The text of a manual · part 2 of 3

Programmable Controllers FX2n Series: Amazing Performance in a Compact Body, pages 9 to 16

Pages 9 to 16 of 23

The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi FX2N-16MR

Page 9 read from a scan by OCR; it may hold reading errors

Open Networks

Linking to Open Networks

The integration of different control systems is often achieved through the use of open networks which provide a common fink between the systems. Open Networks are non-proprietary networks which many manuafacturers equipment can connect to. Presently FXon and FX2n base units can connect to Profibus-DP and CCLink, however this line of products is constantly expand-ing so contact your Mitsubishi dealer for the latest news.

Profibus-DP

There are 2 options for connecting to Profibus-DP;the FXon-32NT- DP and the FX2n-32DP-IF.

FXON-32NEDP a The FXon-32NE-DP module can be used to connect an FXon /FX2N °° base unit onto an existing Profibus DP network as an intelligent oo slave. Up to 20 words of data may be sent/received to/from a master, and speeds of up to 12 Mbaud are supported. This module uses standard TO/FROM commands to communicate with the PLC.

FX2N-32DPIF

The FX2n-32DP-4IF module be used to connect FX2N/ FXon digital Y/O and special function block directly to an existing PROFIBUS. DP network. Digital and Analogue from a profibus-DP master PLC can be sent/received to/from any of the supported 1/O blocks and special function blocks. Up to 256 I/O points or 8 special function blocks can be connected to this unit, limited only by the power supply and the data capability of the master. Baud rates of up to 12 Mbps are supported.

CC-Link

FX2n-32-CCL

The FX2n-32-CCL connects the FX2N/FXON programmable controller to the CClink and is regarded as a remote device station in the CClink network.The data transfer rate, the station FXau-320CL number and the number of occupied stations are set using built = rowen in rotary switches. Data is transferred via the buffer memory using ene standard TO/FROM instructions. Baud rates of up to 10 Mbps are supported.

Page 10 read from a scan by OCR; it may hold reading errors

Programming Tools

Computer Based Programming

Mitsubishi offers a selection of programming tools and operation panels which are designed to be easy to use, practical and common to all its controllers. Both computer software and hand held devices for programming and simple text or more advanced graphic display units for operator control.

Programming and Documentation Software

MEDOC'S simple program structuring and documentation make programs easy to understand, debug, and edit. By using MEDOC to comment a program when it is written, users can separate each program routine clearly. Additionally comments also help in the understanding of program functions, especially if an old program is being revisited.

Two windows based software packages are available to program the FX2n series. The sophisticated Melsec Medoc Plus (MM+) for programming in IEC standard programming language or for those already familiar with the earlier MELSEC MEDOC, MM+ can also program in "MELSEC" mode.

A simple but noJess functional package is the FX-PCS-WIN-E software for the FX family. Easily program in instruction list, familiar ladder or SFC (sequence function chart) simultaneously for any FX controller.

All the software packages include the following features, Fulltime help facility provides an explanation at any stage of any process.

Simple graphical ladder and direct instruction/list programming / monitoring capabilities.

Programming during RUN allows changes to be made to the program without having to STOP the machine

Powerful moving and copying utilities and time saving editing functions.

‘Hot' key quick access to features.

Extensive professional printing capabilities provide printouts of ladder, lists, device names, comments and program expla-nations as required.

Fasy printer setup routines to help the first time user.

sea EX20P a ea Ge)

N

RAR aD ae

As well as computer software there are two hand held pendant style programming devices for the FX-series. Although these will need to be up graded to support the full range of FX2n devices and instructions they can still be used with the FX2n as is up to the instruction and device range of the existing FX-series.

= f+ a, - +

Page 11 read from a scan by OCR; it may hold reading errors

FX-50DU-TK-E and FX50DU-TKS-E: Touch Screen Graphic Display Units

Both FX-SODU models have touch screen operation. There is a choice of monochrome ( FX-5ODU-TE-E ) and color display ( FX-5ODU-TKSE ) capabilities to enable users to create better, clearer operating systems. In fact up to 500 individual screens can be constructed by the user, these are in addition to many standard ‘built-in’ screens. Simple text and device monitoring display units are also available.

¢ The sampling function, where two data devices can be sampled and have their data stored and displayed in either tab-uler or graphical formats.

* Graph mode, where four data devices can be read for ‘live’ data from the programable controller.

¢ Alarm setting and alarm history displays, where users can set up error conditions/warnings and view past or active alarms from a ‘history’ of occurences.

* Use and display of bit map images.

« Automatic 'text' diagnostics for the “parent” programmable controller identifying the current operational status of the monitored unit.

¢ FXos, FXon, FX2n and A series compatibility.

The MAC (MTA) Family: Text and Graphical Operator Interfaces

Seldom is one type of operator interface or data access unit acceptable for all applications. Some require simple text and data display, some require text, data, and function keys, and some require graphics and animation to effectively show what is hap-pening in a process.This is where the MAC (MTA) family of OI products excels. Configured with an easy-to-use Windows-based programming software, and Ranging from simple text and data displays to high function graphic terminals, there's an MTA perfect for any control application.

Page 12 read from a scan by OCR; it may hold reading errors

It

Full Range of Programming Instruction

List of Instructions - 27 Basic instructions

Mnemonic Function Target Element LD Normally-open initial contact XYMS.LC LDI Normally-closed initial contact X¥M,S,TC

QUT Output coil XYM,S,T.C AND Normally-open contact in series XYMS,T.C ANI Normally-closed contact in series XY¥M,S,T.C OR Normally-open contact in parallel XY¥M,S,TC ORI Normally-closed contact in parallel XMS, 0.0 ANB Serial connection of circuit blocks None

ORB Parallel connection of circuit blocks None

NOP No-operation None

SET Latched output drive ON YM,S

RST Latched output drive OFF YM,S,T.C,D PLS Pulse output (OFF/ON trigger) YM

PLF Pulse output (ON/OFF trigger} YM

27 Basic Instructions

* ON/OFF Contact Instructions Conventional contact instructions like LD,AND, and OR have been supplemented by several new ON/OFF pulse contact instructions, such as LDP and LDE Prior to this, the input contact point was detected separately, then the contact of a pulse instruction was used to drive the final instruction. The additional instructions help to simplify programming by allowing operations to be performed at a single instruction.

New instructions

ON detect OFF detect LDP LDF ANDP ANDF ORP ORF

* Invert Operation Result Instruction This instruction inverts the ON or OFF image during an operation and reflects it in the next step. In the circuit below when X001 is ON, M100 is OFF and X002 is ON, YOO1 is OFE Using the INV instruction inverts the results of the operation so far,so that YOO1 becomes OFE This allows the simple negation of complex circuits or an inverse function for the new LDP, LDF pulse contact instructions.

When the INV instruction is used: X001 ON X002 ON INV OFF M100 OFF X001:0N

[- - - Mio0:OFF} =Y001:0FF X002:0N

Mnemonic Function Target Element MC Beginning of master control YM MCR End of master control None MPS Result store (Push) None MRD Result read (Read) None MPP Result clear (Pop) None END End of program None LDP Initial ON pulse operation XYMSTC NEW LDF Initial OFF pulse operation XYMST.C NEW ANDP Serial connection of ON pulse XYM.S,L.C NEW ANDF Serial connection of OFF pulse XYMS,T.C NEW ORP Parallel connection of ON pulse XYMSTC NEW ORF Parallel connection of OFF pulse XYMS,T.C NEW INV Result invert None NEW

¢ Conventional sequence program

LD Pulse output x000 (OFF - ~ON trigger) | | PLS mo Mo SET Yoo) NG In the case of the FX2n LDP X000 t| SET vot

125 Applied Instructions

¢ 18 Additional Compare Instructions

Compare instructions which can be used as contact instructions have been added to the existing Compare instructions (FNC 10 CMP) and Zone Compare (FNC 11 ZCP).=, <,>,4, Sand 2 can also be used as LD, AND and OR contacts. Since the new instruction treats the results as contacts, it does not monopolize them.

¢ Other New Instructions

Several other applied instructions have been added.

- 3 trigonometrical functions: SIN, COS,TAN

- 2 Gray code convert instruction: Convert, Reverse Convert

- 6 Real time data instructions:Time value Read/Write, Compare, Zone Compare, Add, Subtract

Page 13 read from a scan by OCR; it may hold reading errors

18 New Compare Instructions

1=Mnemonic 2= 32-bit Operation 3=Pulse Operation

107 Applied Instructions

= fave | Me 1 2] 3 Details Me 4 ja} 3 Details

224 | _LD= | Yes Initial Comparison contact - active when (S1) = (S2} NEW 236 | AND<x Yes Comparison contact in series - active when (S1) # (S2} NEW 225 | LD> | Yes Initial Comparison contact - active when ($1) > (82) NEW 237 | AND<3 Yes Comparison contact in series - active when (S1) < (62) NEW 226 | LD< | Yes Initiai Comparison contact - active when (St) < (82) NEW 238 | AND>= Yes Comparison contact in series -active when (S1) > (S2) NEW 228 | LD | Yes Initial Comparison contact - active when (St) # (S2) NEW 240 | OR= | Yes Comparison contact in parallel - active when (S1} = (82) NEW 229 | LD<=| Yes initial Comparison contact - active when (S1)} < (S2} NEW 241 | OR> | Yes Comparison contact in parallel - active when (S1) > ($2) NEW 230 | LD>=| Yes Initial Comparison contact - active when (S1} > (82) NEW 242 | OR« | Yes Comparison contact in parallel - active when (51) < ($2) NEW 232 | AND=| Yes Comparison contact in series - active when (S1) = (S2} NEW 244 | OR | Yes Comparison contact in parallel - active when (S1) (62) NEW 233 | AND>| Yes Comparison contact in series - active when (S1) > (S2} NEW 245 | OR<| Yes Comparison contact in parallel - active when (S1) < (62) NEW 234 | AND<| Yes Comparison contact in series - active when (S1) < ($2) NEW 246 | OR>=| Yes Comparison contact in parallel - active when (S1) > (S2) NEW

1=Mnemonic 2= 32-bit Operation 3=Pulse Operation

MC 4 2 | 3 Details PMC. yd | 2 [3 Details

0) G Yes | Conditional Jump - Skip instruction 54 | HSCR | Yes High Speed Counter reset - Compare HSC data to a set value to reset a bit OFF

1 | CALL Yes | Sub-routine Call - Call routine outside main program 55 | HSZ_ | Yes HSC Zone Compare - Compare HSC data to a selected range to set a bit ON

2 | SRET Sub-Routine Return - Return fo main program 56 | SPD Speed Detect - Detect speed by measuring pulse train

3 | IRET interrupt Return - Return from an interrupt routine 57 | PLSY | Yes Pulse Y - Produce 2 pulse train output consisting of a set number of pulses

4 El Interrupt Enable - Enable interrupt processing 58 | PWM Pulse Width Modulation - Produce a pulse train with variable pulse characteristics

5 | Ol Interrupt Disable - Disable interrupt processing 59_| PLSR | Yes Puise R - Produce @ pulse train output with acceleration/deceleration control NEW

6 | FEND First End - End main program 60 | IST Initial State - Additional control for stepladder program flow

7 | WOT Yes | Watchdog Timer - Refresh error detector 61 | SER | Yes | Yes | Search - Search for data

8 | FOR For - Begin repeat loop 62 | ABSD | Yes Absolute Drum Sequence - CAM switch control (absolute setting)

9 | NEXT Next - End repeat loop 63 | INCD Incremental Drum Sequence - CAM switch control (relative setting)

10 | CMP | Yes | Yes | Compare - Compare to obtain <, =, > results 64 | TTMR Teaching Timer - Measure duration of signal, use data to set timer

11 | ZCP | Yes | Yes | Zone Compare - Compare range of data to one value 65 | STMR Special Timer - Provide special timer functions

42 | MOV | Yes | Yes | Move - Copy data 66 | ALT Yes | Alternate - Altemate state of bit device an receipt of input

13 | SMOV Yes | Shift Move - Manipulate decimal digi 67 | RAMP Ramp - Calculate tinear rate of change between data values

14} CML | Yes | Yes | Complement - Invert value 68 | ROTC Rotary Table Control - Provide positioning control for rotary table

15 | BMOV Yes | Block Move - Copy a block of data 89_| SORT Sort - Sort tabulated deta

16 | FMOV| Yes | Yes | Fill Move - Copy one data to multiple locations 70 | TKY | Yes Ten Key ~ Read selected inputs as though coming from a ten-key keypad 17 | XCH | Yes | Yes | Exchange - Swap data 71 | HKY | Yes Hexadecimal Key - Read selected inputs as though coming from a HEX keypad 18 | BCD | Yes | Yes | Binary Coded Decimal - Convert binary into BCD 72 | DSW Digital Switch - Multiplex read of digital switches, 19 | BIN | Yes | Yes | Binary - Convert BCD into binary 73 | SEGD Yes | Seven Segment Decoder - Decode stored data to dive 7-segment display directly | ADD | Yes | Yes | Add - Add two values and store result 74 | SEGL Seven Segment With Laich - Multiplexed 7-segment display output

21 | SUB | Yes | Yes | Subtract - Subtract one value from another and store result 7 | ARWS Arow Swich - Crea user-defined numeric data ety pane

22 | MUL | Yes | Yes | Multiply - Multiply two values and store resut £ = ea ae fone Scat srr {ASC

23} DIV | Yes | Yes | Divide - Divide one value by another and store result 78 | FROM | Yes | Yes From Peat ton sci iunchor bck a ne ‘ \e alin aise eves 1 79 | TO | Yes | Yes | To- Write to special function block

26 | WAND | Yes | Yes | Word and Logical and between data words 80 | RS RS Communications - Serial communication control a7 | WOR | Yes | Yes | Word or - Logical or between cala words 81 | PRUN j Yes | Yes | Parallel Running - Octal data bit transfer

98 | wxoR| Yes | Yes | Word Exclusive ar - Loaical X ; 82 | ASCI Yes | ASCII Conversion - Convert from HEX to ASCII gical or operation 83) HEX Yes | Hex Conversion - Convert from ASCII to HEX

29 | NEG | Yes | Yes | Negation = lve sign complement 84 | CCD Yes | Check Code - Perform and end bit sum check x a \ ve a ran Ramanan ~ wn 85 | VRRD Yes | Variable Read - Read analog values fromm FXZN-8AV-BD potentiometers

32 | RCA | Yes | Yes | Rotation Right with Carry - ROR + store cary bit * VRSC Yes | Variable Scale - Read position values from FX2N-8AV-BD potentiometers 33 | RCL | Yes | Yes | Rotation Left with Carry - ROL + store carry bit - aa) | ig

34 | SER | | Yes | Shit Rignt- Shit content of bit device stack to ight | PID Loop - Proportional, integra, Derivative contol oop

35 | STL Yes | Shit Lf. - Shit content of bit device slack to let 118 | EBCD | Yes | Yes | Extended BCD - Conver floating point value to decimal value NEW 36 | WSFR Yes | Word Shift Right - Shift content of word device stack to right 419 | EBIN | Yes | Yes | Extended Binary - Convert decimal value to floating point value © NEW 37 | WSFL Yes Word Shift left - Shift content of word device stack to left 420 | EAOD | Yas | Yes | EADD - Ada two floating point values NEW 38 | SFWR Yes | Shift Register Write - Write to FIFO stack 121 | ESUB | Yes | Yes | ESUB - Subtract one floating point value from another NEW SO | SFRD Yes |_ Shift Register Read -Reac from FIFO stack _ 122 | EMUL | Yes | Yes | EMUL - Multiply two ficating point values NEW 40 | ZRST Yes | Zone Reset - Reset a range of consecutive devices 123 | EDI | Yes | Yes | EDIV- Divide one floating point value by another NEW M4 | DECO Yes | Decode - Decode a dala value fo a single data bit 127 | ESQR | Yes | Yes | Extended SOR - Return the square root of a floating point value =» NEW 42 | ENCO Yes ) Encode Find which bitis ON 129 | INT_| Yes_| Yes |_ Integer - Convert a floating point value to an integer NEW 43) SUM | Yes | Yes | Sum- Count the number of ON bits 730 | SIN’ [Yes | Yes Sine - SIN tigonametrical function NEW 4 | BON | Yes | Yes | Biton Check - Check status of abit device 131 | COS | Yes | Yes | Cosine - COS trigonometrcal function NEW 45 | MEAN | Yes | Yes | Mean - Calculate mean 132 | TAN | Yes_| Yes | Tangent - TAN trigonometrical function NEW 46 | ANS Annunciator Set - Start a timing sequence to set an alarm bit ON 160 | TCMP Yes | Time Compare - Compare clock data NEW AT | ANR Yes | Annunciator Reset - Reset lowest actve alarm bit 161 | TZCP Yes | Time Zone Compare - Compare range of time data to one time value NEW 48 | SQR | Yes | Yes | Square Root - Return square root of source data (integer result) 162 | TADD Yes | Time Add - Add two time values NEW 49 | FLT | Yes | Yes | Floating Point - Convert integer to floating point notation 163 ) TSUB Yes | Time Subtract - Subtract one time value from another NEW 50 | REF Yes | Refresh - Refresh /Os 166 | TRO Time Read - Read time data NEW St | REFF Yes | Refresh and Filter Adjust - Refresh, and adjust input filter 167 | TWR Time Write - Write time data NEW 52 | MIR Matrix - Multiplex /Os to Read more inputs than the number of /Os available 170 | GRY | Yes | Yes | Gray - Convert to Gray code NEW 53_| HSCS | Yes High Speed Counter Set - Compare HSC data to a set value to set a bit ON 171_| GBIN | Yes | Yes | Gray Binary - Reverse Gray code conversion to binary NEW

12

Page 14 read from a scan by OCR; it may hold reading errors

13

The FX2n Product Range

Available Models - Units

Power Model None inputs Outputs Dimensions Dimensions supply of YO Numer on Number Type (mm) (inches) FXen-16MR-ES/UL 16 8 8 87 x 90 x 130 3.4% 3.5 x 6.12 FXen-32MR-ES/UL 32 16 16 87 x 90 x 150 3.4x3.5x59 FXon-48MR-ES/UL 48 24 24 Relay 87 x 90 x 182 3.4x3.5x7.2 FXen-64MR-ES/UL 64 32 32 87 x 90 x 220 3.4x3.5x87 FXen-80MR-ES/UL 80 40 40 87 x 90 x 280 3.4x3.5x 11.2 ac. | PXe128MR-ES/UL 128 64 Sink/Source | 64 87 x 90 x 350 3.4x 3.5 x 13.8 FXon-1 6MT-ESS/UL 16 8 selectable 8 87 x 90 x 130 3.4x3.5x 5.12 FX2n-32MT-ESS/UL 32 16 16 87 x 90 x 150 3.4x3.5x 5.9 FX2n-48MT-ESS/UL 48 24 24 oe 87 x 90 x 182 3.4x3.5x7.2 FXen-64MT-ESS/UL 64 32 32 87 x 90 x 220 3.4x3.5x 87 FX2n-8OMT-ESS/UL 80 40 40 87 x 90 x 280 3.4x3.5x 11.2 FXen-128MT-ESS/UL 128 64 64 87 x 90 x 350 3.4x 3.5 x 13.8 Power Supply: AC 100-240V, + 10%/-15%, 50/60Hz. DC Powered Base Unit

Power Model Nanoer inputs Outputs Dimensions Dimensions supply of VO Number ee Nuniber Type (mm) (inches) FXen-32MR-DS 32 16 16 87 x 90 x 150 3.4x3.5x 5.9 FXen-48MR-DS 48 24 24 87 x 90 x 182 3.4x3.5x7.2

Relay FXen-64MR-DS 64 32 32 87 x 90 x 220 3.4x3.5x 87 - FX2n-8OMR-DS 80 40 Sink/Source 40 87 x 90 x 280 3.4x3.5x 11.2

FXen-32MT-DSS 32 16 selectable 16 87 x 90 x 150 3.4x3.5x5.9 FXen-48MT-DSS 48 24 24 Source 87 x 90 x 182 3.4x3.5x7.2 FXen-64MT-DSS 64 32 32 Transistor 87 x 90 x 220 3.4x 3.5 x 8.7 FXen-80MT-DSS 80 40 40 87 x 90 x 280 3.4x 3.5 x 11.2

Power Supply: DC 24V, +20%, -30%

Page 15 read from a scan by OCR; it may hold reading errors

val

YNOE-N2X4 SISTER

HGP X4 SATA

Tritt ose TERETE

Page 16 read from a scan by OCR; it may hold reading errors

Available Models - Powered Extension Units

Inputs Outputs Power Model Noor Dimensions Dimensions ode Numb Number i supply of 0 a er Type Type (mm) (inches) FXen-32ER-ES/UL 32 16 16 87 x 90 x 150 3.4x3.5x 5.9 Relay FXen-48ER-ES/UL 48 24 Sink/Source 24 87 x 90 x 182 3.4x35x 7.2 AC FXon-32ET-ESS/UL 32 16 selectable 16 Source 87 x 90 x 150 3.4x3.5x59 FXen-48ET-ESS/UL 48 24 24 Transistor 87 x 90 x 182 3.4x3.5x7.2 Power Supply: AC 100-240V, +10%/-15%, 50/60Hz. Total Inputs Outputs ; ; ; ; Power Model Number [yy Numb, Dimensions Dimensions : ; of JO | of Type ot Type (mm) (inches) we FXen-48ER-DS 48 24 Sink/Source 24 Relay 87 x 90 x 150 3.4x3.5x 5.9 FXov-48ET-DSS 48 24 selectable 24 | Source Transistor] 87 x 90 x 150 3.4x3.5 x59

Power Supply: DC 24V, +20%, -30%

MITSUBISHI

AGELSRE FXan-32ER