For the Mitsubishi FX2NC-32MT
Page 65
FX2NC Series Programmable Controllers
3.11
Installation notes 3.
Wiring techniques The wiring of FX2NC products has been designed to be safe and easy. If during the installation of these products or associated products concern is felt, please contact a professional electrician who is trained to the local and national standards applicable to the installation site.
Wiring cautions • Do not run input signals in the same multicore cable as output signals or allow them to share the same wire. • Do not lay I/O signal cables next to power to power cables or allow them to share the same trunking duct. Low voltage cables should be reliably separated or insulated with regard to high voltage cabling. • Where I/O signal lines are used over an extended distance consideration for voltage drop and noise interference should be made.
3-17
Page 66
FX2NC Series Programmable Controllers
3.12
Installation notes 3.
Termination of connector style I/O The I/O connector should be the 20-pin type and should conform to MIL C 83503 of Military Standard. This type of connector is also used for FX2C series programmable controllers. The output connectors of the main unit and the connector-type 16-point output extension blocks are the 16-point common type (8-point common type for the FX2NC-16MT). These output connectors have two COM1 to COM3 pins that are connected to each other inside the programmable controller. To connect the line to an external unit, shortcircuit these two pins at the external circuit so that the load of each pin can be reduced.
3-18
Page 67
FX2NC Series Programmable Controllers
3.13
Installation notes 3.
Termination of screw terminals Cables terminating at a screw terminal of an FX2N and FX0N product should be fitted with insulated crimp terminals, see example shown. Terminals screws should be tightened to between 0.5 to 0.8 N‚m. Screw terminals must be secured to prevent a loose connection from causing a malfunction. Failure to do so may cause equipment failures or malfunctions. Figure 3.14: • When one wire is connected to one terminal.
6.2mm (0.24") or less
φ 3.2 (0.13")
6.2mm (0.24") or less
Terminal Crimp screw terminal
φ 3.2 (0.13")
Terminal
• When two wires are connected to one terminal. 6.2mm (0.24") or less
φ 3.2 (0.13") 6.3mm (0.25") or more
6.2mm (0.24") or less
Terminal Crimp screw terminal
φ 3.2 (0.13") 6.3mm (0.25") or more
Terminal
Caution Make sure to turn OFF the power before starting any wiring work.
3-19
Page 68
FX2NC Series Programmable Controllers
3.14
Installation notes 3.
Termination of connector style I/O cables Standard, pre-terminated cables are available from Mitsubishi in 1.5, 3 and 5 meter (4.9, 9.8 and 16.4 ft) lengths. However, users are encouraged to make their own cables to the lengths they require. The following table identifies connectors and cable requirements; Figure 3.15: F X 2N C n p o q (
Table 3.5 : MODEL
LENGTH
FX-16E-500CAB-S 5m (16.4) FX-16E-150CAB
1.5m (4.9)
FX-16E-300CAB
3m (9.8)
FX-16E-500CAB
5m (16.4)
n o p
20 Pin No connector Single wire connector 20 Pin 20 Pin connector connector
Flat cables
20 Pin 20 Pin connector connector
Round cables
FX-16E-150CAB-R 1.5m (4.9) FX-16E-300CAB-R 3m (9.8)
): ft q Input switch or Loads TERMINAL BLOCK xFX-16E-TB xFX-32E-TB xFX-16EX-A1-TB xFX-16EYR-TB xFX-16EYT-TB
FX-16E-500CAB-R 5m (16.4)
3-20
Page 69
FX2NC Series Programmable Controllers
1
INTRODUCTION
2
TERMINAL LAYOUTS
3
INSTALLATION NOTES
4
POWER SUPPLY
5
INPUTS
6
OUTPUTS
7
DIAGNOSTICS
8
DISCONTINUED MODEL
9
APPENDIX
Power supply 4.
Page 70
FX2NC Series Programmable Controllers Power supply 4.
ae MITSUBISHI