FX2NC (D/UL) Series Programmable Controllers Hardware Manual: 4. Power supply

Pages 71 to 78 of 140, from FX2NC (D/UL) Series Programmable Controllers Hardware Manual

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi FX2NC-32MT

Page 71

FX2NC Series Programmable Controllers

4.

Power supply 4.

Power supply Table 4.1 : Power requirements FX2NCFX2NCFX2NCFX2NC16MT-D/UL 32MT-D/UL 64MT-D/UL 96MT-D/UL 24V DC +20%, -15% Ripple Voltage (p-p) 5% or less

Power supply Max. allowable momentary power 5ms (5ms > PC = RUN, 5ms < PC = STOP) failure period Fuse (size) rating 250V 3.15A (3A) 5φ×20mm (0.2×0.79 inches) In-rush current 30A or less 0.5ms/24V DC Power consumption *1 6W 8W 11W 14W

*1 Includes the input current (7 or 5 mA per point). Table 4.2 :Power consumption of FX2NC extension blocks When connecting extension blocks, add the values shown below to the power consumption value of the main unit. Type Input extension Output extension Special extension

Model

Power consumption

FX2NC-16EX-D/UL

2.2W *2

FX2NC-32EX-D/UL

4.2W *2 0.35W 0.7W

FX2NC-16EYT-D/UL FX2NC-32EYT-D/UL See sec. Table 1.4

*2 Includes the input current (5 mA per point).

4-1

Page 72

FX2NC Series Programmable Controllers

Power supply 4.

- To supply the power to the main unit, use the power cable FX2NC-100MPCB. - To supply the power to an input extension block, use the power cable FX2NC-100BPCB. To supply the power to the second input block or later, perform crossover wiring using the power cable FX2NC-10BPCB1. Figure 4.1 : Connection of power supply cables Main unit Input Output Input

Main unit

Input block

1

+

2

-

3 Ground

Red+ BlackGreen Ground

Terminal layout of power supply connector

1 2 1 2

Red+ BlackProtective cover

Upper

Lower

The lower power connector is provided for crossover wiring to a later input block. It is covered with a protective cover at the time of shipment from the factory.

4-2

Page 73

FX2NC Series Programmable Controllers

Power supply 4.

Three types of power cables shown below are offered. A and B are offered with the main unit, and C is offered with an input extension block. Table 4.3 : Type

Application

Model name

Length

FX2NC-100MPCB

1m(3.3ft)

Product in same package

A

Power cable for main unit

B

Input power cable for input extension FX2NC-100BPCB block

1m(3.3ft)

C

Input power cable for input extension FX2NC-10BPCB1 block (for crossover wiring)

0.1m(0.3ft) Input extension block

Main unit

The crossover cable C can be wired across up to four 16-point output blocks. To supply the power to an input block beyond four output blocks, use the cable B . For the 24V DC power source of the FX or FX2N series programmable controllers, the correction value should be written in data register D8008; a special data register that sets the power failure detection period. However, for the FX2NC series programmable controllers, it is not necessary to write the correction value. The data stored in the D8008 register will be automatically corrected by the system program. Do not modify the D8008 data.

4-3

Page 74

FX2NC Series Programmable Controllers

Power supply 4.

Figure 4.2 : EX.wiring EX.FX2NC-16M

Power supply 24V DC +20% -15% u n Ripple voltage (p-p) 5% or less

*1

DC/DC n 5V DC 24V DC v t o

*1

EX.FX2NC-16EX

MC o Circuit protector or Fuse p Emergency stop q Power supply switch r Power ON pilot indicator s Power supply for loads t Grounding resistor 100Ω or less (class D)

MC w EX.FX2NC-16EX q p u Fuse

PL v Main unit r w Input extension blocks 11

MC w EX.FX2NC-16EYT

11 s

Output extension block

MC *1 It is recommended to use the same power source to power the main unit, input extension blocks and special function blocks. If two sources s are required, follow the below guidelines: - Supply power to the input extension blocks and special function blocks before or at the same time the main unit is powered. - The power supplies may be cut the same time after ensuring system safety.

4-4

Page 75

FX2NC Series Programmable Controllers

4.1

Power supply 4.

Power supply cautions As shown in the following figure, supply 24V DC to the main unit, special function blocks, and data access unit from the same power source. Figure 4.3 : Use of same power source C om m unication cable M ain U nit

E xtension blocks

D ata access unit

F X 2N C -C N V -IF

24V D C +20% -15%

5% ripple (p-p) or less

4-5

Page 76

FX2NC Series Programmable Controllers

Power supply 4.

If the power has to be supplied from two power sources due to low capacity of the DC power supply unit, etc., be sure to connect the minus lines of the two power supply units. Figure 4.4: Connection of minus lines C om m unication cable M ain U nit

E xtension blocks

D ata access unit

F X 2N C -C N V -IF

24V D C +20% -15%

4.2

5% ripple (p-p) or less

Earthing / Grounding Use a cable at least 0.2mm2 (AWG24) to ground equipment. Ground resistance must be less than 100Ω (class D). Note that the ground cable must not be connected to the same ground as the power circuits. Grounding is recommended but if a proper ground cannot be provided the PC will still operate correctly without being grounded.

4-6

Page 77

FX2NC Series Programmable Controllers

1

INTRODUCTION

2

TERMINAL LAYOUTS

3

INSTALLATION NOTES

4

POWER SUPPLY

5

INPUTS

6

OUTPUTS

7

DIAGNOSTICS

8

DISCONTINUED MODEL

9

APPENDIX

Inputs 5.

Page 78 read from a scan by OCR; it may hold reading errors

FX2NC Series Programmable Controllers Inputs 5.

ae MITSUBISHI