FX2NC (D/UL) Series Programmable Controllers Hardware Manual: 6. Outputs, pages 101 to 110

Pages 101 to 110 of 140, from FX2NC (D/UL) Series Programmable Controllers Hardware Manual

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi FX2NC-32MT

Page 101

FX2NC Series Programmable Controllers

6.2.3

Outputs 6.

Relay output example Table 6.6 : Item check AC power supply n

Figure 6.6:Typical wiring to the 4-point common type

COM1

➋

➊

Y0

Y1

Y2

Y3

MC2 MC1

➍

M C 1

M C 2

COM2

➐ ➏

➋ ➑

Y4

Y5

Y6

➒ ➌ ➎

➓ o

Fuse p

Solenoid valve q

Incandescent lamp r s

Neon lamp t

Noise suppressor 0.1µF capacitor + 100-200Ω resistor u v

DC power supply w

Surge absorbing diode

Contactor

LED

Common points (See sec, 2.1, 2.2, 2.3) • FX2N-16EYR-ES/UL : 8points (COM1, COM2) • FX2N-8EYR-ES/UL, FX2N-8ER-ES/UL : 4points (COM1, COM2) • FX0N Extension blocks : 4points (COM1 to COM4)

6-11

Page 102

FX2NC Series Programmable Controllers

Outputs 6.

Table 6.7 :Item check

Figure 6.7 :Typical wiring to the 8-point common type

COM1

Y0

Y1

Y2

M C 1

M C 2

Y3

Y4

Y5

Y6

➊

AC power supply

➋

Fuse

➌

Incandescent lamp

Y7

➋ ➊

➌

6-12

Page 103

FX2NC Series Programmable Controllers

6.3

Outputs 6.

Triac (SSR) output specifications Table 6.8 : Switched voltages (resistive load)

85-242V AC

Rated current / N points (resistive load)

0.3A/1point, 0.8A/COM

Max. Inductive load

15VA/100V AC, 36VA/240V AC

Minimum load

0.4VA/100V AC, 2.3VA/240V AC

Open circuit current leakage

1mA/100V AC, 2.4mA/240V AC

Response time (approx.)

OFF→ON

<1ms

ON→OFF

<10ms

Circuit isolation by photocoupler

Operation indication

LED is lit when photocoupler is driven

6-13

Page 104

FX2NC Series Programmable Controllers

6.3.1

Outputs 6.

In-rush currents These currents should be kept as low possible. The root mean square ( rms) <0.2A. Reference Eqn 1 for ( rms) -In-rush current (A) -In-rush time (sec) -Switch current (A) -Switch time (sec) -Operation time (sec) Figure 6.9 :Current graph

Eqn 1 2 rms

=

×

+ +

2

×

+

Ex. 0.2A=

42 × 0.02 + 0.42 ×0.7 0.02+0.7+10

6-14

Page 105

FX2NC Series Programmable Controllers

6.3.2

Outputs 6.

Output circuit configuration 1) Very low current load The triac output circuit inside the PLC has a C-R absorber for turning OFF. When connecting a very low current load of "0.4 VA / 100V AC or less, or 1.6 VA / 200V AC or less", please connect a surge absorber parallel to the load. Select the rated voltage of the surge absorber suitable to the load used. Refer to the table below for other specifications. Item

Guide

Electrostatic capacitance

Approx.0.1 µF

Resistance value

Approx.100 to 200 Ω

Very low current load PLC output

2) Interlock For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously, an exter nal interlock should be provided for interlocking the PLC's internal programs as shown to the right.

Surge absorber

Inter- Limit of normal lock rotation

PLC output element

Normal rotation

Reverse Limit of reverse rotation rotation

6-15

Page 106

FX2NC Series Programmable Controllers

Outputs 6.

3) In-phase PLC output contacts (*) should be used in an "inphase" manner.

*

Bad

*

*

Good

*

6-16

Page 107

FX2NC Series Programmable Controllers

6.3.3

Outputs 6.

Triac output example Figure 6.10:Typical wiring Table 6.9: Item check n AC power supply COM1

➋

➊ 6.4

Y0

Y1

Y2

MC2 MC1

➍

M C 1

Y3

COM2

Y4

Y5

➋

M C 2

➌ o

Fuse p

Solenoid valve q

Incandescent lamp r

Noise suppressor 0.1µF capacitor+100-200Ω resistor r

Applying safe loads Ensure all loads are applied to the same side of each PC output, see previous figures. Loads which should NEVER simultaneously operate (e.g. direction control of a motor), because of a safety critical situation, should not rely on the PC's sequencing alone. Mechanical interlocks MUST be fitted to all safety critical circuits. (See preceding figure.)

6-17

Page 108 read from a scan by OCR; it may hold reading errors

FX2NC Series Programmable Controllers Outputs 6.

MEMO ae MITSUBISHI 6-18

Page 109

FX2NC Series Programmable Controllers

1

INTRODUCTION

2

TERMINAL LAYOUTS

3

INSTALLATION NOTES

4

POWER SUPPLY

5

INPUTS

6

OUTPUTS

7

DIAGNOSTICS

8

DISCONTINUED MODEL

9

APPENDIX

Diagnostics 7.

Page 110 read from a scan by OCR; it may hold reading errors

FX2NC Series Programmable Controllers Diagnostics 7.