Page 111

FX2NC Series Programmable Controllers

7.

Diagnostics

7.1

Preliminary checks POWER RUN BATT ERROR

Check power supply, ground and I/O cables are wired correctly.

POWER RUN BATT ERROR

Turn the power supply on. Check the power LED is lit. Down load a small test program into the PC using a handheld programmer or MEDOC. Verify the program to ensure it has been written to the PC correctly. Using the programming device forcibly turn ON/OFF each output. Check the output LEDs for operation.

POWER RUN BATT ERROR

Put the PC into RUN. Check the RUN LED is lit. Check the previously down loaded program works correctly. Once all check are complete take the PC out of run and turn OFF the power supply.

Diagnostics 7.

During this testing stage take extrem care not to touch any live or hazardous parts.

7-1

Page 112

FX2NC Series Programmable Controllers

7.2

Diagnostics 7.

Basic diagnostics The following diagnostic functions will help identify, common faults.

7.2.1

BATT LED ON

POWER RUN BATT ERROR

7.2.2

Fault BATT LED ON

Remedy Monitor M8006 with a programming tool.

M8006:ON Possible results

If the current program and/or date is stored only in the PCs RAM, copy and store this immediately. Proceed to replace the PCs battery.

Monitor D8005. This is the current battery voltage (in 0.1V units). ConM8006:OFF tact a Mitsubishi service center for further consideration of the problem.

ERROR LED flashes (PROGRAM ERROR) POWER RUN BATT ERROR

Fault ERROR LED flashes

Remedy Check BATT LED.

Possible results

LED OFF

Is the BATT OK? Work through BATT diagnostic. If the BATT LED is cured yet the ERROR LED still flashes check for a programming problem.

LED is lit

Check for programming problem.

7-2

Page 113

FX2NC Series Programmable Controllers

7.2.3

Diagnostics 7.

ERROR LED ON (CPU ERROR)

POWER RUN BATT ERROR

Fault ERROR LED ON

Remedy Reset PC. Power Possible OFF,ON results and trigger RUN input.

Remedy Power OFF A

Disconnect earth/ Possible results ground terminal

LED is lit

LED is lit

A

B Check for programming error. Ensure the earth/ ground cable is correctly rewired.

LED is flashing

Power ON

B

LED OFF

Has the memory cassette been installed or removed while the units has still been powered?

Remedy Possible program/scan time error. Check D8012 for program scan time, (units 0.2 msec must be less than 0.2 sec, i.e data value <2000).

PC

M /C

9

PC

M /C

PC

9

M /C

8

Possible results D8012 > D8000

7-3

Page 114

FX2NC Series Programmable Controllers

7.3

Diagnostics 7.

Common errors - Corroded contact points at some point in an I/O line. - An I/O device has been used outside its specified operating range. - An input signal occurs in a shorter time period that taken by one program scan.

7-4

Page 115

FX2NC Series Programmable Controllers

7.4

Diagnostics 7.

Writing of program and program check [power ON and PLC stopped] 1) Turn on the PLC power. Make sure that the RUN/STOP switch of the PLC is set to STOP, and turn the power on. 2) Check the program. Check for circuit errors and grammatical errors with the program check function of the programming tool. 3) Transfer the sequence program. Wr ite the program to the memor y board with the programming tool.

Figure 7.1: Memory board protect switch

When the memory board is used Make sure to set the protect switch of the memory cassette to OFF (shown right). 4) Verify the sequence program. Verify that the program has been correctly written to the memory board. 5) Execute PLC diagnosis. Check for errors in the PLC main body with the PLC diagnostic function of the programming tool.

7-5

Page 116

FX2NC Series Programmable Controllers

7.5

Diagnostics 7.

Replacing the battery Turn OFF PC's power supply. Remove sidecover from the PC. Remove battery from holder-disconnect and replace (this should be carried out in 20 sec if the current data held in the PC’s RAM is not to be lost). Refit battery and cover.

Figure 7.2: Battery (FX2NC-32BL)

7-6

Page 117

FX2NC Series Programmable Controllers

Diagnostics 7.

Caution: • Battery replacement requires users to verify data integrity such as the PLC program (when a memory board is not attached), latched (battery backed) device values and RTC values. Before switching the PLC to RUN, ensure the safety of the operation. • If the battery backed data becomes unstable, clear the latched (battery backed) devices, and transfer the data again. Set the RTC and default values again if necessary. • Use the battery for memory backup correctly in conformance to this manual. - Use the battery only for the specified purpose. - Connect the battery correctly. - Do not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the battery. - Do not store or use the battery at high temperatures or expose to direct sunlight. - Do not expose to water, bring near fire or touch liquid leakage or other contents directly. - Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment.

7-7

Page 118

FX2NC Series Programmable Controllers

Diagnostics 7.

• Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device. When disposing of batteries, separate them from other waste according to local regulations. (For details of the Battery Directive in EU countries, refer to Appendix 9.2) • Before transporting the PLC, turn on the power to the PLC to check that the BATT LED is off. If the PLC is transported with the BATT LED on or the battery exhausted, the batterybacked data may be unstable during transportation. • The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in the general specifications (section 4.1). Failure to do so may cause failures in the PLC. After transportation, verify the operations of the PLC. • When transporting lithium batteries, follow required transportation regulations. (For details of the regulated products, refer to Appendix 9.1)

7.6

Maintenance - Battery has a 3 year life. - Check interior temperature of the panel. - Check panel air filters if fitted. - Check for loosening of terminals or mounting facilities (due to vibration).

7-8

Page 119

FX2NC Series Programmable Controllers

7.7

Diagnostics 7.

Error flags ON indicates error. M8004 (ref. 8004)

Error occurance (ON when M8060-7 are ON)

M8060 (ref. D8060)

I/O configuration error

M8005

Battery voltage abnormally low

M8061 (ref. D8061)

PC hardware error

M8006 (ref. D8005/6)

Latched low battery voltage flag

M8062 (ref. D8062)

PC/programming device communication error

M8007 (ref. D8007/8)

Momentary power failure

M8063 (ref. D8063)

Parallel link error

M8008 (ref. D8008)

Power failure (see Figure 7.2)

M8064 (ref. D8064)

Parameter error

M8009 (ref. D8009)

24V DC OFF

M8065 Syntax error (ref. D8065, D8069)

M8030

Battery LED OFF - Battery voltage low

M8066 Program (circuit) error (ref. D8066, D8069)

M8035

Forced RUN mode

M8067 Program execution error (ref. D8067, D8069)

M8036

Forced RUN signal

M8068 (ref. D8068)

Execution error latch

M8037

Forced STOP signal

M8069 (ref. D8069)

I/O bus check

M8039 (ref. D8039)

Constant scan mode

7-9

Page 120

FX2NC Series Programmable Controllers

Diagnostics 7.

Figure 7.3: Power down and its associated flags POWER ON OFF M8000 (RUN)

RUN STOP

M8007

ON OFF

M8008

ON OFF

5 msec D8008 (10 msec)

7-10