Manual · Mitsubishi
FX2NC (D/UL) Series Programmable Controllers Hardware Manual
Manual140 pagesPDF 2.3 MB
Hardware manual for Mitsubishi FX2NC (D/UL) series PLCs, including the FX2NC-32MT-D/UL main unit: installation, wiring, I/O and diagnostics.
Covers · 1 model
The models it covers
Summary
What is in it
The hardware manual for the Mitsubishi FX2NC (D/UL) series programmable controllers, such as the FX2NC-16MT, -32MT, -64MT and -96MT main units. It covers model names and system configuration rules, terminal layouts for main units and extension blocks, installation and mounting, the 24V DC power supply and grounding, input and output specifications (transistor, relay and triac), and diagnostics with error codes, battery replacement, maintenance and an instruction list.
Its parts
- Introduction
- Terminal layouts
- Installation notes
- Power supply
- Inputs
- Outputs
- Diagnostics
- Discontinued model
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Mitsubishi hardware manual (JY992D87201, revision F, June 2010) for the FX2NC (D/UL) Series programmable controllers: the FX2NC-16MT-D/UL, FX2NC-32MT-D/UL, FX2NC-64MT-D/UL and FX2NC-96MT-D/UL main units with their extension and special function blocks. It covers system configuration, installation, power and I/O wiring, and diagnostics. The site files it under the FX2NC-32MT, which the manual names in its D/UL version.
- Main unit
- FX2NC-32MT-D/UL: 16 inputs (24V DC sink) and 16 transistor (sink) outputs p. 13
- Power supply
- 24V DC +20%, -15%, ripple 5% or less p. 71
- 5V DC capacity
- FX2NC-32MT-D/UL: 560mA 5V DC current capacity p. 28
- Inputs
- 24V DC +20%, -15%, photocoupler isolated, 10ms response, adjustable 0-60ms on X000-X017 p. 79
- Transistor outputs
- FX2NC main unit: 5-30V DC, 0.1A per point, 0.8A per 8 points, 0.3A per point on Y000-Y003 p. 91
- Power cables
- Supplied with the main unit: FX2NC-100MPCB main unit power cable and FX2NC-100BPCB input block power cable, both 1m p. 21, 73
- Battery
- FX2NC-32BL, 3 year life p. 116, 118
- Output commons
- FX2NC-32/64/96MT-D/UL: 16 points per common p. 94
- Temperature
- 0 to 55 °C operating, -20 to 70 °C storage p. 54
- FX2N block adapter
- FX2NC-CNV-IF connects FX2N and FX0N extension and special function blocks p. 16
- RUN/STOP control
- RUN/STOP switch, a standard input (X000 to X017) set by parameters, or remotely from a PC p. 52
- Memory and clock
- Memory board / real time clock board connector; system diagram lists FX2NC-EEPROM-16, FX2NC-EEPROM-4C, FX2NC-EEPROM16C, FX2NC-ROM-CE1, FX2NC-RTC p. 24, 51
- Programming devices
- System diagram lists FX-20P-E, FX-30P, FX-10P-E, GX Developer and the FX-USB-AW RS422/USB converter p. 24
- Error flags
- M8004 error occurrence; M8005 battery voltage abnormally low; M8061 PC hardware error; M8064 parameter error; M8065 syntax error p. 119
What this manual walks you through
- Choosing main units, extension blocks and special function blocks p. 13, 14, 15, 16, 17, 18, 19, 20
- Totaling current consumption and I/O points of a system p. 28, 38
- Terminal layouts of main units and extension blocks p. 43, 44, 45, 46
- Controlling RUN and STOP by switch, input or remote p. 52, 53
- Wiring the 24V DC power supply and power cables p. 71, 72, 73, 74
- Wiring 24V DC inputs p. 79, 80, 81, 82
- Wiring transistor outputs p. 91, 92, 93, 94, 95
- Start-up checks and LED diagnostics p. 111, 112, 113
- Writing and checking a program p. 115
- Replacing the battery p. 116, 117
Good to know
- A battery swap should take no more than 20 seconds to keep the data held in RAM. p. 116
- Input extension and special function blocks should be powered before or together with the main unit when two supplies are used. p. 74
- Do not modify the data in register D8008; the system corrects it automatically on the FX2NC. p. 73
- Check that the BATT LED is off before transporting the PLC. p. 118
- Loads such as forward/reverse contactors need an external interlock. p. 93
Questions this manual answers
What power supply does the FX2NC-32MT-D/UL need?
24V DC, +20% / -15%, with ripple of 5% or less. p. 71
What does the BATT LED on an FX2NC mean?
Monitor M8006; if it is ON, save any program held only in RAM and replace the battery. p. 112
How do I connect FX2N extension blocks to an FX2NC?
Through the FX2NC-CNV-IF connector conversion adapter. p. 16
How much current can each FX2NC-32MT-D/UL output switch?
0.1A per point (0.3A on Y000 to Y003), and 0.8A per 8 points, at 5-30V DC resistive load. p. 91
Contents
Chapters and sections
Each line opens the PDF at its page.
- Front Cover1
- Mannual number3
- Guidelines4
- 1. Introduction13
- 2. Terminal layouts43
- 3. Installation notes49
- 3.1 Product outline50
- 3.2 FX2NC RUN/STOP Control52
- 3.3 General specifications54
- 3.4 PC mounting arrangements55
- 3.5 Connection of extension blocks to main unit57
- 3.6 DIN rail mounting57
- 3.7 Direct mounting58
- 3.8 Extension cable installation62
- 3.9 General notes63
- 3.10 Memory Board installation64
- 3.11 Wiring techniques65
- 3.12 Termination of connector style I/O66
- 3.13 Termination of screw terminals67
- 3.14 Termination of connector style I/O cables68
- 4. Power supply71
- 5. Inputs79
- 6. Outputs91
16 more lines, from page 111 on
The whole text · 18 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 31-3
- Guidelines4-6
- Contents7-12
- 1. Introduction, pages 13 to 2213-22
- 1. Introduction, pages 23 to 3223-32
- 1. Introduction, pages 33 to 4233-42
- 2. Terminal layouts43-48
- 3. Installation notes, pages 49 to 5649-56
- 3. Installation notes, pages 57 to 6457-64
- 3. Installation notes, pages 65 to 7065-70
- 4. Power supply71-78
- 5. Inputs79-90
- 6. Outputs, pages 91 to 10091-100
- 6. Outputs, pages 101 to 110101-110
- 7. Diagnostics, pages 111 to 120111-120
- 7. Diagnostics, pages 121 to 130121-130
- 8. Discontinued model131-134
- Pages 135 to 140135-140
The file