Mitsubishi Electric beginners manual for the MELSEC FX family of programmable logic controllers: FX1S, FX1N, FX2N, FX2NC and FX3U. It explains what a PLC is and how it processes programs, the layout of each series' base units, bits, bytes and number systems, the basic instruction set with worked examples (an alarm system, a rolling shutter gate), inputs, outputs, relays, timers, counters and registers, applied instructions for moving, comparing and math, and the expansion modules available.
Its parts
- Introduction
- Programmable Logic Controllers
- An Introduction to Programming
- Devices in Detail
- More Advanced Programming
- Expansion Options
From the manual
Key facts from this manual
Each line names its page in the PDF.
Mitsubishi Electric beginners manual (article number 166388, Version A, 2006) for the MELSEC FX family of programmable logic controllers: FX1S, FX1N, FX2N, FX2NC and FX3U. It explains what a PLC is, how to pick a base unit, the layout of the FX2NC base units, and the basics of programming inputs, outputs, relays and timers. It closes with an overview of expansion options.
- Manual
- Beginners guide to installing, operating and programming MELSEC FX1S, FX1N, FX2N, FX2NC and FX3U PLCs p. 1, 3
- FX2NC-32 I/O
- FX2NC-32: 16 inputs and 16 outputs p. 21
- Inputs
- Floating inputs, isolated from the other PLC circuits by optical couplers p. 22
- Memory battery
- FX2NC: battery backs up RAM, latched timers, counters and relays, and the real-time clock p. 25
- Service power
- FX2NC: no built-in 24V DC service power supply for inputs and sensors p. 25
- Status LEDs
- FX2NC: POWER, RUN, BATT and ERROR LEDs plus input and output status LEDs p. 24
- FX2NC layout
- RUN/STOP switch, optional memory cassette slot, side extension bus, connectors for terminal strips, second interface for a CNV adapter p. 24
- I/O addressing
- FX2NC base units: 8, 16, 32 or 48 inputs from X00 and outputs from Y00, numbered in octal p. 60
- Programming
- FX-20P-E hand-held programming unit, or a PC or notebook with software such as GX Developer/FX p. 25
- Output current
- 2 A on 250 V AC with relay outputs; 0.5 A on 24 V DC; non-reactive loads p. 22
- Networks
- Communications modules for the FX2NC: Profibus/DP, AS-interface, DeviceNet, CANopen, CC-Link p. 102
- Special relays
- M8004 PLC error; M8005 low battery voltage; M8034 disables outputs while the program keeps running p. 62
What this manual walks you through
- What a PLC is and how it processes a program p. 17, 18, 19
- Choosing the right FX base unit p. 21
- Parts of the FX2NC base unit p. 24
- What each PLC component does p. 25
- Input and output numbering on each FX series p. 60
- Using special relays and timers in a program p. 62
- Expansion, analog, communications and positioning modules p. 101, 102
Good to know
- The manual is meant for trained, qualified electrical technicians. p. 7
- Only peripherals and expansion equipment recommended and approved by Mitsubishi Electric may be used. p. 7
- Expansion adapter boards are available for all FX lines except the FX2NC. p. 25
- With a memory cassette inserted, the PLC runs only the program stored in the cassette. p. 25
- An input below its rated switching voltage is not processed. p. 22
Questions this manual answers
How many inputs and outputs does an FX2NC-32 base unit have?
16 inputs and 16 outputs. p. 21
Does the FX2NC have a 24V DC service power supply?
No. The manual says the 24V DC service power supply for inputs and sensors is not provided on the FX2NC. p. 25
What does the battery in an FX2NC do?
It keeps the RAM contents and the latched timers, counters and relays during a power failure, and powers the real-time clock. p. 25
What happens when a memory cassette is fitted to an FX PLC?
The internal memory is disabled and the PLC runs only the program in the cassette. p. 25
How are FX2NC inputs and outputs numbered?
Inputs are X and outputs are Y, numbered in octal from X00 and Y00. p. 60