Page 31

An Introduction to Programming

3.4

The Basic Instruction Set

The Basic Instruction Set The instructions of the PLCs of the MELSEC FX family can be divided into two basic categories, basic instructions and applied instructions, which are sometimes referred to as “application instructions”. The functions performed by the basic instructions are comparable to the functions achieved by the physical wiring of a hard-wired controller. All controllers of the MELSEC FX family support the instructions in the basic instruction set, but the applied instructions supported vary from model to model (see Chapter 5). Basic instruction set quick reference

Instruction

Function

Description

LD

Load

Initial logic operation, polls for signal state “1” (normally open)

LDI

Load invers

Initial logic operation, polls for signal state “0” (normally closed)

OUT

Output instruction

Assigns the result of a logic operation to a device

AND

Logical AND

Logical AND operation, polls for signal state “1”

ANI

AND NOT

Logical AND NOT operation, polls for signal state “0”

OR

Logical OR

Logical OR operation, polls for signal state “1”

ORI

OR NOT

Logical OR NOT operation, polls for signal state “0"

ANB

AND Block

Connects a parallel branch circuit block to the preceding parallel block, in series.

ORB

OR Block

Connects a serial block of circuits to the preceding serial block, in parallel.

LDP

Load Pulse, load on detection of rising edge of device signal pulse

LDF

Load Falling Pulse, load on falling device signal pulse

ANDP ANDF

Pulse signal instructions

AND Pulse, logical AND on rising device signal pulse AND Falling Pulse, logical AND on falling device signal pulse

ORP

OR Pulse, logical OR on rising device signal pulse

ORF

OR Falling Pulse, logical OR on falling device signal pulse

SET

Set device

RST

Reset device

MPS MRD MPP

Store, read and delete intermediate operation results

PLS Pulse instructions PLF

Assigns a signal state that is retained even if after input condition is no longer true

Reference Chapter 3.4.1 Chapter 3.4.2 Chapter 3.4.4

Chapter 3.4.5

Chapter 3.4.6

Chapter 3.4.7

Chapter 3.4.8

Memory Point Store, store an operation result in the stack Memory Read, read a stored operation result from the stack

Chapter 3.4.9

Memory POP, read a stored operation result and delete it from the stack Pulse, sets a device for one operation cycle on the rising pulse of the input condition (input turns ON) Pulse Falling, sets a device* for one operation cycle on the falling pulse of the input condition (input turns OFF)

Chapter 3.4.10

MC

Master Control

MCR

Master Control Reset

Instructions for activating or deactivating the execution of defined parts of the program

Chapter 3.4.11

INV

Invert

Inverts the result of an operation

Chapter 3.4.12

FX Beginners Manual

3–5

Page 32

The Basic Instruction Set

3.4.1

An Introduction to Programming

Starting logic operations Instruction

Function

Symbol

GX Developer FX

LD

Load instruction, starts a logic operation and polls the specified device for signal state “1”

F5

LDI

Load instruction, starts a logic operation and polls the specified device for signal state “0”

F6

A circuit in a program always begins with an LD- or LDI instruction. These instructions can be performed on inputs, relays, timers and counters. For examples of using these instructions see the description of the OUT instruction in the next section.

3.4.2

Outputting the result of a logic operation Instruction OUT

Function

Symbol

GX Developer FX

Output instruction, assigns the result of an operation to a device

F7

The OUT instruction can be used to terminate a circuit. You can also program circuits that use multiple OUT instructions as their result. This is not necessarily the end of the program, however. The device set with the result of the operation using OUT can then be used as an input signal state in subsequent steps of the program. Example (LD and OUT instructions) Instruction List

Ladder Diagram

X000 0

Y000

0 1

LD OUT

X000 Y000

These two instructions result in the following signal sequence: ON (1)

X0

OFF (0) ON (1)

Y0 OFF (0)

The condition of the LD instruction (poll for signal state “1”) is true so the result of the operation is also true (“1”) and the output is set.

3–6 t

MITSUBISHI ELECTRIC

Page 33

An Introduction to Programming

The Basic Instruction Set

Example (LDI and OUT instructions) Ladder Diagram

Instruction List

X000 0

0 1

Y000

LDI OUT

X000 Y000

ON (1)

X0

OFF (0) ON (1)

Y0 OFF (0)

The condition of the LDI instruction (poll for signal state “0”) is no longer true so the output is reset.

t

Double assignment of relays or outputs Never assign the result of an operation to the same device in more than one place in the program! The program is executed sequentially from top to bottom, so in this example the second assignment of M10 would simply overwrite the result of the first assignment.

You can solve this problem with modification shown on the right. This takes all the required input conditions into account and sets the result correctly.

FX Beginners Manual

X001

X003 M10

X004

X005 M10

X001

X003 M10

X004

X005

3–7

Page 34

The Basic Instruction Set

3.4.3

An Introduction to Programming

Using switches and sensors Before we continue with the description of the rest of the instructions we should first describe how signals from switches, sensors and so on can be used in your programs. PLC programs need to be able respond to signals from switches, buttons and sensors to perform the correct functions. It is important to understand that program instructions can only poll the binary signal state of the specified input – irrespective of the type of input and how it is controlled.

Make contact

When a make contact is operated the input is set (ON, signal state “1”)

Break contact

When a break contact is operated the input is reset (OFF, signal state “0”)

As you can imagine, this means that when you are writing your program you need to be aware whether the element connected to the input of your PLC is a make or a break device. An input connected to a make device must be treated differently to an input connected to a break device. The following example illustrates this.

Usually, switches with make contacts are used. Sometimes, however, break contacts are used for safety reasons – for example for switching off drives (see section 3.5). The illustration below shows two program sequences in which the result is exactly the same, even though different switch types are used: When the switch is operated the output is set (switched on). 24 V LD X000 OUT Y000

X000 0

Y000

X0 Switch operated ON

X0

OFF ON

Y0 OFF t 24 V LDI X000 OUT Y000

X000 0

Y000

X0

Switch operated ON

X0

OFF ON

Y0 OFF t

3–8

MITSUBISHI ELECTRIC

Page 35

An Introduction to Programming

3.4.4

The Basic Instruction Set

AND operations Instruction

Function

Symbol

AND

Logical AND (AND operation with poll for signal state “1” or ON)

ANI

Logical AND NOT (AND operation with poll for signal state “0” or OFF)

GX Developer FX

F5 F6

An AND operation is logically the same as a serial connection of two or more switches in an electrical circuit. Current will only flow if all the switches are closed. If one or more of the switches are open no current flows – the AND condition is false.

Note that the programming software uses the same icons and function keys for the AND and ANI instructions as for the LD and LDI instructions. When you program in Ladder Diagram format the software automatically assigns the correct instructions on the basis of the insertion position. When you program in Instruction List format remember that you can’t use the AND and ANI instructions at the beginning of circuit (a program line in ladder diagram format)! Circuits must begin with an LD or LDI instruction (see Chapter 3.4.1). Example of an AND instruction Ladder Diagram

Instruction List AND instruction

X000

X001

0

Y000

0 1 2

LD AND OUT

X000 X001 Y000

In the example output Y0 is only switched on when inputs X0 and X1 are both on: ON (1)

X0

OFF (0) ON (1)

X1

OFF (0) ON (1)

Y0 OFF (0)

t

FX Beginners Manual

3–9

Page 36

The Basic Instruction Set

An Introduction to Programming

Example of an ANI instruction Instruction List

Ladder Diagram ANI instruction

X000

X001

0

Y000

0 1 2

LD ANI OUT

X000 X001 Y000

In the example output Y0 is only switched on when input X0 is on and input X1 is off: ON (1)

X0

OFF (0) ON (1)

X1

OFF (0) ON (1)

Y0 OFF (0)

t

3 – 10

MITSUBISHI ELECTRIC

Page 37

An Introduction to Programming

3.4.5

The Basic Instruction Set

OR operations Instruction

Function

Symbol

OR

Logical OR (OR operation with poll for signal state “1” or ON)

ORI

Logical OR NOT (OR operation with poll for signal state “0” or OFF)

GX Developer FX

F5 F6

An OR operation is logically the same as the parallel connection of multiple switches in an electrical circuit. As soon as any of the switches is closed current will flow. Current will only stop flowing when all the switches are open.

Example of an OR instruction Instruction List

Ladder Diagram

X000 0

Y000

0 1 2

LD OR OUT

X000 X001 Y000

X001 OR instruction

In the example output Y0 is switched on when either input X0 or input X1 is on: ON (1)

X0

OFF (0) ON (1)

X1

OFF (0) ON (1)

Y0 OFF (0)

t

FX Beginners Manual

3 – 11

Page 38

The Basic Instruction Set

An Introduction to Programming

Example of an ORI instruction Ladder Diagram

Instruction List

X000 0

0 1 2

Y000

LD ORI OUT

X000 X001 Y000

X001 ORI instruction

In the example output Y0 is switched on when either input X0 is on or input X1 is off: ON (1)

X0

OFF (0) ON (1)

X1

OFF (0) ON (1)

Y0 OFF (0)

t

3.4.6

Instructions for connecting operation blocks Instruction

Function

ANB

AND Block (serial connection of blocks of parallel operations/circuits)

ORB

OR Block (parallel connection of blocks of serial operations/circuits)

Symbol

GX Developer FX

F9 uF9

Although ANB- and ORB are PLC instructions they are only displayed and entered as connecting lines in the Ladder Diagram display. They are only shown as instructions in Instruction List format, where you must enter them with their acronyms ANB and ORB. Both instructions are entered without devices and can be used as often as you like in a program. However, the maximum number of LD and LDI instructions is restricted to 8, which effectively also limits the number of ORB or ANB instructions you can use before an output instruction to 8 as well.

3 – 12

MITSUBISHI ELECTRIC

Page 39

An Introduction to Programming

The Basic Instruction Set

Example of an ANB instruction Ladder Diagram ANB instruction

X000

X001

0

Y007 M2

M10

Instruction List 0 1 2 3 4 5

LD ORI LDI OR ANB OUT

X000 M2 X001 M10

1st parallel connection (OR operation) 2nd parallel connection (OR operation) ANB instruction connecting both OR operations

Y007

In this example output Y07 is switched on if input X00 is “1”, or if relay M2 is “0” and input X01 is “0”, or if relay M10 is “1”. Example of an ORB instruction Ladder Diagram

X000

X001

0

Y007 M2

ORB instruction

M10

Instruction List 0 1 2 3 4 5

LD ANI LDI AND ORB OUT

X000 X001 M2 M10 st

1 serial connection (AND operation) 2nd serial connection (AND operation) ORB instruction connecting both AND operations

Y007

In this example output Y07 is switched on if input X00 is “1” and input X01 is “0”, or if relay M2 is “0” and relay M10 is “1”.

FX Beginners Manual

3 – 13

Page 40

The Basic Instruction Set

3.4.7

An Introduction to Programming

Pulse-triggered execution of operations Instruction

Function

Symbol

LDP

Load Pulse, loads on the rising edge of the device’s signal

LDF

Load Falling Pulse, loads on the falling edge of the device’s signal

ANDP

AND Pulse, logical AND operation on the rising edge of the device’s signal

ANDF

AND Falling Pulse, logical AND operation on the falling edge of the device’s signal

ORP

OR Pulse, logical OR operation on the rising edge of the device’s signal

ORF

OR Falling Pulse, logical OR operation on the falling edge of the device’s signal

GX Developer FX

In PLC programs you will often need to detect and respond to the rising or falling edge of a bit device’s switching signal. A rising edge indicates a switch of the device value from “0” to “1”, a falling edge indicates a switch from “1” to “0”. During program execution operations that respond to rising and falling pulses only deliver a value of “1” when the signal state of the referenced device changes. When do you need to use this? For example, suppose you have a conveyor belt with a sensor switch that activates to increment a counter every time a package passes it on the belt. If you don’t use a pulse-triggered function you will get incorrect results because the counter will increment by 1 in every program cycle in which the switch registers as set. If you only register the rising pulse of the switch signal the counter will be incremented correctly, increasing by 1 for each package. Note

Most applied instructions can also be executed by pulse signals. For details see chapter . 5). Evaluating a rising signal pulse Instruction List

Ladder Diagram

X001 M0

0

0 1

LDP OUT

X001 M0

ON (1)

X1

OFF (0) 1

M0 0

Relay M0 is only switched on for the duration of a single program cycle

3 – 14 t