FX2NC (D/UL) Series Programmable Controllers Hardware Manual: 5. Inputs
Pages 79 to 90 of 140, from FX2NC (D/UL) Series Programmable Controllers Hardware Manual
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi FX2NC-32MT
Page 79
FX2NC Series Programmable Controllers
Inputs 5.
5.
Inputs
5.1
24V DC input specifications Table 5.1 :FX2NC input specifications FX2NC main unit, extension block X0 Æ X7 Input voltage
X10 Æ ∞ 24V DC +20%, -15%
Input current Input switching current
FX0N, FX2N Extension block
OFF Æ ON ON Æ OFF
Response time Variable response time Circuit isolation Operation indication
24V DC, 7mA
24V DC, 5mA
24V DC, 5mA
>4.5mA
>3.5mA
>3.5mA <1.5mA 10ms
X000-X017 0-60ms (FX2NC-16M : X000-X007)
---
Photocoupler LED is lit
5-1
Page 80
FX2NC Series Programmable Controllers
5.1.1
Inputs 5.
Typical wiring Figure 5.1 : sink ➊
➋
➏
NPN
➌
COM
X0
COM
➐
➍
X1
X2 ‚‚‚‚‚‚‚
➌
➎
X3
COM
COM
X0
➑
➎
X1
S/S
➒
X0
X1
X2
➓ ‚‚‚‚‚‚‚
5-2
X3
Page 81
FX2NC Series Programmable Controllers
Inputs 5.
Table 5.2 : Item check External power supply 24V DC +20% -15% n o
NPN proximity sensor p
Switch q
Push button r
Contact s
Rotary switch t
MPU main processing unit (main unit)
u
FX2NC Input extension block v
FX2NC-CNV-IF Connector conversion adapter w
FX0N, FX2N Extension block
5-3
Page 82
FX2NC Series Programmable Controllers
5.1.2
Inputs 5.
Input circuit connection Figure 5.2 : FX2NC Main unit and FX2NC Extension block
24V DC +20% -15%
Main unit (Sink)
Extention block (Sink)
3.3 kΩ*
3.3 kΩ*
X
X
COM
COM
COM
COM
*: X10→X
4.3 kΩ
24V DC +20% -15% Next input block *: X10→X
4.3 kΩ
5-4
Page 83
FX2NC Series Programmable Controllers
Inputs 5.
Figure 5.3 : FX2N and FX0N Extension block
Sink
Source
4.3 kΩ
4.3 kΩ
X
24V DC +20% -15%
S/S
X
24V DC +20% -15%
S/S
5-5
Page 84
FX2NC Series Programmable Controllers
5.1.3
Inputs 5.
Diodes and inputs connected in series; Vdrop across the diode Max. 4V No more than 2 LEDs should be connected in series. Figure 5.4 : Series diodes FX2NC Main unit FX2NC Extention block X
COM COM
Ex. Sink
FX0N, FX2N Extention block X
S/S
5-6
Page 85
FX2NC Series Programmable Controllers
5.1.4
Inputs 5.
Resistors and inputs connected in parallel; Parallel resistance Rp: FX2NC = 15kΩ. If resistance Rp is less than the stated value, then add Rb. See equation 1 for Rb calculation. Alternatively; Current leakage: FX2NC = 1.5mA. If the current leakage is greater than the stated value, then add Rb. See equation 2 for Rb calculation. Figure 5.5 : Parallel LED
Eqn 1 : Rb ≤
4Rp 15 - Rp
Eqn 2 : Rb ≤
6 Ι - 1.5
FX2NC Main unit FX2NC Extention block
+24V Rb
X LED Rp COM
5-7
Page 86
FX2NC Series Programmable Controllers
5.2
Inputs 5.
AC110V input Extension block Table 5.3 : FX0N-8EX-UA1/UL, FX2N-8EX-UA1/UL input specification Input voltage
85-132V AC 50/60Hz
Input impedance
21kΩ/50HZ 18kΩ/60Hz
Input current
4.7mA 100V AC/50Hz 6.2mA 110V AC/60Hz
OFF Æ ON/ON Æ OFF; input switching current 80V 3.8mA/30V 1.7mA
5.2.1
Response time
25ms
Circuit isolation / Operation indication
Photocoupler/LED is lit
Input circuit connection Figure 5.6 : FX0N-8EX-UA1/UL, FX2N-8EX-UA1/UL 85-132 V AC 50/60 Hz COM1
X0 X1 X2
5-8
Page 87
FX2NC Series Programmable Controllers
5.2.2
Inputs 5.
Programming caution When using 110V AC units, high speed counter and interrupt routines are not suitable for use due to the long 'ON/OFF' times. The following instructions are also not suitable. FNC 51 REFF
FNC 70 TKY
FNC 52 MTR
FNC71 HKY
FNC 56 SPD
FNC 72 DSW
FNC 68 ROTC
FNC 75 ARWS
✘
5-9
Page 88
FX2NC Series Programmable Controllers Inputs 5.
MEMO ae MITSUBISHI 5-10