Page 13
FX2NC Series Programmable Controllers
1.
Introduction 1.
Introduction This manual covers the hardware installation instructions for the following programmable controller (PC) product ranges; - FX2NC main units. - FX2NC extension blocks and special function blocks Table 1.1 : Main units INPUT
OUTPUT
MODEL QTY
TYPE
QTY
FX2NC-16MT-D/UL
8
8
FX2NC-32MT-D/UL
16
16
FX2NC-64MT-D/UL
32
FX2NC-96MT-D/UL
48
24V DC Sink
32 48
TYPE
POWER SUPPLY
W
24V DC +20% -15% Transistor (Sink)
DIMENSIONS mm (inches) H
MASS kg (lbs)
D
35 (1.4) 60 (2.4)
Ripple Voltage 86 (p-p) (3.4) 5% or less
0.2 (0.44) 90 (3.5)
87 (3.4)
0.35 (0.77) 0.45 (0.99)
1-1
Page 14
FX2NC Series Programmable Controllers
Introduction 1.
Figure 1.1 :Main unit dimensions UNITS: mm (inches)
FX2NC-96M 86(3.39) FX2NC-64M 60(2.36) FX2NC-32M FX2NC-16M 35(1.38) RUN
STOP
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17
13 (0.5)
X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17
Power supply cable
DIN Rail: 35mm (1.38)
74(2.91)
87(3.43)
13 (0.51)
90(3.54)
POWER RUN BATT ERROR
1-2
Page 15
FX2NC Series Programmable Controllers
Introduction 1.
Table 1.2 : Extension blocks INPUT
MODEL
QTY FX2NC-16EX-D/UL
16
FX2NC-16EYT-D/UL
-
FX2NC-32EX-D/UL
32
FX2NC-32EYT-D/UL
-
FX0N-8EX-UA1/UL FX2N-8EX-UA1/UL
8
FX0N-8EX-ES/UL FX2N-8EX-ES/UL FX0N-8ER-ES/UL FX2N-8ER-ES/UL FX0N-8EYR-ES/UL FX2N-8EYR-ES/UL FX0N-8EYT-ESS/UL FX2N-8EYT-ESS/UL
8 4
TYPE 24V DC Sink 24V DC Sink 110V AC inputs 24V DC Sink/ Source
DIMENSIONS mm (inches)
OUTPUT QTY
DEVICE
TYPE
W
-
-
-
16
Transistor
Sink
14.6 (0.6)
-
-
-
32
Transistor
Sink
-
-
-
-
-
-
4
-
26.2 (1.0)
-
8
-
-
8
Transistor
Source
-
-
-
16 16
Relay Transistor
Source
FX0N-16EX-ES/UL
16
FX0N-16EYR-ES/UL FX0N-16EYT-ESS/UL
-
24V DC Sink/ Source -
90 (3.5)
D
87 (3.4)
43 (1.7)
Relay -
H
MASS kg (lbs)
0.2 (0.44)
0.2 (0.44) 90 (3.5)
-
0.15 (0.33)
87 (3.4)
70 (2.8)
0.3 (0.66)
1-3
Page 16
FX2NC Series Programmable Controllers
Introduction 1.
Table 1.2 : Extension blocks INPUT
MODEL
QTY FX2N-16EX-ES/UL
16
FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL
-
DIMENSIONS mm (inches)
OUTPUT
TYPE 24V DC Sink/ Source -
QTY
DEVICE
TYPE
-
-
-
16 16
Relay Transistor
Source
MASS kg (lbs)
W
H
D
40 (1.6)
90 (3.5)
87 (3.4)
0.3 (0.66)
Table 1.3 : Connector conversion adapter MODEL
FX2NC-CNV-IF
DESCRIPTION Extension blocks and special functions blocks of FX2N and FX0N is connected by this adapter
DIMENSIONS mm (inches)
MASS kg (lbs)
W
H
D
14.6 (0.6)
90 (3.5)
74 (2.9)
1-4
0.15 (0.33)
Page 17
FX2NC Series Programmable Controllers
Introduction 1.
Figure 1.2 :Extension block dimensions UNITS: mm (inches)
FX2NC-32E 26.2(1.03) FX2NC-16E 14.6(0.57)
74(2.91)
87(3.43)
13 (0.51)
90(3.54)
POWER X0 X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7
DIN Rail: 35mm (1.38)
Power supply connectors for input extension blocks
FX0N, FX2N Extension block dimensions →(See sec. 3.7)
1-5
Page 18
FX2NC Series Programmable Controllers
Introduction 1.
Figure 1.3 :Connector conversion adapter
90(3.54)
UNITS: mm (inches)
14.6(0.57)
74(2.91) DIN Rail: 35mm (1.38)
Table 1.4 :Special function blocks MODEL
DESCRIPTION
NUMBER OF I/O I
O
POWER SUPPLY Internal External 5V DC 24V DC
FX2N-2AD
-
8
-
20mA
50mA*1
FX2NC-4AD
-
8
-
50mA
130mA
FX2N-4AD
-
8
-
30mA
55mA
FX2N-8AD
-
8
-
50mA
80mA
Analog to digital converter
DIMENSIONS mm (inches)
W
H
D
MASS kg (lbs)
43 87 0.2(0.44) (1.7) (3.4) 20 89 0.13 (0.8) 90 (3.5) (0.29) 55 (3.5) 87 0.3(0.66) (2.1) (3.4) 75 75 (2.9) (2.9) 0.4(0.88)
1-6
Page 19
FX2NC Series Programmable Controllers
Introduction 1.
Table 1.4 :Special function blocks MODEL
DESCRIPTION
NUMBER OF I/O I
O
POWER SUPPLY Internal External 5V DC 24V DC
W 43 (1.7) 55 (2.1) 43 (1.7) 24 (0.9)
-
8
-
30mA
90mA*1
FX2N-5A
-
8
-
70mA
90mA
FX2N-2DA
-
8
-
30mA
85mA*1
-
8
-
30mA
130mA
-
8 8 8 8 8
-
30mA 30mA 30mA 70mA 90mA
200mA 50mA 50mA 55mA -
-
8
-
90mA
-
-
8
-
55mA
40mA
-
8
-
120mA
70mA*2
-
8
-
-
5W
-
8
-
-
10W
FX0N-3A Analog / Digital converter
FX2NC-4DA FX2N-4DA FX2N-4AD-PT FX2N-4AD-TC FX2N-2LC FX2N-1HC FX2NC-1HC FX2N-1PG-E FX2N-10PG
Digital to analog converter
PT 100 probe interface Thermo-couple interface Temperature control High speed counter Pulse output, Position control
FX2N-10GM Positioning controller FX2N-20GM
DIMENSIONS mm (inches)
H
D
MASS kg (lbs) 0.2(0.44)
87 (3.4) 0.3(0.66) 0.2(0.44) 89 (3.5)
0.13 (0.29)
55 87 90 (2.1) (3.5) (3.4) 0.3(0.66)
20.2 (0.8)
89 (3.5)
0.13 (0.29)
43 (1.7)
0.2(0.44)
60 (2.4) 86 (3.4)
87 (3.4) 0.3(0.66) 0.4(0.88)
1-7
Page 20
FX2NC Series Programmable Controllers
Introduction 1.
Table 1.4 :Special function blocks MODEL
DESCRIPTION
NUMBER OF I/O I
O
POWER SUPPLY Internal External 5V DC 24V DC
DIMENSIONS mm (inches)
W
H
D
MASS kg (lbs)
FX2N-1RM-ESET
Programmable cam switch
-
8
-
-
5W
FX2N-232IF
RS-232C Interface block
-
8
-
40mA
80mA
FX2N-16CCL-M
CC-Link Interface block
*3
8
*3
-
150mA
FX2N-32CCL
CC-Link Interface block
-
8
-
130mA
50mA
FX2N-64CL-M
CC-Link/LT Interface block
*4
8
*4
190mA
25mA*4
200mA
90mA
55 111 97 0.5(1.1) (2.1) (4.4) (3.8) 55 0.3(0.66) (2.1) 85 0.4(0.88) (3.3) 0.2(0.44) 90 87 0.15 (3.5) (3.4) (0.01) 43 (1.7) 0.5(1.1)
20mA
60mA
0.2(0.44)
FX2N-16LNK-M FX0N-16NT
MELSEC-I/O LINK Remote I/O system master block Net-mini interface
*5 8
8
*1 : Internal 24V DC *2 : When the voltage of the external DC power supply is 24V DC and 5V DC, the current is 70 mA and 100 mA, respectively. *3 : Maximum number of I/O points per system Connection is allowed as far as the following condition is satisfied: (Actual number of I/O points of PLC) + (Number of points occupied by special extension blocks) + (Number of points occupied by FX2N-16CCL-M: 8) + (32 x Number of remote I/O modules) ≤ 256 *4 : For details, refer to the FX2N-64CL-M user's manual. *5 : The value depends on the switch setting.
1-8
Page 21
FX2NC Series Programmable Controllers
1.1
Introduction 1.
Unit accessories - MPU-Main unit : FX2NC-100MPCB main unit power supply cable and FX2NC-100BPCB input extetion block power supply cable. - FX2NC Input extention block : FX2NC-10BPCB1 input extention block power supply cable. - FX2NC output extention and FX0N, FX2N extention block : I / O label kit.
1.2
World Spec. Table 1.5 : World / Japanese Spec. Input Sink / Source
World spec models : SINK / SOURCE. Japanese models : ALWAYS SINK.
Outputs Transistor
World spec models : ALWAYS SOURCE. Japanese models : ALWAYS SINK.
1-9
Page 22
FX2NC Series Programmable Controllers
1.3
Introduction 1.
Model name
F X 2 N C - 1 6 M T-
-D / UL
A) B) C)
G) F) E) D)
Table 1.6 : Model table A)
PC type : FX2NC, FX2N, FX0N
B)
Total number of I / O channels
E)
Omit AC, Japanese spec.
M MPU - main unit
D
24V DC Japanese spec.
E
DS
24V DC World spec.
Powered extension unit
EX Extension block, input
F)
EY Extension block, output Output type D)
Terminal style I/O. ,Only FX2NC. Features
Unit type C)
T
R
Relay
S
Triac (SSR)
T
Transistor
DSS 24V DC World spec., DC source transistor ES
AC Power Supply World spec.,DC sink transistor
ESS
AC Power Supply World spec., DC source transistor
UA1 AC Power Supply, AC inputs G)
UL
CE,UL registered product
1-10