Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 5 of 18

FX2NC (D/UL) Series Programmable Controllers Hardware Manual: 1. Introduction, pages 23 to 32

Pages 23 to 32 of 140, from FX2NC (D/UL) Series Programmable Controllers Hardware Manual

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi FX2NC-32MT

Page 23

FX2NC Series Programmable Controllers

1.4

Introduction 1.

Serial numbers <Product during December, 2009 or earlier>

9

Z

0

0

0

<Product from January, 2010>

1

Control number Month (Example: Dec.): 1 to 9 = January to September, X = October, Y = November, Z = December Year (Example: 2009): Last digit of year

1

0

1

0

0

0

1

Control number Month (Example: Jan.): 1 to 9 = January to September, X = October, Y = November, Z = December Year (Example: 2010): Last two digit of year

1-11

Page 24

FX2NC Series Programmable Controllers

1.5

Introduction 1.

Configuration Figure 1.4 :Schematic system FX0N-232ADP FX0N-485ADP FX2NC-232ADP FX2NC-485ADP

F

FX2NC-EEPROM-16 FX2NC-RTC FX2NC-EEPROM-4C FX2NC-EEPROM16C FX2NC-ROM-CE1 G

FX2NC-16EX-D/UL FX2NC-16EYT-D/UL FX2NC-32EX-D/UL FX2NC-32EYT-D/UL

FX2NC-16MT-D/UL 1 FX2NC-32MT-D/UL 5 FX2NC-64MT-D/UL FX2NC-96MT-D/UL

FX2NC-4AD FX2NC-4DA FX2NC-1HC

2

3

4

B

6

A

FX2NC-CNV-IF RS 422/RS 232 CONVERTER FX-232AW FX-232AWC FX-232AWC-H RS422/USB CONVERTER FX-USB-AW MELSEC MEDOC FX-PCS/AT-EE GX IEC Developer FX-PCS/WIN-E GX Developer FX-30P FX-20P-E-SET0 FX-10P-E

C

FX-16E-TB FX-32E-TB FX-16EYR-TB FX-16EYT-TB FX-16EX-A1-TB

J

L

FX-10DU-E FX-20DU-E FX-25DU-E FX-30DU-E

K

FX-20P-E I

FX-40DU-ES FX-40DU-TK-ES FX-50DU-TK(S)-E F930GOT F940GOT H

FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL FX0N-8EX-ES/UL FX0N-8EX-UA1/UL FX0N-8ER-ES/UL FX0N-8EYR-ES/UL FX0N-8EYT-ESS/UL FX2N-8EX-ES/UL FX2N-8EX-UA1/UL FX2N-8ER-ES/UL FX2N-8EYR-ES/UL FX2N-8EYT-ESS/UL FX0N-16EX-ES/UL FX0N-16EYR-ES/UL FX0N-16EYT-ESS/UL D FX0N-3A FX2N-5A FX2N-2AD FX2N-2DA FX2N-4AD FX2N-4DA FX2N-8AD FX2N-2LC FX2N-4AD-PT FX2N-4AD-TC FX2N-1HC FX2N-10PG FX2N-1PG-E FX2N-10GM FX2N-20GM FX2N-1RM-E-SET FX2N-232IF FX2N-32CCL FX2N-16CCL-M FX2N-64CL-M FX2N-16LNK-M FX0N-16NT E 1-12

Page 25

FX2NC Series Programmable Controllers

Introduction 1.

Table 1.7 : Configuration notes A

MPU-Main unit (Main Processing Unit)

c

Left hand side port

B

Extension block, Special function block d

Memory port

C

Connector conversion adapter e

Programming port

D

Extension block f

I/O port

E

Special function block g

MPU bus port

F

Function adapters h

Unit bus port

G

Memory board (Real time clock)

H

Data access units, GOT

I

Dedicated programming

J

Computer interface

K

Computer software

L

Terminal block

Note When connecting peripheral equipment (programming tool or GOT [direct connection to CPU]) via the FX2NC-232ADP or the FX0N-232ADP, FX2NC main unit should be the following setting condition. - Set the special data register for the communication format setting of the channel connecting the peripheral equipment (D8120) to K0. - Set the communication parameter to "Not set".

1-13

Page 26

FX2NC Series Programmable Controllers

1.5.1

Introduction 1.

Summary Connection of FX2NC series extension blocks only The FX2NC series input extension blocks and FX2NC series output extension blocks can be directly connected to the FX2NC series main unit. These input/output extension blocks can be connected in the desired order. After connection, octal numbers will be assigned to the input/ output points of the extension blocks. These octal numbers are regarded as the input/output numbers. The smallest number will be assigned to the input/output point next to the main unit, and then sequentially increased for the subsequent input/output points. Before connection, calculate the number of connectable input/output points by referring to Sec. 1.5.3, or quickly obtain this number using the table shown in Sec. 1.5.5. X020

X060

X100

-

-

-

-

X000-X017

X040

X037

X057

X077

X117

FX2NC-32MT-D/UL X: 16 points Y: 16 points Y000-Y017

16EX 16EX 16EYT 16EX 16EYT 16EYT 16EX 16EYT 16 points 16 points 16 points 16 points 16 points 16 points 16 points 16 points

Y020

Y040

Y060

Y100

-

-

-

-

Y037

Y057

Y077

Y117

1-14

Page 27

FX2NC Series Programmable Controllers

Introduction 1.

Connection of FX0N and FX2N series extension blocks and function adapter To connect the FX2NC series main unit to the FX0N or FX2N series extension blocks, be sure to connect the FX2NC-CNV-IF connector conversion adapter first. Following the adapter, you can connect up to 4 blocks. In addition, one special adapter can be connected to the left side of the base unit. Before connection, calculate the number of connectable input/output points by referring to Sec. 1.5.3. FX0N-232ADP (Function adapter)

FX2NC-32MT -D/UL

FX2NC Series extension blocks

FX2NC-CNV-IF (Connector conversion adapter) FX2N-16EYR -ES/UL relay output block

FX2N-232IF RS-232C block

FX2N-1PG-E FX2N-4AD pulse output analog block block

4 blocks, maximum

1-15

Page 28

FX2NC Series Programmable Controllers

1.5.2

Introduction 1.

Current consumption and input/output points The following tables show the current consumption and input/output points of various types of FX2NC series main units, extension blocks, and special function blocks. While referring to Sec. 1.5.3, calculate the total current consumption and total input/output values using the following main unit values (values n through q), extension block values, and special function block values. Table 1.8 : Base units MODEL n CURRENT CAPACITY o INPUT p OUTPUT

5V DC

X

Y

FX2NC-16MT-D/UL

600mA

8

8

16

FX2NC-32MT-D/UL

560mA

16

16

32

FX2NC-64MT-D/UL

480mA

32

32

64

FX2NC-96MT-D/UL

400mA

48

48

96 q TOTAL

1-16

Page 29

FX2NC Series Programmable Controllers

Introduction 1.

.

Table 1.9 : Extension blocks CURRENT CONSUMPTION 5V DC

INPUT X

OUTPUT Y

TOTAL

FX2NC-16EX-D/UL

30mA

16

-

16

FX2NC-16EYT-D/UL

50mA

-

16

16

FX2NC-32EX-D/UL

60mA

32

-

32

FX2NC-32EYT-D/UL

100mA

-

32

32

FX0N-8ER-ES/UL FX2N-8ER-ES/UL

25mA

4(8)

4(8)

16*1

FX0N-8EX-ES/UL FX2N-8EX-ES/UL

25mA

8

-

8

FX0N-8EX-UA1/UL FX2N-8EX-UA1/UL

25mA

8

-

8

FX0N-8EYR-ES/UL FX2N-8EYR-ES/UL

30mA

-

8

8

FX0N-8EYT-ESS/UL FX2N-8EYT-ESS/UL

30mA

-

8

8

FX0N-16EX-ES/UL

40mA

16

-

16

FX0N-16EYT-ESS/UL

40mA

-

16

16

FX0N-16EYR-ES/UL

40mA

-

16

16

FX2N-16EX-ES/UL

45mA

16

-

16

FX2N-16EYR-ES/UL

40mA

-

16

16

FX2N-16EYT-ESS/UL

180mA

-

16

16

MODEL

*1:8 points are used for actual input/output, however, this block should occupy 16 input/output points. 1-17

Page 30

FX2NC Series Programmable Controllers

Table 1.10: Special function block

Introduction 1.

Function adapters

CURRENT CONSUMPTION 5V DC

INPUT X

TOTAL

X/Y

OUTPUT Y

FX0N-3A

30mA

-

8

-

8

FX0N-16NT

20mA

8

-

8

16

FX2N-2AD

20mA

-

8

-

8

FX2N-4AD

30mA

-

8

-

8

FX2NC-4AD

50mA

-

8

-

8

FX2N-8AD

50mA

-

8

-

8

FX2N-4AD-PT

30mA

-

8

-

8

FX2N-4AD-TC

30mA

-

8

-

8

FX2N-5A

70mA

-

8

-

8

FX2N-2DA

30mA

-

8

-

8

FX2N-4DA

30mA

-

8

-

8

FX2NC-4DA

30mA

-

8

-

8

FX2N-8AD

50mA

-

8

-

8

FX2N-2LC

70mA

-

8

-

8

FX2N-1HC

90mA

-

8

-

8

FX2NC-1HC

90mA

-

8

-

8

FX2N-1PG-E

55mA

-

8

-

8

FX2N-10PG

120mA

-

8

-

8

FX2N-232IF

40mA

-

8

-

8

MODEL

1-18

Page 31

FX2NC Series Programmable Controllers

Introduction 1.

CURRENT CONSUMPTION 5V DC

INPUT X

TOTAL

X/Y

OUTPUT Y

FX2N-16CCL-M

-

*1

8

*1

8

FX2N-32CCL

130mA

-

8

-

8

FX2N-64CL-M

190mA

*2

8

*2

*2

FX2N-16LNK-M

200mA

*3

*3

*3

*3

FX2N-10GM

-

-

8

-

8

FX2N-20GM

-

-

8

-

8

FX2N-1RM-E-SET *4

-

-

8

-

8

FX0N-232ADP

200mA

-

-

-

-

FX2NC-232ADP

100mA

-

-

-

-

FX0N-485ADP

30mA

-

-

-

-

FX2NC-485ADP

150mA

-

-

-

-

FX-2PIF

290mA

-

-

-

-

MODEL

*1:Maximum number of I/O points per system Connection is allowed as far as the following condition is satisfied: (Actual number of I/O points of PLC) + (Number of points occupied by special extension blocks) + (Number of points occupied by FX2N-16CCL-M: 8) + (32 x Number of remote I/O modules) ≤ 256 *2:For details, refer to the FX2N-64CL-M user’s manual. *3:Value depends on the switch setting (16, 32, 48, 64, 96 or 128 points). *4:Maximum of 1 unit can be connected. 1-19

Page 32

FX2NC Series Programmable Controllers

1.5.3

Introduction 1.

Rules 1) Add the input/output points of the extension blocks and special functions blocks to the input/ output points of the main unit. The total number of input points should be 184 points or less, and the total number of output points should be also 184 points or less. The total number of input and output points should be no more than 256 points. 2) The FX2NC series main unit supplies the control power (5V DC) to the extension blocks and special function blocks. For this reason, the total current consumption of all the blocks connected to the main unit should not exceed the current capacity of the main unit. 3) Next to the FX2NC-CNV-IF, up to 4 blocks can be connected. To connect a special function unit, such as the FX2N-10GM or FX2N-1RM-E-SET, refer to the instruction manual of the corresponding special function block. Calculation form for system configuration Enter current consumption values and input/output points of the extension blocks and special function blocks while referring to Sec. 1.5.2, and then calculate the total current value r and total input and output points s through v. From the obtained values, judge whether the blocks can be connected.

1-20