Page 91
FX2NC Series Programmable Controllers
6.
Outputs
6.1
Transistor output specification
Outputs 6.
Table 6.1 : Switched voltage (resistive load)
5-30V DC
Rated current / N points (resistive load)
FX2NC Main unit, Extension block: 0.1A/1point, 0.8A/8point, 0.3A/1point (Y000-Y003) FX0N, FX2N Extension block: 0.5A/1point, 0.8A/4point, 1.6A/8point
Max. Inductive load
FX2NC Main unit, Extension block: 2.4W/24V DC, 7.2W/24V DC (Y000-Y003) FX0N, FX2N Extension block: 12W/24V DC OFF Æ ON
<0.2ms (100mA/24V DC), <15µs (100mA/5V DC) (Y000,Y001)
ON Æ OFF
<0.2ms (100mA/24V DC), <30µs (100mA/5V DC) (Y000,Y001)
Response time (approx.)
Open circuit current leakage
0.1mA/30V DC
Circuit isolation
Photocoupler
Operation indication
LED is lit when photocoupler is driven
6-1
Page 92
FX2NC Series Programmable Controllers
6.1.1
Outputs 6.
Response times OFF times increase as the load current decreases. For improved response times use a 'dummy' resistor, see Figure 6.1. If a response time of 0.5 ms or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal line has a current greater than 60mA/24V DC. Figure 6.1 :Dummy load FX2NC Main unit FX2NC Extention block
FX0N, FX2N Extention block
Y
Y
Load COM1
Sink
Load Dummy load 5 to 30V DC
+V
Source
Dummy load 5 to 30V DC
6-2
Page 93
FX2NC Series Programmable Controllers
6.1.2
Outputs 6.
Output circuit configuration Interlock For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for interlocking the PLC’s internal programs as shown to the right.
External Writing of Sink Output Type Interlock Limit of normal rotation Limit of reverse rotation
PLC output element
External Writing of Source Output Type Interlock Limit of normal rotation Limit of reverse rotation
PLC output element
6-3
Page 94
FX2NC Series Programmable Controllers
6.1.3
Outputs 6.
Transistor output example
Common points (See sec, 2.1, 2.2, 2.3) • FX2NC-16MT-D/UL : 8 points (COM1 See sec, 3.12) • FX2NC-32/64/96MT-D/UL, FX2NC-16/32EYT-D/UL : 16 points (COM1 to COM3 See sec, 3.12) • FX2N-16EYT-ESS/UL : 8 points (+V0, +V1) • FX2N-8EYT-ESS/UL : 4 points (+V0, +V1) • FX0N Extension blocks : 4 points (+V0 to +V3) Typical wiring to the 4-point common type. Figure 6.2:FX0N, FX2N Extension (Source)
Figure 6.3:Ref. Japanese Spec. (Sink)
➍ +V0 Y0
Y1
Y2
Y3 +V1 Y
➍
Y
COM1
Y0
Y1
➌ ➋
MC2 MC1 M C 1
Y2
Y3
COM2
Y
Y
➌ ➋
➋
M C 2
MC2 MC1 M C 1
➊
➋
M C 2
➊
Table 6.2 : Item check n
DC power supply p
External, mechanical inter-lock o
Fuse q
Internal noise suppressor 6-4
Page 95
FX2NC Series Programmable Controllers
Outputs 6.
Typical wiring to the 8 and 16-point common type. Table 6.3:Item check
Figure 6.4 :FX2NC (D/UL) (Sink) ... COM1 COM1
Y0
Y1
➍
Y2
Y3
Y4
Y5
Y6
➊
DC power supply
➋
Fuse
➌
External, mechanical inter-lock
➌ ➋
MC2 MC1 M C 1
➍
M C 2
➊ Figure 6.5 :FX0N, FX2N Extension (Source) ... +V0 Y0
Y1
Y2
Y3
Y4
Y5
Y6
The output connectors of the main unit and the connector-type 16-point output extension blocks are the 16point common type (8-point common type for the FX2NC-16MT). These output connectors have two COM1 to COM3 pins that are connected to each other inside the programmable controller. To connect the line to an external unit, shortcircuit these two pins at the external circuit so that the load of each pin can be reduced.
➌ ➋
MC2 MC1 M C 1
M C 2
➊ 6-5
Page 96
FX2NC Series Programmable Controllers
6.2
Outputs 6.
Relay output specification Table 6.4 : Switched voltages (resistive load)
≤ 250V AC, ≤ 30V DC
Rated current / N points (resistive load)
FX2N ,FX0N:Extension blocks 2A/1point, 8A/COM
Max. Inductive load
80VA See table 6.5
Minimum load
When supply voltage < 24V DC allow at least 5mA flow
Response time (approx.)
OFF Æ ON
10ms
ON Æ OFF
10ms
Circuit isolation by relay
Operation indication
LED is lit when coil is energized
6-6
Page 97
FX2NC Series Programmable Controllers
6.2.1
Outputs 6.
Product life of relay contacts The product life of relay contacts considerably varies depending on the load type used. Take care that loads generating reverse electromotive force or rush current may cause poor contact or deposition of contacts which may lead to considerable reduction of the contact product life. 1) Inductive load Inductive loads generate large reverse electromotive force between contacts at shutdown which may cause arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller, the arc energy gets larger. The test results in table 6.5 were gathered from a 1 sec ON/OFF test cycle. Please note that the over current induced by in-rush greatly reduces the relay contacts life. The rated life for an inductive AC load such as a contactor or solenoid valve is 500,000 operations at 20VA.
6-7
Page 98
FX2NC Series Programmable Controllers
Outputs 6.
Table 6.5 : Load capacity Life of contact (cycles)
20VA
35VA
80VA
0.2A/100V AC 0.1A/200V AC
0.35A/100V AC 0.17A/200V AC
0.8A/100V AC 0.4A/200V AC
3,000,000
1,000,000
200,000
The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down. * For countermeasures while using inductive loads, refer to "Output circuit configuration" below in this section. Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load. 2) Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load. 3) Capacitive load Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load. Capacitive loads such as capacitors may be present in electronic circuit loads including inverters. * For the maximum specified resistance load, refer to Section 6.1. 6-8
Page 99
FX2NC Series Programmable Controllers
6.2.2
Outputs 6.
Output circuit configuration An internal protection circuit for the relays is not provided in the relay output circuit for this product. It is recommended to use inductive loads with built-in protection circuits. When using loads without built-in protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product life. 1) DC load Connect a diode in parallel with the load. The diode (for commutation) must comply with the following specifications. Item
Guide
Reverse voltage
5 to 10 times the load voltage
Forward current
Load current or more
2) AC load Connect the surge absorber shown to the right (combined CR components such as a surge killer and spark killer, etc.) parallel to the load. Select the rated voltage of the surge absorber suitable to the output used. Refer to the table below for other specifications. Item
Guide
Electrostatic capacitance
Approx. 0.1 µF
Resistance value
Approx. 100 to 200 Ω
Inductive load PLC output contact
Diode (for commutation)
Inductive load PLC output contact
Surge absorber
6-9
Page 100
FX2NC Series Programmable Controllers
3) Interlock For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an external interlock should be provided for inter locking t he P LC's inter nal programs as shown to the right.
Outputs 6.
Inter- Limit of normal lock rotation PLC output contact Limit of reverse rotation
PLC output contact
4) In-phase PLC output contacts (*) should be used in an "inphase" manner.
Bad
* *
Good
* *
6-10