 Constant scan duration
Content of register
Error Detection (Refer to Subsection 14.6.3 for details)
Analog Volume and Constant Scan
[D]8032 to [D]8038 Not used
Number and name
Memory Cassette
Number and name
Page 364
FX3G Series Programmable Controllers
Appendix A: Special Device List
User's Manual - Hardware Edition
Number and name
Content of register
Appendix A-2 Special Data Register (D8000 to D8511)
Corresponding special device
Output Refresh Error [D]8109
Number and name
Corresponding special device
Content of register
Inverter Communication Function
Y number where output refresh error occurs
[D]8110 to [D]8119 Not used
M8109
D 8150*4
Response wait time of inverter communication [ch1]
-
[D]8151*4
Step number of instruction during inverter communication [ch1] Default: -1
M8151
-
RS (FNC 80) and Computer Link [ch1] D 8120*1
RS (FNC 80) instruction and computer link [ch1] Communication format setting
-
[D]8152*3*4
Error code for inverter communication [ch1]
M8152
D 8121*1
Computer link [ch1] Station number setting
-
[D]8153*4
M8153
[D]8122*2
RS (FNC 80) instruction: Remaining points of transmit data
Inverter communication error step number latched [ch1] Default: -1
M8122
[D]8154
Not used
-
M8123
D 8155*4
Response wait time of inverter communication [ch2]
-
[D]8156*4
Step number of instruction during inverter communication [ch2] Default: -1
M8156
[D]8157*3*4
Error code for inverter communication [ch2]
M8157
[D]8158*4
Inverter communication error step number latched [ch2] Default: -1
M8158
[D]8159
Not used
[D]8123*2
RS (FNC 80) instruction: Monitoring receive data points
D 8124
RS (FNC 80) instruction: Header <Default: STX>
-
D 8125
RS (FNC 80) instruction: Terminator <Default: ETX>
-
[D]8126
Not used
-
D 8127
Computer link [ch1] Specification of on-demand head device register
D 8128
Computer link [ch1] Specification of on-demand data length register
D 8129*1
RS (FNC 80) instruction, computer link [ch1] Time-out time setting
*1. *2.
M8126 to M8129
[D]8130 to [D]8135 Not used D 8136
Lower
D 8137
Upper
Lower
D 8141
Upper
D 8143
PLSY (FNC 57), PLSR (FNC 59) instructions: Accumulated total number of pulses output to Y000 and Y001
Lower
Upper
-
Not used
D 8140
D 8142
Accumulated number of pulses output to Y000 for PLSY (FNC 57) and PLSR (FNC 59) instructions, or current address of Y000 for positioning instruction Accumulated number of pulses output to Y001 for PLSY (FNC 57) and PLSR (FNC 59) instructions, or current address of Y001 for positioning instruction
[D]8162
Not used
-
[D]8165
-
[D]8166
-
[D]8167
-
[D]8168 [D]8169
*5.
Access restriction status*5
-
Access restriction status Present value
Access restriction status
H**00*7 2nd keyword is not set
Program
Present Monitor value -ing Read Write change *6
*6
-
-
-
-
H**10*7 Write protection
H**12*7
-
All online operation protection
*6
*6
-
-
-
H**20*7 Keyword cancel
Not used
D 8164
H**11*7 Read / write protection
D 8145
-
D 8148
-
[D]8149
-
358
-
-
-
D 8147
-
[D]8161
-
[D]8144 D 8146
[D]8160
[D]8163
Positioning
[D]8139
Cleared when PLC switches from STOP to RUN. Supported in Ver. 1.10 or later.
Advanced Function
Latch device Cleared when PLC switches from RUN to STOP.
[D]8138
*3. *4.
-
*6. *7.
Accesses are restricted by the keyword setting status. "**" indicates areas used by the system.