The text of a manual · part 3 of 11
FX Family MELSEC PLC Technical Catalogue: FX series, pages 13 to 22
Pages 13 to 22 of 85, from FX Family MELSEC PLC Technical Catalogue
The original document is the PDF (4.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi FX1S-14MR-ES/UL
Page 13
Farbprofil: Deaktiviert Komposit Standardbildschirm
/// BASE UNITS FX1S SERIES
The MELSEC FX1S Series
0 4 12 5 3 6 7 IN
All units feature two analog potentiometers for setpoint value entry and an integrated RUN/STOP switch.
1S FX
B S U IT
0 O U 4 12 T 5 3
IS H
I
-1 4M R
PO
R W U ER N ER R O R
Square pulse output (this applies only to transistor units.) Two integrated high speed pulse outputs for frequencies up to 100 kHz for outputting pulse signals and controlling stepping motors
M
EL
SE
C
M
Integration of interface, extension, and functions adapters for direct installation in the base unit
The internal service power supply unit for 24 V DC has a capacity of 400 mA. Note: service power supply is only available for AC Power Supply types.
Integrated real-time clock with year, month, day and time Integrated serial RS422 interface for direct communication with computers
Flexible installation with the integrated DIN rail adapter and screw fastening holes for mounting on flat surfaces
Password access protection facility for effective protection of your intellectual property.
Your PLC programs are stored in a maintenance-free EEPROM user memory with a capacity of 2,000 program steps, so there is no need for a backup battery to protect against power failures.
Description of the Unit Components Protective cover
Terminal cover Fixing hole Connection of the power supply
Terminals for digital inputs
Adapter interface 100-240 VAC
L
N
X7 X5 X3 X1 S/S X6 X4 X2 X0
0 1 2 3 4 5 6 7
Slot for adapter
LEDs for indicating the input status
IN
RUN/STOP switch POWER RUN ERROR
2 analog potentiometers Connection for programming units Service voltage source
FX1S-14MR OUT
0 1 2 3 4 5 Y4 Y2 Y1 Y0 0V Y5 COM2 Y3 24V COM0 COM1
14MR -ES/UL
MITSUBISHI
LEDs for indicating the operating status LEDs for indicating the output status Housing cover
Terminals for digital outputs
13
MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:12
13
FX BASE UNITS
High-speed inputs for fast counting tasks with counting frequencies of up to 60 kHz and interrupt processing capabilities
Page 14
Farbprofil: Deaktiviert Komposit Standardbildschirm
BASE UNITS FX1S SERIES ///
þ FX1S ¨ FX1N ¨ FX2N ¨ FX3U
왎 Base Units
Base Units FX1S The FX1S series base units are available with 10 to 30 input/output points. It is possible to choose between relay and transistor output type. Note: Versions with UL certification are available on request. 100-240 VAC
L
N
X7 X5 X3 X1 S/S X6 X4 X2 X0
Special Features:
0 1 2 3 4 5 6 7
FX BASE UNITS
앬 Integrated power supply (AC or DC powered) 앬 Maintenance-free EEPROM memory 앬 Ample memory capacity (2000 steps) and device ranges 앬 High-speed operations 앬 Incorporated positioning control 앬 Integrated real-time clock 앬 System upgrades by exchangeable interface and I/O adapter
IN
MITSUBISHI POWER RUN ERROR
FX1S-14MR OUT
0 1 2 3 4 5 Y4 Y2 Y1 Y0 0V Y5 OM2 Y3 24V COM0 COM1C
14MR -ES/UL boards for direct fitting into the base unit 앬 LEDs for indicating the input and output status 앬 Standard programming unit interface 앬 User-friendly programming systems, including IEC 61131.3
(EN 61131.3)-compatible programming software, HMIs and hand-held programming units
Base Units with 10 – 14 I/Os Specifications
FX1S-10 MR-DS
FX1S-10 MR-ES/UL
FX1S-10 MT-DSS
FX1S-14 MR-DS
FX1S-14 MR-ES/UL
FX1S-14 MT-DSS
Max. number inputs/outputs Power supply Integrated inputs Integrated outputs
10 24 V DC 6 4
10 100–240 V AC 6 4
14 24 V DC 8 6
14 100–240 V AC 8 6
Output type
Relay
Relay
10 24 V DC 6 4 Transistor (source)
Relay
Relay
14 24 V DC 8 6 Transistor (source)
19 0.3 60 x 90 x 75
6 0.22 60 x 90 x 49
6.5 0.22 60 x 90 x 49
19 0.3 60 x 90 x 75
6.5 0.22 60 x 90 x 49
141243
141246
141247
141248
141249
Power consumption Weight Dimensions (W x H x D) Order information
W 6 kg 0.22 mm 60 x 90 x 49 Art. no. 141240
Base Units with 20 – 30 I/Os Specifications
FX1S-20 MR-DS
FX1S-20 MR-ES/UL
FX1S-20 MT-DSS
FX1S-30 MR-DS
FX1S-30 MR-ES/UL
FX1S-30 MT-DSS
Max. number inputs/outputs Power supply Integrated inputs Integrated outputs
20 24 V DC 12 8
20 100–240 V AC 12 8
30 24 V DC 16 14
30 100–240 V AC 16 14
Output type
Relay
Relay
20 24 V DC 12 8 Transistor (source)
Relay
Relay
30 24 V DC 16 14 Transistor (source)
20 0.4 75 x 90 x 75
7 0.3 75 x 90 x 49
8 0.35 100 x 90 x 49
21 0.45 100 x 90 x 75
8 0.35 100 x 90 x 49
141252
141254
141255
141256
141257
Power consumption Weight Dimensions (W x H x D) Order information
W 7 kg 0.3 mm 75 x 90 x 49 Art. no. 141251
14
FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:16
MITSUBISHI ELECTRIC 14
Page 15
Farbprofil: Deaktiviert Komposit Standardbildschirm
/// BASE UNITS FX1S SERIES
þ FX1S ¨ FX1N ¨ FX2N ¨ FX3U
왎 Base Units Environmental Specifications Data
Ambient temperature
0 – 55 °C (storage temperature: -20 – +70 °C)
Protection
IP 10
Noise durability
1000 Vpp with noise generator; 1 µs at 30 – 100 Hz
Dielectric withstand voltage
1,500 V AC, 1 min. (500 V AC for direct voltage modules)
Ambient relative humidity
35 – 85 % (non-condensing)
Shock resistance
Acc. to IEC/EN 68-2-27: 15G (3 times each in 3 directions for 11 ms)
Vibration resistance
Acc. to IEC/EN 68-2-6: 1G (resistance to vibrations from 57 - 150 Hz for 80 minutes along all 3 axes); 0.5G for DIN rail mounting
Insulation resistance
500 V DC, 5 MΩ
Ground
Class D: Grounding resistance 100 Ω or less
Fuse rating
AC models: 250 V 1.0 A; DC models: 0.8 A
Environment
Avoid environments containing corrosive gases, install in a dust-free location.
Certifications
Please refer to page 82 in this catalogue
FX BASE UNITS
General specifications
Electrical Specifications Power supply specifications
DC powered modules (FX1S- M -DS/-DSS)
Power supply
24 V DC (+10% / -15 %)
Inrush current at ON
10 A / 0.1 ms (at 24 V DC)
Allowable momentary power 5 ms failure time Primary power supply 24 V DC, 400 mA External power supply (24 V DC), AC powered modules (FX1S- M -ES/UL) 100 – 240 V AC (+10 % / -15 %), 50/60 Hz (±10 %) 15 A / 5 ms (at 100 V AC); 25 A / 5 ms (at 200 V AC)
Output specifications Switching voltage (max.) - per output Max. output current - per group* - inductive load Max. switching current - lamp load Response time
10 ms 400 mA
Life of contacts (switching times)**
Transistor Type Relay modules modules V < 250 V AC, < 30 V DC 5 – 30 V DC A 2 0.5 A 8 0.8 80 VA 12 W W 100 1.2 ms 10 0.2 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA
* The limitation applies only per reference terminal for each group, 1 and 4 outputs for relays and transistors. Please observe the terminal assignments for the group identification. ** Not guaranteed by Mitsubishi Electric.
Programming Specifications System specifications
FX1S
Program data Program memory
2.000 steps EEPROM (internal)
Program execution
Periodical execution of the stored program
Program protection
Password protection with 3 protection levels. Note: Protection levels may only be changed with FX-20P-E and FX-10P-E.
Number of instructions
27 sequence instructions, 2 step ladder instructions, 85 applied instructions
Cycle period
0.55 – 0.7 µs / logical instruction
Operands Internal relays
512 total, with 384 general (M0 – M383) and 128 latched (M384 – M511)
Special relays
256 (M8000 – M8255)
State relays
128
Timers
64 (max. 63 timers, partially switchable to 100 ms and 10 ms)
External setpoint entry via potentiometer
2 potentiometers
Counter
32 (16 bit), C0 – C31
High-speed counter inputs
1 phase, 6 points max: 60kHz / 2 points, 10kHz / 4 points ; 2 phase, 2 points max: 30kHz / 1 point, 5kHz / 1 point
Data register
256 subtotal (128 general (D0 – D127) and 128 latched (D128 – D255))
Index register
16
Special register
256 (16 bit), D8000 – D8255
Pointer
64, P0 – P63
Nesting operands
8, N0 – N7
Interrupt inputs
6
Constants
16 bits: K: -32768 to +32767, hex: 0–FFFF 32 bits: K: -2147483648 to +2147483647, hex: 0–FFFF FFFF
15
MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:18
15
Page 16
Farbprofil: Deaktiviert Komposit Standardbildschirm
BASE UNITS FX1N SERIES ///
The MELSEC FX1N Series
Integrated RUN/STOP switch and two analog potentiometers for setpoint value entry.
The base units can be expanded for up to 128 inputs/outputs with different extension units.
PO
R W U ER N ER R O R
IN
0 4 1 10 5 2 14 1 1 6 3 15 12 7 13
Integration of interface, extension, and functions adapters for direct installation in the base unit
MR
I H IS IT S
U
B
0 O 4 1 U T 10 5 2 11 6 3 7
-24
1N
FX
M
EL
SE
C
M
FX BASE UNITS
High-speed inputs for fast counting tasks with counting frequencies of up to 60 kHz and interrupt processing capabilities
The base units have integrated, maintenance-free EEPROM user memory for up to 8,000 PLC program steps with a backup battery to protect memory contents against power failures. You can also configure password protection to prevent unauthorized access to your programs.
Integrated real-time clock with year, month, day and time
Square pulse output (This only applies for transistor units.) Two integrated high-speed pulse outputs for frequencies up to 100 kHz for outputting pulse signals and controlling stepping motors
External EEPROM memory cassettes for PLC program storage
Description of the Unit Components Protective cover Terminals for digital inputs
Terminal cover
Connection of the power supply
Fixing hole
Extension bus
RUN/STOP switch 100-240 VAC
Slot for memory cassettes, displays and ADPs.
L
X15 X7 X11 X13 X5 X3 X1 X14 S/S X6 X10 X12 X4 X2 X0 N 0 1 2 3 4 5 6 7 11 10 8 9 12 13 14 15 IN
POWER RUN ERROR
2 analog potentiometers
LEDs for indicating the operating status
FX1N-24MR OUT
0 1 2 3 4 5 6 7 10 11
Connection for programming units
Y6 Y10 Y5 Y3 Y2 Y1 Y11 Y0 0V COM4 Y7 COM2 COM3 Y4 24+ COM0 COM1
LEDs for indicating the input status
24MR -ES/UL
LEDs for indicating the output status
MITSUBISHI
Terminals for service voltage source
Housing cover
Terminals for digital outputs
Lid
Terminal cover Protective cover
16
FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:25
MITSUBISHI ELECTRIC 16
Page 17
Farbprofil: Deaktiviert Komposit Standardbildschirm
/// BASE UNITS FX1N SERIES
¨ FX1S þ FX1N ¨ FX2N ¨ FX3U
왎 Base Units
Base Units FX1N The FX1N series base units are available with 14 to 60 input/output points. It is possible to choose between relay and transistor output type. Note: Versions with UL certification are available on request.
L
N
X15 X7 X11 X13 X5 X3 X1 X14 S/S X6 X10 X12 X4 X2 X0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MITSUBISHI
Special Features: 앬 Integrated serial interface for communication between
IN
Personal computers and HMI
POWER RUN ERROR
FX1N-24MR OUT
0 1 2 3 4 5 6 7 10 11 Y6 Y10 Y5 Y3 Y2 Y1 Y11 Y0 0V COM4 Y7 COM2 COM3 Y4 24+ COM0 COM1
24MR -ES/UL
앬 Standard programming unit interface 앬 LEDs for indicating the input and output status 앬 Detachable terminal blocks for units with 14, 24, 40, and 60 I/Os. 앬 Slot for memory cassettes 앬 All DC models with variable voltage from 12 up to 24 V 앬 Integrated real-time clock 앬 Exchangeable interface and I/O adapter boards for direct fitting into the base unit
Base Units with 14 – 24 I/Os Specifications
FX1N-14 MR-DS
FX1N-14 MR-ES/UL
FX1N-14 MT-DSS
FX1N-24 MR-DS
FX1N-24 MR-ES/UL
FX1N-24 MT-DSS
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
14 12–24 V 8 6
14 100–240 V 8 6
24 12–24 V 14 10
24 100–240 V 14 10
Output type
Relay
Relay
14 12–24 V 8 6 Transistor (source)
Relay
Relay
24 12–24 V 14 10 Transistor (source)
29 0.45 90 x 90 x 75
13 0.45 90 x 90 x 75
15 0.45 90 x 90 x 75
30 0.45 90 x 90 x 75
15 0.45 90 x 90 x 75
141259
141260
141261
141262
141263
Power consumption Weight Dimensions (W x H x D) Order information
W 13 kg 0.45 mm 90 x 90 x 75 Art. no. 141254
Base Units with 40 – 60 I/Os Specifications
FX1N-40 MR-DS
FX1N-40 MR-ES/UL
FX1N-40 MT-DSS
FX1N-60 MR-DS
FX1N-60 MR-ES/UL
FX1N-60 MT-DSS
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
40 12–24 V DC 24 16
40 100–240 V AC 24 16
60 12–24 V DC 36 24
60 100–240 V AC 36 24
Output type
Relay
Relay
40 12–24 V DC 24 16 Transistor (source)
Relay
Relay
60 12–24 V DC 36 24 Transistor (source)
32 0.65 130 x 90 x 75
18 0.65 130 x 90 x 75
20 0.8 175 x 90 x 75
35 0.8 175 x 90 x 75
20 0.8 175 x 90 x 75
141265
141266
141267
141268
141269
Power consumption Weight Dimensions (W x H x D) Order information
W 18 kg 0.65 mm 130 x 90 x 75 Art. no. 141264
17
MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:30
17
FX BASE UNITS
100-240 VAC
Page 18
Farbprofil: Deaktiviert Komposit Standardbildschirm
BASE UNITS FX1N SERIES ///
¨ FX1S þ FX1N ¨ FX2N ¨ FX3U
왎 Base Units Environmental Specifications
FX BASE UNITS
General specifications
Data
Ambient temperature
0 – 55 °C (storage temperature: -20 – +70 °C)
Protection
IP 10
Noise durability
1000 Vpp with noise generator; 1 µs at 30 – 100 Hz
Dielectric withstand voltage
1,500 V AC, 1 min. (500 V AC for direct voltage modules)
Ambient relative humidity
35 – 85 % (non-condensing)
Shock resistance
Acc. to IEC 68-2-27: 15G (3 times each in 3 directions for 11 ms)
Vibration resistance
Acc. to IEC 68-2-6: 1G (resistance to vibrations from 57 - 150 Hz for 80 minutes along all 3 axes); 0.5G for DIN rail mounting
Insulation resistance
500 V DC, 5 MΩ
Ground
Class D: Grounding resistance 100 Ω or less
Fuse rating
AC units: From FX1N-14M첸 to FX1N-24M첸: 250 V AC 1.0 A; From FX1N-40M첸 to FX1N-60M첸: 250 V AC 3.15 A / DC units: 125 V DC 3.15 A
Environment
Avoid environments containing corrosive gases, install in a dust-free location.
Certifications
Please refer to page 82 in this catalogue
Electrical Specifications Power supply specifications
DC powered modules (FX1N- M -DS/-DSS)
AC powered modules (FX1N- M -ES/UL)
Output specifications
Power supply
12–24 V DC (+20% / -15 %)
100 – 240 V AC (+10 % / -15 %), 50/60 Hz (±10 %)
Switching voltage (max.)
Inrush current at ON
25 A /1 ms (at 24 V DC); 22 A / 0.3 ms (at 12 V DC)
Allowable momentary power failure time
5 ms
Primary power supply
24 V DC, 400 mA
30 A / 5 ms (at 100 V AC); 50 A / 5 ms (at 200 V AC) 10 ms
External power supply (24 V DC), Transistor modules
V < 240 V AC, < 30 V DC
5 – 30 V DC
Max. output current
- per output
A 2
0.5
- per group
A 8
0.8
Max. switching current
- inductive load
Response time 400 mA
Type Relay modules
Life of contacts (switching times)*
80 VA ms 10
12 W <0.2(Y0,Y1<5µs)
3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA
* Not guaranteed by Mitsubishi Electric.
Programming Specifications System specifications
FX1N
System specifications
Program data
FX1N
Operands
I/O points (addresses)
128 (+4 optional)
Internal relays
Address range
Max.128 inputs X0–X177, max. 128 outputs Y0–Y177
Special relays
256
8,000 steps EEPROM (internal), exchangeable EEPROM for easy program exchange
Step ladder
1,000
Timer
256 2
Program memory
1,536
Cycle period
0.55 – 0.7 µs /logical instruction
Ext. preset value via potentiometer
Number of instructions
27 sequence instructions, 2 step ladder instructions, 89 applied instructions
Counter
235
Programming language
Step ladder, instruction list, SFC
High-speed counter
1phase,6pointsmax:60kHz/2points,10kHz/4points; 2phase,2pointsmax:30kHz/1point,5kHz/1point
Program execution
Cyclical execution, refresh mode processing
Real-time clock
Year, month, day, hour, minute, second, weekday
Password protection with 3 protection levels*
Data register
8,000
File register
Max. 7,000 (parameter editable), Total registers = 8,000
Index register
16
Program protection
* Protection levels may only be changed with FX-20P-E and FX-10P-E.
18
FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:32
Special register
256
Pointer
128
Nestings
8
Interrupt inputs
6
Constants
16 bits: K: -32768 to +32767, hex: 0–FFFF; 32 bits: K: 2147483648 to +2147483647, hex: 0–FFFF FFFF
MITSUBISHI ELECTRIC 18
Page 19
Farbprofil: Deaktiviert Komposit Standardbildschirm
/// BASE UNITS FX2N SERIES
The MELSEC FX2N Series
W ER PO IN
I BI SH
T
U
OU
IT S
M
CO
3 2 Y1 Y1 1 0 Y1 Y1 M3 CO Y6 Y5 Y4 M2
YO M1
CO
Y2 Y1
Y3
R U N BA TT .V O CP G U E E
0 10 1 11 2 12 3 13 4 14 5 15 6 16 7 17
X6 X4 X2 X0
PR
0 10 1 11 2 12 3 13 4 14 5 15 6 16 7 17
6 X1
4
X1
2 X1 0 X1
M
Add-in function boards can be installed in the PLC to provide a second RS485 / RS422 / RS232 communications interface for programming or network configurations. An add-in function board with 8 analog potentiometers is also available.
The base units can be expanded to provide configurations with up to 256 inputs and outputs with modular and compact extension units.
16 Y17
Y 5 4 Y1 Y1 M4
CO
Y7
CO
Integrated real-time clock with year, month, day and time
Integrated serial interface for direct communication with computers
Two integrated pulse outputs for frequencies from 2 to 20,000 Hz for controlling stepping motors and outputting pulse-width modulated signals.
An integrated RUN/STOP switch is available.
Description of the Unit Components Connection of the power supply Slot for memory cassettes Detachable terminal strip for digital inputs
Terminal cover Fixing hole
LEDs for indicating the input status LEDs for indicating the operating status
Extension connector for function boards Back-up battery
Connection for extensions
Connection for programming units
Protective cover for the extension bus LEDs for indicating the output status
RUN/STOP switch Detachable terminal strip for digital outputs
Protective cover
Housing cover
19
MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:41
19
FX BASE UNITS
RAM/EEPROM memory for up to 16,000 PLC program steps gives you plenty of reserve, even for big, complex applications.
Integrated high-speed counter inputs for processing fast input signals. For example, you can configure two 60 kHz counters and four 10 kHz counters. Interrupt processing is also handled via the inputs.
Page 20
Farbprofil: Deaktiviert Komposit Standardbildschirm
BASE UNITS FX2N SERIES ///
¨ FX1S ¨ FX1N þ FX2N ¨ FX3U
왎 Base Units
Base Units FX2N The FX2N series base units are available with 16, 32, 48, 64, 80 or 128 input/output points. It is possible to choose between relay and transistor output type. Triac output types for 110 V AC for sink/source are also available. Note: Additional special versions are available on request.
Special Features:
FX BASE UNITS
앬 Exchangeable interface modules for direct mounting into a base unit 앬 Standard programming unit interface 앬 LEDs for indicating the input and output status 앬 Detachable terminal blocks (except for 16 I/O base units) 앬 Slot for memory cassettes for up to 16 k steps PLC program 앬 Integrated real-time clock
Base Units with 16 I/Os Specifications
FX2N-16 MR-DS
FX2N-16 MR-ES/UL
FX2N-16 MT-DSS
FX2N-16 MT-ESS/UL
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
16 24 V DC 8 8
16 100–240 V AC 8 8
Output type
Relay
Relay
16 24 V DC 8 8 Transistor (source type)
16 100–240 V AC 8 8 Transistor (source type)
30 VA 0.6 130 x 90 x 87
20 W 0.6 130 x 90 x 87
30 VA 0.6 130 x 90 x 87
141271
103689
141272
Power consumption Weight Dimensions (W x H x D) Order information
20 W kg 0.6 mm 130 x 90 x 87 Art. no. 141270
Base Units with 32 I/Os Specifications
FX2N-32 MR-DS
FX2N-32 MR-ES/UL
FX2N-32 MT-DSS
FX2N-32 MT-ESS/UL
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
32 24 V DC 16 16
32 100–240 V AC 16 16
Output type
Relay
Relay
32 24 V DC 16 16 Transistor (source type)
32 100–240 V AC 16 16 Transistor (source type)
40 VA 0.65 150 x 90 x 87
25 W 0.65 150 x 90 x 87
40 VA 0.65 150 x 90 x 87
141274
141275
141276
Power consumption Weight Dimensions (W x H x D) Order information
25 W kg 0.65 mm 150 x 90 x 87 Art. no. 141273
20
FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:46
MITSUBISHI ELECTRIC 20
Page 21
Farbprofil: Deaktiviert Komposit Standardbildschirm
/// BASE UNITS FX2N SERIES
Specifications
FX2N-48 MR-DS
FX2N-48 MR-ES/UL
FX2N-48 MT-ESS/UL
FX2N-48 MT-DSS
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
48 24 V DC 24 24
48 100–240 V AC 24 24
Output type
Relay
Relay
48 100–240 V AC 24 24 Transistor (source type)
48 24 V DC 24 24 Transistor (source type)
50 VA 0.85 182 x 90 x 87
50 VA 0.85 182 x 90 x 87
30 W 0.85 182 x 90 x 87
141278
141280
141279
Power consumption Weight Dimensions (W x H x D) Order information
30 W kg 0.85 mm 182 x 90 x 87 Art. no. 141277
FX BASE UNITS
Base Units with 48 I/Os
Base Units with 64 I/Os Specifications
FX2N-64 MR-DS
FX2N-64 MR-ES/UL
FX2N-64 MT-ESS/UL
FX2N-64 MT-DSS
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
64 24 V DC 32 32
64 100–240 V AC 32 32
Output type
Relay
Relay
64 100–240 V AC 32 32 Transistor (source type)
64 24 V DC 32 32 Transistor (source type)
60 VA 1.0 220 x 90 x 87
60 VA 1.0 220 x 90 x 87
35 W 1.0 220 x 90 x 87
141282
141284
141283
Power consumption Weight Dimensions (W x H x D) Order information
35 W kg 1.0 mm 220 x 90 x 87 Art. no. 141281
Base Units with 80 – 128 I/Os Specifications
FX2N-80 MR-DS
FX2N-80 MR-ES/UL
FX2N-80 MT-DSS
FX2N-80 MT-ESS/UL
FX2N-128 MR-ES/UL
FX2N-128 MT-ESS/UL
Integrated inputs/outputs Power supply Integrated inputs Integrated outputs
80 24 V DC 40 40
80 100–240 V AC 40 40
Relay
Relay
80 100–240 V AC 40 40 Transistor (source type)
128 100–240 V AC 64 64
Output type
80 24 V DC 40 40 Transistor (source type)
Relay
128 100–240 V AC 64 64 Transistor (source type)
70 VA 1.2 285 x 90 x 87
40 W 1.2 285 x 90 x 87
70 VA 1.2 285 x 90 x 87
100 VA 1.8 350 x 90 x 87
100 VA 1.8 350 x 90 x 87
141287
141288
141289
141290
141292
Power consumption Weight Dimensions (W x H x D) Order information
40 W kg 1.2 mm 285 x 90 x 87 Art. no. 141286
21
MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:48
21
Page 22
Farbprofil: Deaktiviert Komposit Standardbildschirm
BASE UNITS FX2N SERIES ///
¨ FX1S ¨ FX1N þ FX2N ¨ FX3U
왎 Base Units Environmental Specifications
FX BASE UNITS
General specifications
Data
Ambient temperature
0 – 55 °C (storage temperature: -20 – +70 °C)
Protection
IP 10
Noise durability
1000 Vpp with noise generator; 1 µs at 30 – 100 Hz
Dielectric withstand voltage
DC PSU: 500 V AC, 1 min AC PSU: 1,500 V AC, 1 min
Ambient relative humidity
35 – 85 % (non-condensing)
Shock resistance
Acc. to IEC 68-2-27: 15G (3 times each in 3 directions for 11 ms)
Vibration resistance
Acc. to IEC 68-2-6: 1G (resistance to vibrations from 57 - 150 Hz for 80 minutes along all 3 axes); 0.5G for DIN rail mounting
Insulation resistance
500 V DC, 5 MΩ
Ground
Class D: Grounding resistance 100 Ω or less
Fuse
From FX2N-16M첸 to FX2N-32M첸: 3.15 A; From FX2N-48M첸 to FX2N-128M첸: 5 A
Environment
Avoid environments containing corrosive gases, install in a dust-free location.
Certifications
Please refer to page 82 in this catalogue
Electrical Specifications Power supply specifications
DC powered modules (FX2N- M -DS/-DSS)
AC powered modules (FX2N- M -ES/UL)
Output specifications
Power supply
24 V DC (+20% / -30 %)
100 – 240 V AC (+10 % / -15 %), 50/60 Hz
Switching voltage (max.)
V < 240 V AC, < 30 V DC
5 – 30 V DC
Max. output current
A 2
0.5 / 0.3햲
- per group*
A 8
0.8 / 1.6햳
- inductive load, 40 A / <5 ms (at 100 V AC); 60 A / <5 ms (at 200 V AC)
Allowable momentary power failure time
5 ms
10 ms
Max. switching current
Primary power supply
24 V DC, Response time
80 VA ms 10
햴
FX2N-16/32M: 250 mA / FX2N-48/64/80/128M: 460 mA
Transistor modules
- per output
Inrush current at ON
External power supply (24 V DC), Type Relay modules
Life of contacts (switching times)
햲 for Y0 and Y1 = 0.3 A; all others 0.5 A
햴 Not guaranteed by Mitsubishi Electric.
12 W / 7.2 W <0.2(Y0,Y1<30 µs)
3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA 햳 0.8 for 4 per group and 1.6 for 8 per group
* This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification.
Programming Specifications System specifications
FX2N
System specifications
Program data
FX2N
Operands
I/O points (addresses)
256
Internal relays
Address range
Max. 189 inputs X0-X267, max. 184 outputs Y0-Y267
Special relays
256
Step ladder
1,000
Program memory
8,000 steps RAM (internal), 4,000 and 8,000 steps EEPROM cassettes (optional), 16,000 steps RAM cassettes (optional), 16,000 steps EPROM cassette (optional) 16,000 steps EEPROM cassettes (optional)
Cycle period
0.08 µs / logical instruction
Number of instructions
27 sequence instructions, 2 step ladder instructions, 132 applied instructions
3,072
Timer
256
Ext. preset value via potentiometer, Counter
235
High-speed counter
6 single phase inputs (max. 60 kHz), 2 double phase inputs (max. 30 kHz)
Real-time clock
Year, month, day, hour, minute, second, weekday
Data register
8.000
Programming language
Step ladder, instruction list, SFC
Program execution
Cyclical execution, refresh mode processing
File register
Max . 7,000 (parameter editable), Total registers = 8,000
Program protection
Password protection with 3 protection levels*
Index register
16
* Protection levels may only be changed with FX-20P-E and FX-10P-E.
22
FX1-Cat 2006 Euro GB01-22.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:10:50
Special register
256
Pointer
128
Nestings
8
Interrupt inputs
6
Constants
16 bits: K: -32768 to +32767, hex: 0–FFFF 32 bits: K: 2147483648 to +2147483647, hex: 0–FFFF FFFF 32 bitsfloatingpoint:0, ±1.175x10-38 to ±3.403x10-38
MITSUBISHI ELECTRIC 22