Page 23

Farbprofil: Deaktiviert Komposit Standardbildschirm

/// BASE UNITS FX3U SERIES

The MELSEC FX3U Series Integrated high-speed counter inputs for processing fast input signals. For example, you can configure six 100 kHz counters and two 10 kHz counters. Interrupt processing is also handled via the inputs.

The base units can be expanded to provide configurations with up to 384 inputs and outputs with compact extension units (total of 384 only by using main unit I/Os, extension unit I/Os and remote I/Os).

Add-in function boards can be installed in the PLC to provide a second RS485 / RS422 / RS232/USB communications interface for programming or network configurations.

Integrated real-time clock with year, month, days and time An integrated RUN/STOP switch is available.

Three integrated pulse outputs for frequencies up to 100 kHz with deceleration and acceleration ramps for controlling stepping motors and outputting pulse-width modulated signals.

Integrated serial interface for direct communication with computers

Description of the Unit Components

Battery cover

Protective cover

Terminal block cover Input terminals LEDs for indicating the input status LEDs for indicating the operating status

Battery Installation place for FX3U-7DM

Extension device connecting connector cover

Expansion board dummy cover RUN/STOP switch

LEDs for indicating the output status Output terminals

Periphal device connecting connector

Terminal block cover

Top cover with Model name (used,if FX3U-7DM is not installed)

Protective cover

23

MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:19:58

23

FX BASE UNITS

RAM/EEPROM memory for up to 64,000 PLC program steps gives you plenty of reserve, even for big, complex applications.

Page 24

Farbprofil: Deaktiviert Komposit Standardbildschirm

BASE UNITS FX3U SERIES ///

¨ FX1S ¨ FX1N ¨ FX2N þ FX3U

왎 Base Units

Base Units FX3U The FX3U series base units are available with 16, 32, 48, 64, 80 or 128 input/output points. It is possible to choose between relay and transistor output type. Note: Additional special versions are available on request.

Special Features: 앬 Exchangeable interface modules for direct mounting into

FX BASE UNITS a base unit 앬 Standard programming unit interface 앬 LEDs for indicating the input and output status 앬 Slot for memory cassettes for up to 64 k steps PLC program 앬 Integrated real-time clock

Base Units with 16 I/Os Specifications

FX3U-16 MR/DS

FX3U-16 MR/ES

FX3U-16 MT/DSS

FX3U-16 MT/ESS

Integrated inputs/outputs Power supply Integrated inputs Integrated outputs

16 24 V DC 8 8

16 100–240 V AC 8 8

Output type

Relay

Relay

16 24 V DC 8 8 Transistor (source type)

16 100–240 V AC 8 8 Transistor (source type)

30 VA 0.6 130 x 90 x 86

25 W 0.6 130 x 90 x 86

30 VA 0.6 130 x 90 x 86

165236

169499

168585

Power consumption Weight Dimensions (W x H x D) Order information

25 W kg 0.6 mm 130 x 90 x 86 Art. no. 169489

Base Units with 32 I/Os Specifications

FX3U-32 MR/DS

FX3U-32 MR/ES

FX3U-32 MT/DSS

FX3U-32 MT/ESS

Integrated inputs/outputs Power supply Integrated inputs Integrated outputs

32 24 V DC 16 16

32 100–240 V AC 16 16

Output type

Relay

Relay

32 24 V DC 16 16 Transistor (source type)

32 100–240 V AC 16 16 Transistor (source type)

35 VA 0.65 150 x 90 x 86

30 W 0.65 150 x 90 x 86

35 VA 0.65 150 x 90 x 86

165237

169500

168586

Power consumption Weight Dimensions (W x H x D) Order information

30 W kg 0.65 mm 150 x 90 x 86 Art. no. 169490

24

FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:01

MITSUBISHI ELECTRIC 24

Page 25

Farbprofil: Deaktiviert Komposit Standardbildschirm

/// BASE UNITS FX3U SERIES

Specifications

FX3U-48 MR/DS

FX3U-48 MR/ES

FX3U-48 MT/ESS

FX3U-48 MT/DSS

Integrated inputs/outputs Power supply Integrated inputs Integrated outputs

48 24 V DC 24 24

48 100–240 V AC 24 24

Output type

Relay

Relay

48 100–240 V AC 24 24 Transistor (source type)

48 24 V DC 24 24 Transistor (source type)

40 VA 0.85 182 x 90 x 86

40 VA 0.85 182 x 90 x 86

35 W 0.85 182 x 90 x 86

165238

168587

169501

Power consumption Weight Dimensions (W x H x D) Order information

35 W kg 0.85 mm 182 x 90 x 86 Art. no. 169491

FX BASE UNITS

Base Units with 48 I/Os

Base Units with 64 I/Os Specifications

FX3U-64 MR/DS

FX3U-64 MR/ES

FX3U-64 MT/ESS

FX3U-64 MT/DSS

Integrated inputs/outputs Power supply Integrated inputs Integrated outputs

64 24 V DC 32 32

64 100–240 V AC 32 32

Output type

Relay

Relay

64 100–240 V AC 32 32 Transistor (source type)

64 24 V DC 32 32 Transistor (source type)

45 VA 1.0 220 x 90 x 86

45 VA 1.0 220 x 90 x 86

40 W 1.0 220 x 90 x 86

165239

168588

169502

Power consumption Weight Dimensions (W x H x D) Order information

40 W kg 1.0 mm 220 x 90 x 86 Art. no. 169492

Base Units with 80 – 128 I/Os Specifications

FX3U-80 MR/DS

FX3U-80 MR/ES

FX3U-80 MT/DSS

FX3U-80 MT/ESS

FX3U-128 MR/ES

FX3U-128 MT/ESS

Integrated inputs/outputs Power supply Integrated inputs Integrated outputs

80 24 V DC 40 40

80 100–240 V AC 40 40

Relay

Relay

80 100–240 V AC 40 40 Transistor (source type)

128 100–240 V AC 64 64

Output type

80 24 V DC 40 40 Transistor (source type)

Relay

128 100–240 V AC 64 64 Transistor (source type)

50 VA 1.20 285 x 90 x 86

45 W 1.20 285 x 90 x 86

50 VA 1.20 285 x 90 x 86

65 VA 1.80 350 x 90 x 86

65 VA 1.80 350 x 90 x 86

165240

169503

168589

169504

169506

Power consumption Weight Dimensions (W x H x D) Order information

45 W kg 1.20 mm 285 x 90 x 86 Art. no. 169493

25

MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:03

25

Page 26

Farbprofil: Deaktiviert Komposit Standardbildschirm

BASE UNITS FX3U SERIES ///

¨ FX1S ¨ FX1N ¨ FX2N þ FX3U

왎 Base Units Environmental Specifications

FX BASE UNITS

General specifications

Data

Ambient temperature

0 – 55 °C (storage temperature: -25 – +75 °C)

Protection

IP 10

Noise durability

1000 Vpp with noise generator; 1 µs at 30 – 100 Hz

Dielectric withstand voltage

AC PSU: 1500 V AC, 1 min. / DC PSU: 500 V AC, 1 min.

Ambient relative humidity

5 – 95 % (non-condensing)

Shock resistance

Acc. to IEC 68-2-27: 15G (3 times each in 3 directions for 11 ms)

Vibration resistance

Acc. to IEC 68-2-6: 1G (resistance to vibrations from 57 - 150 Hz for 80 minutes along all 3 axes); 0.5G for DIN rail mounting

Insulation resistance

500 V DC, 5 MΩ

Ground

Class D: Grounding resistance 100 Ω or less

Fuse

From FX3U-16M첸 to FX3U-32M첸: 3.15 A; From FX3U-48M첸 to FX3U-128M첸: 5 A

Environment

Avoid environments containing corrosive gases, install in a dust-free location.

Certifications

Please refer to page 82 in this catalogue

Electrical Specifications Power supply specifications

DC powered modules (FX3U- M /DS/DSS)

AC powered modules (FX3U- MR/ES)

Output specifications

Power supply

24 V DC (+20% / -30 %)

100 – 240 V AC (+10 % / -15 %), 50/60 Hz

Switching voltage (max.)

V < 240 V AC, < 30 V DC

5 – 30 V DC

Max. output current

A 2

0.5 / 0.3햲

- per group*

A 8

0.8 / 1.6햳

- inductive load, 30 A / <5 ms (at 100 V AC); 65 A / <5 ms (at 200 V AC)

Allowable momentary power failure time

5 ms

10 ms

Max. switching current

Primary power supply

24 V DC, Response time

80 VA ms 10

햴

FX3U-16/32MR/ES: 400 mA / FX3U-48–128MR/ES: 600 mA

Transistor modules

- per output

Inrush current at ON

External power supply (24 V DC), Type Relay modules

Life of contacts (switching times)

햲 for Y0 and Y1 = 0.3 A; all others 0.5 A

햴 Not guaranteed by Mitsubishi Electric.

12 W / 7.2 W <0.2(Y0,Y1<30 µs)

3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA 햳 0.8 for 4 per group and 1.6 for 8 per group

* This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification.

Programming Specifications System specifications

FX3U

System specifications

Program data

FX3U

Operands

I/O points (addresses)

Max. total 384 (with remote I/O)

Internal relays

7,680

Address range

Max. 256 direct addressing and max. 256 network I/Os

Special relays

512 4,096

Program memory

64,000 steps RAM (internal), exchangeable FLROM for easy program exchange

State relays Timer

512

Cycle period

0.065 µs /basic instruction

Counter

235

Number of instructions

27 sequence instructions, 2 step ladder instructions, 209 applied instructions

High-speed counter

16

Programming language

Step ladder, instruction list, SFC

High-speed counter speed

1 phase, 8 points max: 100kHz / 6 points 10kHz / 2 points 2 phase, 2 points max: 50kHz / 2 points

Program execution

Cyclical execution, refresh mode processing

Program protection

Password protection with 3 protection levels*

* Protection levels may only be changed with FX-20P-E and FX-10P-E.

26

FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:04

Real-time clock

Year, month, day, hour, minute, second, weekday

Data register

8,000

Extension file register

32768

Index register

16

Special register

512

Pointer

4,096

Nestings

8

Interrupt inputs

6

Constants

16 bits: K: -32768 to +32768, hex: 0–FFFF; 32 bits: K: -2147483648 to +2147483647; hex: 0–FFFF FFFF

MITSUBISHI ELECTRIC 26

Page 27

Farbprofil: Deaktiviert Komposit Standardbildschirm

/// COMPACT EXTENSION UNITS

¨ FX1S þ FX1N þ FX2N þ FX3U

왎 Powered Compact Extension Units

Extension Units FX0N The FX0N series extension units are available with 40 input/ output points. It is possible to choose between relay and transistor output type.

Special Features:

Specifications Electrical data Integrated inputs/outputs AC range (+10%, -15%) Power Frequency at AC Hz supply DC range (+20%, -15%) Max. input apparent power 100 V AC Inrush current at ON 200 V AC 24 V DC Allowable momentary power ms failure time External service power supply (24 V DC) mA Inputs Integrated inputs Min. current for logical 1 mA Max. current for logical 0 mA Response time Outputs Integrated outputs Output type Max. switching voltage A Max. output - per output current - per group* A Max. switching - inductive load VA power Response time ms Life of contacts (switching times)햳 Mechanical data Weight kg Dimensions (W x H x D) mm Order information

FX0N-40 ER-ES/UL

FX0N-40 ER-DS

FX0N-40 ET-DSS

40 100 – 240 V 50/60, 40 VA 30 A / 5 ms 50 A / 5 ms, 40, - 24 V 20 W, - 60 A / 50 µs

40, - 24 V 30 W, - 60 A / 50 µs

10

5

5

200, - 24 24 3.5 3.5 1.5 1.5 For all base units of the MELSEC FX0N series: 10 ms (at time of shipment)

24 3.5 1.5

16 16 Relay Relay Generally for relay version: < 240 V AC, < 30 V DC; for transistor version: 5 – 30 V DC 2 2 5 5

16 Transistor

80

12

80

EXTENSION MODULES

앬 LEDs for indicating the input and output status 앬 MELSEC FX1N series compatible 앬 Integrated service power supply with up to 200 mA capacity

0.5 0.8햲

10 10 < 0.2 For all extension units of the MELSEC FX0N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (only for relay output) 0.75 150 x 90 x 87

Art. no. 60012

0.75 150 x 90 x 87

0.75 150 x 90 x 87

55955

55954

햲 0.8 for 4 per group

햳 Not guaranteed by Mitsubishi Electric.

* This limitation applies only per reference terminal for each group. Please observe the terminal assignments for the group identification.

27

MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:10

27

Page 28

Farbprofil: Deaktiviert Komposit Standardbildschirm

COMPACT EXTENSION UNITS ///

¨ FX1S þ FX1N þ FX2N þ FX3U

왎 Powered Compact Extension Units

Extension Units FX2N The FX2N series extension units are available with 32 or 48 input/output points. It is possible to choose between relay and transistor output type.

Special Features:

EXTENSION MODULES

앬 LEDs for indicating the input and output status 앬 MELSEC FX1N/FX2N and FX3U series compatible 앬 Detachable terminal blocks 앬 Integrated service power supply with 250 mA or 460 mA

FX2N-32 ER-ES/UL

FX2N-32 ET-ESS/UL

FX2N-48 ER-DS

FX2N-48 ER-ES/UL

FX2N-48 ET-DSS

FX2N-48 ET-ESS/UL

32 100 – 240 V 50/60, 35 VA 40 A < 5 ms 60 A < 5 ms

32 100 – 240 V 50/60, 35 VA 40 A < 5 ms, 48, - 24 V 30 W, - 48 100 – 240 V 50/60, 45 VA 40 A < 5 ms 60 A < 5 ms

48, - 24 V 30 W 40 A < 5 ms 60 A < 5 ms

48 100 – 240 V 50/60, 45 VA 40 A < 5 ms 60 A < 5 ms

10

10

5

10

5

10

250 690

250 690, 690

460 690, 690

460 690

16 16 24 24 3.5 3.5 3.5 3.5 1.5 1.5 1.5 1.5 For all extension units of the MELSEC FX2N series: 10 ms (at time of shipment)

24 3.5 1.5

24 3.5 1.5

16

16 24 24 Transistor Relay Relay Relay (source) Generally for relay version: < 264 V AC, < 30 V DC; for transistor version: 5 – 30 V DC A 2 0.5 2 2 A 8 0.8 / 1.6햳 8 8

24 Transistor (source)

24 Transistor (source)

0.5 0.8 / 1.6햳

0.5 0.8 / 1.6햳

W 80

12

12

Specifications Electrical data Integrated inputs/outputs AC range (+10 %, -15 %) Power frequency at AC Hz supply DC range (+20 %, -30 %) Max. input apparent power 100 V AC Inrush current at ON 200 V AC Allowable momentary power ms failure time External service power supply (24 V DC) mA Power supply int. bus (5 V DC) mA Inputs Integrated inputs Min. current for logical 1 mA Max. current for logical 0 mA Response time Outputs Integrated outputs Output type Switching voltage (max.) Max. output - per output current - per group * Max. switching - inductive load power Response time Life of contacts (switching times)햲 Mechanical data Weight Dimensions (W x H x D) Order information 햲 Not guaranteed by Mitsubishi Electric

12

80

80 ms 10 < 0.2 10 10 < 0.2 For all extension units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (for relay output only)

< 0.2 kg 0.65 mm 150 x 90 x 87 Art. no. 65568

0.65 150 x 90 x 87

0.85 182 x 90 x 87

0.85 182 x 90 x 87

0.85 182 x 90 x 87

0.85 182 x 90 x 87

65569

66633

65571

66634

65572

햳 0.8 for 4 per group and 1.6 for 8 per group

* This limitation applies only per reference terminal for each group. Please observe the terminal assignments for the group identification.

28

FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:16

MITSUBISHI ELECTRIC 28

Page 29

Farbprofil: Deaktiviert Komposit Standardbildschirm

/// MODULAR EXTENSION UNITS

¨ FX1S þ FX1N þ FX2N þ FX3U

왎 Unpowered Modular Extension Blocks

Extension Blocks FX2N The FX2N series modular extension blocks are available with 8 or 16 input/output points. It is possible to choose between relay and transistor output type.

Special Features: 앬 LEDs for indicating the input and output status 앬 MELSEC FX1N/FX2N and FX3U series compatible 앬 Very compact dimensions 앬 Vertically terminal blocks with a cable guide to the upper or

2

IN

OUT

EXTENSION MODULES lower side

FX2N-8EX-ES OUT

FX2N-16EYR-ES/UL

Specifications Electrical data Integrated inputs/outputs Power supply Inputs Integrated inputs Min. current for logical 1 Max. current for logical 0 Response time Outputs Integrated outputs Output type Max. switching voltage Max. output - per output current - per group햲 Max. switching - inductive load power Response time Life of contacts (switching times)햳 Mechanical data Weight Dimensions (W x H x D) Order information

FX2N-8 ER-ES/UL

FX2N-8 EX-ES/UL

FX2N-8 EYR-ES/UL

8 8 8 All modular extension blocks are supplied by the base unit.

FX2N-8 EYT-ESS/UL

FX2N-16 EX-ES/UL

FX2N-16 EYR-ES/UL

FX2N-16 EYT-ESS/UL

8

16

16

16

16 3.5 1.5, - - - - - 4 8, - mA 3.5 3.5, - mA 1.5 1.5, - For all extension blocks of the MELSEC FX2N series: 10 ms (at time of shipment) 4, 8

8, 16

Relay, Relay

Transistor, Relay

16 Transistor (source)

Generally for relay version: < 240 V AC, < 30 V DC; for transistor version: 5 – 30 V DC A 2, 2 0.5 A 8, 8 0.8, - 2 8

0.5 1.6

VA 80, 80

12, 80

12 ms 10 10 10 < 0.2, 10 For all extension units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (for relay output only)

< 0.2 kg 0.2 mm 43 x 90 x 87 Art. no. 166285

0.2 43 x 90 x 87

0.2 43 x 90 x 87

0.2 43 x 90 x 87

0.3 40 x 90 x 87

0.3 40 x 90 x 87

0.3 40 x 90 x 87

166284

166286

166287

65776

65580

65581

햲 This limitation applies only per reference terminal for each group. Please observe the terminal assignments for the group identification. 햳 Not guaranteed by Mitsubishi Electric

29

MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:22

29

Page 30

Farbprofil: Deaktiviert Komposit Standardbildschirm

ANALOG MODULES ///

¨ FX1S þ FX1N þ FX2N þ FX3U

왎 Analog Output Modules FX2N-2DA, FX2N-4DA, FX3U-4DA

The analog output modules provide the user with 2 to 4 analog outputs. The modules convert digital values from the FX1N/FX2N/FX3U controller to the analog signals required by the process. The module can output both current and voltage signals. Note: The FX3U-4DA can only be used in combination with a FX3U series base unit.

Specifications Analog channels FX3U -4DA

FX2N-2DA

Analog output range 24 V D/A

SPECIAL FUNCTION MODULES

FX3U-4DA

FX2N-2DA, 2 0 – +10 V DC / 0 – +5 V DC / 4 – +20 mA 2.5 mV (12 bits) 4 µA (12 bits) ±1 % 30 mA (from base unit) 85 mA (from base unit) 8 kg 0.3 mm 43 x 90 x 87 inputs outputs voltage current Fullscale overall accuracy 5 V DC Power supply 24 V DC Related I/O points Weight Dimensions (W x H x D) Resolution

Order information

Art. no. 102868

FX2N-4DA, 4 -10 – +10 V DC / 0 – +20 mA / 4 – +20 mA 5 mV (10 bits) 20 µA (11 bits + sign) ±1 % 30 mA (from base unit) 200 mA 8 0.3 55 x 90 x 87

FX3U-4DA, 4 -10 – +10 V DC / 0 – +20 mA / 4 – +20 mA 0.32 mV (16 bits +sign) 0.63 µA (15 bits) ±0.3 – 0.5 %*, 160 mA 8 0.2 55 x 90 x 87

65586

169509

* Dependent on the ambient temperature

¨ FX1S þ FX1N þ FX2N þ FX3U

왎 Analog Input Modules

FX2N-2AD, FX2N-4AD, FX3U-4AD, FX2N-8AD The analog input modules provide the user with 2 to 8 analog inputs. The module converts analog process signals into digital values which are further processed by the MELSEC FX1N/FX2N/FX3U controller. The actual values or mean values over several measurements may be output. FX 2N -2AD

Note: The FX3U-4AD can only be used in combination with a FX3U series base unit.

POWER

Specifications Analog channels

FX2N-2AD 2, 0 – +10 V DC / 0 – +5 V DC / 0/ 4 – +20 mA inputs outputs

Analog input range voltage

2.5mV, 1.25mV / 4 µA (12 bits)

Resolution current Fullscale overall accuracy

±1 % 20 mA (from base unit) 50 mA (from base unit) 8 kg 0.3 mm 43 x 90 x 87

5 V DC Power supply 24 V DC

MITSUBISHI FX2N-8AD POWER 24V

Related I/O points Weight Dimensions (W x H x D) Order information

Art. no. 102869

FX2N-4AD 4, -10 – +10 V DC / -20 – +20 mA / 4 – +20 mA 5 mV (11 bits + sign) 20 µA (10 bits + sign) ±1 % 30 mA (from base unit)

FX3U-4AD 4, -10 – +10 V DC / -20 – +20 mA / 4 – +20 mA 0.32 mV (16 bits + sign) 1.25 µA (15 bits + sign) ±0.3 – 1 %*, FX2N-8AD 8, -10 – +10 V DC / -20 – +20 mA / 4 – +20 mA 0.63 mV (14 bits + sign) 2.5 µA (13 bits + sign) ±0.3 – 0.5 %* 50 mA (from base unit)

55 mA

90 mA

80 mA

8 0.3 55 x 90 x 87

8 0.2 55 x 90 x 87

8 0.4 75 x 105 x 75

65585

169508

129195

*Dependent on the ambient temperature Note: The FX2N-8AD can be configured to accept standard analog inputs as well as selected temperature inputs such as K, T or J type thermocouples.

30

FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:33

MITSUBISHI ELECTRIC 30

Page 31

Farbprofil: Deaktiviert Komposit Standardbildschirm

/// ANALOG MODULES

¨ FX1S þ FX1N þ FX2N þ FX3U

왎 Combined Analog I/O Modules FX0N-3A, FX2N-5A

The analog input/output modules are available in two different models. They provide the user with 2 or 4 analog inputs and 1 analog output. They serve for conversion of analog process signals into digital values, and vice versa. As of the FX2N-5A module the analog inputs can be selected between current or voltage input signals. Note: The FX2N-5A may not be used in combination with a FX1N series base unit.

Number of analog points

FX2N -5A

FX0N-3A

FX0N-3A 2 1 0 – +10 V (8 bit), 0 – +5 V (8 bit)

inputs outputs voltage

24 V AD / DA

Input (resolution)

FX2N-5A Output (resolution)

current

0/4 – +20 mA (8 bit)

voltage

0 – +10 V (8 bit), 0 – +5 V (8 bit) 4 – +20 mA (8 bit) ±1 % 30 mA (from base unit) 90 mA (from base unit) 8 kg 0.2 mm 43 x 90 x 87 current Total accuracy Power supply

5 V DC 24 V DC

Related I/O points Weight Dimensions (W x H x D) Order information

FX2N-5A 4 1 -10 – +10 V (15 bit + sign), -100 – +100 mV (11 bit + sign) -20 – +20 mA (14 bit + sign), 0/4 – +20 mA (14 bit) -10 – +10 V (12 bit) 0/4 – +20 mA (10 bit) ±0.3 – 1 %* 70 mA (from base unit) 90 mA 8 0.3 55 x 90 x 87

Art. no. 41790

153740

*Dependent on the ambient temperature

왎 Analog Temperature Input Modules

¨ FX1S ¨ FX1N þ FX2N þ FX3U

FX2N-4AD-TC, FX2N-4AD-PT, FX2N-2LC The analog input module for thermocouples FX2N-4AD-TC is used for processing temperatures. It has 4 independent inputs for detecting signals from thermocouples of types J and K. The type of thermocouple can be chosen independently for each point. The analog input module for Pt100 inputs FX2N-4AD-PT permits the connection of four Pt100 sensors to the FX2N/FX3U series controller. The temperature control module FX2N-2LC is equipped with two temperature input points and two transistor (open collector) output points. It is used to read temperature signals from thermocouples and Pt100 sensors, and performs PID output control

FX2N -4AD-TC

Note: The FX2N-2LC may not be used in combination with a FX1N series base unit. A/D

Specifications Analog inputs

FX2N-4AD-PT 4 (Pt100 sensors)

Resolution

FX2N-4AD-TC 4 (J or K type) – +600 (J type) / °C -100 -100 – +1200 (K type) -1000 – +6000 (J type) / -1000 – +12000 (K type) 0.3 (J type) / 0.4 (K type)

Total accuracy

±0.5 % fullscale +1 °C

±1. 0 % fullscale

Compensated temperature range Digital outputs

Power supply

5 V DC 24 V DC

40 mA (from base unit) 60 mA 8 kg 0.3 mm 55 x 90 x 87

Related I/O points Weight Dimensions (W x H x D) Order information

Art. no. 65588

-1,000 – 6,000 (12 bit conversion) 0.2 – 0.3 °C

2 transistor output points

30 mA (from base unit) 50 mA 8 0.3 55 x 90 x 87

0.1 °C or 1 °C ±0.7 % fullscale (±0.3 % when ambient temperature is 23 °C ±5 °C) 70 mA (from base unit) 55 mA 8 0.3 55 x 90 x 87

65587

129196

31

MITSUBISHI ELECTRIC FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:40

-100 – +600

FX2N-2LC 2 points Thermocouple and Pt100 sensor

31

SPECIAL FUNCTION MODULES

Specifications

Page 32

Farbprofil: Deaktiviert Komposit Standardbildschirm

ANALOG MODULES ///

¨ FX1S ¨ FX1N ¨ FX2N þ FX3U

왎 Analog Temperature Input Adapters

FX3U-4AD-TC-ADP, FX3U-4AD-PT-ADP The analog input adapter for thermocouples FX3U-4AD-TC-ADP is used for processing temperatures. It has 4 independent inputs for detecting signals from thermocouples of types J and K. The analog input adapter module for Pt100 inputs FX3U-4AD-PT-ADP permits the connection of four Pt100 sensors to the FX3U series controller.

FX3U -4AD-TC-ADP

24-

24+

POWER

L1+

J-type

•ú

•ú

Note: These adapters can only be used with the FX3U and they require a function extension board.

L2+

L1-

FX3U -4AD-PT-ADP

Specifications Analog inputs

L4-

L4+

24-

L3-

24+

L3+

L2-

POWER

°C

J-type

•ú

•ú

Compensated temperature range

L2+

L1-

L1+

Digital outputs

L2-

Resolution Total accuracy

L4-

L4+

L3-

L3+

FX3U-4AD-TC-ADP

SPECIAL FUNCTION MODULES

Power supply

FX3U-4AD-PT-ADP

°C 5 V DC 24 V DC

Related I/O points Weight Dimensions (W x H x D)

kg mm

Order information

FX3U-4AD-TC-ADP 4 (J or K type) -100 – +600 (J type) / -100 – +1000 (K type) -1000 – +6000 (J type) / -1000 – +10000 (K type) 0.3 (J type) / 0.4 (K type) ±0.5 % fullscale 15 mA (from base unit) 45 mA 0 0.1 17.6 x 90 (106) x 89.5

Art. no. 165273

FX3U-4AD-PT-ADP 4 (Pt100 sensors) -50 – +250 -500 – +2500 0.1 ±0.5 – 1.0 % fullscale* 15 mA (from base unit) 50 mA 0 0.1 17.6 x 90 (106) x 89.5 165272

*Dependent on the ambient temperature

¨ FX1S ¨ FX1N ¨ FX2N þ FX3U

왎 Analog I/O Adapters FX3U-4AD-ADP, FX3U-4DA-ADP

The FX3U-4AD-ADP adapter module for analog input is a special function adapter to add four analog input points to the FX3U PLC system. The FX3U-4DA-ADP adapter module for analog output is a special function adapter to add four analog output points to the FX3U PLC system. Note: These adapters can only be used with the FX3U and they require a function extension board.

FX3U -4DA-ADP

Specifications Analog channels

FX3U-4AD-ADP 4, 0 – +10 V DC, 4 – +20 mA 2.5 mV / 10 µA (12 bit / 11 bit ) ±0.5 %* / ±1 % 15 mA (from base unit) 40 mA 0 kg 0.1 mm 17.6 x 90 (106) x 89.5 inputs outputs

Analog range Resolution Overall accuracy

V3+

COM2

I2+

V2+

COM1

I1+

V1+

24-

24+

POWER

Power supply

COM4

I4+

V4+

COM3

I3+

FX3U-4AD-ADP

FX3U-4DA-ADP

5 V DC 24 V DC

Related I/O points Weight Dimensions (W x H x D) Order information

Art. no. 165241

FX3U-4DA-ADP, 4 0 – +10 V DC, 4 – +20 mA 2.5 mV / 4 µA (12 bit) ±0.5 %* / ±1 % 15 mA (from base unit) 150 mA 0 0.1 17.6 x 90 (106) x 89.5 165271

*Dependent on the ambient temperature and signal quality

32

FX1-Cat 2006 Euro GB23-44.prn FX1-Cat 2006 Euro GB Donnerstag, 20. April 2006 20:20:50

MITSUBISHI ELECTRIC 32