Page 121

FX2NC Series Programmable Controllers

7.8

Diagnostics 7.

Error registers

D8000 Watchdog timer (default 200msec) M8001

M8002

M8003

M8004 M8005 D8006 (default 3.0V) D8007

PC version 24201=FX2NC/FX2N V2.01 (24=FX2NC/FX2N, 201=V2.01)

D8008

Power failure detection period (Automatically corrected)

D8009

Lowest device affected by 24V DC power failure

Memory capacity 02=2K steps, 04=4K steps, 08=8K(16K) steps Memory type 02H=EEPROM protect switch OFF 0AH=EEPROM protect switch ON 10H=MPU memory Error flag number 8060=M8060, (8060-8068) Battery voltage 36=3.6V (uniits 0.1V) Low battery detection level Number of momentry power failures - reset on full power OFF

7-11

Page 122

FX2NC Series Programmable Controllers

D8060

Reports location of I/O configuration error (see Figure 7.3)

D8061

Error code for PC hardware error

D8062

Error code number for programmer communications fault

D8063

Error code for parallel link fault

D8064

Parameter error code

D8065

Systax error code

D8066

Program (circuit) error code

D8067

Program execution error code

D8068

Latched step number of execution error

D8069

Step number of errors associated with error flags M8065-M8067

Diagnostics 7.

Figure 7.4: I/O configuration error, A) number, B) type. 1 0 7 0 A) No.10 to 370 B) 1=X 0=Y

7-12

Page 123

FX2NC Series Programmable Controllers

7.9

Diagnostics 7.

Error codes D8061 0000 6101 6102 6103 D8062 0000 6201 6202 6203 6204 6205

Check cable connections No error RAM error Operation circuit error I/O bus error (M8069 = ON) Check the programmer / PC connections No error Parity/overrun/framing error Character error Data sum check error Data format error Command error

D8063 0000 6301 6302 6303 6304 6305 6306

Check both power and communications connections No error Parity/overrun/framing error Character error Data sum check error Data format error Command error Watchdog timer error

7-13

Page 124

FX2NC Series Programmable Controllers

7.10

Diagnostics 7.

Instruction list Table 7.1: Numerically sorted 0

1 CALL ZCP SUB ROL DECO REFF SER HKY PRUN

2 SRET MOV MUL RCR ENCO MTR ABSD DSW ASCI

3 4 IRET EI SMOV CML DIV INC RCL SFTR SUM BON HSCS HSCR INCD TTMR SEGD SEGL HEX CCD

000 010 020 030 040 050 060 070 080

PROGRAM FLOW TRANSFERS, COMP +-×÷, LOGICS ROTATION, SHIFT DATA OPERATION 1 HIGH-SPEED HANDY INSTR. 1 FX I/O DEVICES FX SER DEVICES

CJ CMP ADD ROR ZRST REF IST TKY RS

110 120 130 140 150 160 170 180

FLOATING POINT 1 FLOATING POINT 2 FLOATING POINT 3 DATA OPERATION 2 POSITIONING REAL TIME CLOCK GREY CODES ADDITIONAL FUNC

ECMP EZCP EADD ESUB EMUL EDIV SIN COS TAN TCMP TZCP TADD TSUB GRY GBIN EXTR* -

220 230 IN-LINE COMPARE 240

LD≥ OR=

OR>

-

5

6 7 DI FEND WDT BMOV FMOV XCH DEC WAND WOR SFTL WSFR WSFL MEAN ANS ANR HSZ SPD PLSY STMR ALT RAMP ARWS ASC PR VRRD VRSC -

8 9 FOR NEXT BCD BIN WXOR NEG SFWR SFRD SQR FLT PWM PLSR ROTC SORT FROM TO PID -

ABS* -

EBCD EBIN ESQR INT SWAP HOUR* TRD TWR RD3A* WR3A* -

LD= LD> AND= AND> AND< OR< OR≠ OR≤

LD< LD≠ LD≤ AND≠ AND≤ AND≥ OR≥ -

* V3.00 or later 7-14

Page 125

FX2NC Series Programmable Controllers

Diagnostics 7.

Table: 7.2 Alphabetically sorted Symbol FNC No. D P ABS* 155 ABSD 062 ADD 020 ALT 066 AND 232-238 A ANR 047 ANS 046 ARWS 075 ASC 076 ASCI 082 BCD 018 BIN 019 B BMOV 015 BON 044 CALL 001 CCD 084 CJ 000 C CML 014 CMP 010 COS 131 025 D DEC

Symbol FNC No. D P DECO 041 DI 005 D DIV 023 DSW 072 EADD 120 EBCD 118 EBIN 119 ECMP 110 EDIV 123 EI 004 E EMUL 122 ENCO 042 ESQR 127 ESUB 121 EXTR* 180 EZCP 111 FEND 006 FLT 049 016 F FMOV FOR 008 FROM 078

Symbol FNC No. D P GBIN 171 G GRY 170 HOUR* 169 HEX 083 HKY 071 H HSCR 054 HSCS 053 HSZ 055 INC 024 INCD 063 129 I INT IRET 003 IST 060 224-230 L LD MEAN 045 MOV 012 M MTR 052 MUL 022 NEG 029 N NEXT 009 240-246 O OR

7-15

Page 126

FX2NC Series Programmable Controllers

Symbol FNC No. D P PID 088 PLSR 059 PLSY 057 P PR 077 PRUN 081 PWM 058 RAMP 067 RCL 033 RCR 032 RD3A* 176 REF 050 R REFF 051 ROL 031 ROR 030 ROTC 068 RS 080 SEGD 073 SEGL 074 S SER 061 SFRD 039 SFTL 035

Diagnostics 7.

Symbol FNC No. D P SFTR 034 SFWR 038 SIN 130 SMOV 013 SORT 069 SPD 056 S SQR 048 SRET 002 STMR 065 SUB 021 SUM 043 SWAP 147 TADD 162 TAN 132 TCMP 160 TKY 070 T TO 079 TRD 166 TSUB 163 TTMR 064 TWR 167

Symbol FNC No. D P T TZCP 161 VRRD 085 V VRSC 086 WAND 026 WDT 007 WOR 027 W WR3A* 177 WSFL 037 WSFR 036 WXOR 028 X XCH 017 ZCP 011 Z ZRST 040 * V3.00 or later

7-16

Page 127

FX2NC Series Programmable Controllers

Diagnostics 7.

FX2NC Built-in memory(RAM) = 8K steps FX2NC-EEPROM-4C = 2K - 4K steps FX2NC-EEPROM-16 = 2K - 16K steps FX2NC-EEPROM16C = 2K - 16K steps

Program capacity Input (X) relay

X0 - 267 (184 pnts)

Output (Y) relay

Y0 - 267 (184 pnts)

Auxiliary relay (3072 pnts, + 256 pnts)

State relay (1000 pnts)

Timer (256 pnts)

General

M0-M499 (500 pnts)

Battery backup

M500-M1023 (524 pnts)

(X + Y) ≤ 256 pnts Max. Battery backup by Parameters

Battery backup

M1024-M3071 (2048 pnts)

Special function

M8000-M8255 (256 pnts)

General

S0-S499 (500 pnts)

Battery backup

S500-S999 (500 pnts) (S900-S999 ANS FNC46)

Battery backup by Parameters

100 ms

T0-T199 (200 pnts)

10 ms

T200-T245 (46 pnts)

1 ms retentive 100 ms retentive

Battery backup

T246-T249 (4 pnts) T250-T255 (6 pnts)

7-17

Page 128

FX2NC Series Programmable Controllers

Diagnostics 7.

FX2NC

Counter (256 pnts)

16 bit

C0-C99 (100 pnts)

16 bit

C100-C199 (100 pnts)

32 bit

C200-C219 (20 pnts)

32 bit

C220-C234 (15 pnts)

Battery backup by Parameters

Battery backup by Parameters

C235-C245 32 bit High speed counter

C246-C250 C251-C255

Data register (8000 pnts, + 256 pnts)

Pointer Nesting

General

D0-D199 (200 pnts)

Battery backup

D200-D511 (312 pnts)

Battery backup

D512-D7999 (7488 pnts)

Battery backup by Parameters D1000-D7999 File register by Parameters

Special function

D8000-D8255 (256 pnts)

Index

V0-V7, Z0-Z7 (16 pnts)

CJ (FNC 00), CALL (FNC 01) EI (FNC 04)

P0-P127 (128 pnts) I00

MC /MCR

- I50 , I6

- I8

, I010 - I060 (6, 3, 6 pnts)

N0 - N7 (8 pnts)

Numbers

16 bit

32 bit

K

-32,768 to 32,767

-2,147,483,648 to 2,147,483,647

H

0 to FFFFH

0 to FFFFFFFFH

7-18

Page 129

FX2NC Series Programmable Controllers

1

INTRODUCTION

2

TERMINAL LAYOUTS

3

INSTALLATION NOTES

4

POWER SUPPLY

5

INPUTS

6

OUTPUTS

7

DIAGNOSTICS

8

DISCONTINUED MODEL

9

APPENDIX

Discontinued model 8.

Page 130 read from a scan by OCR; it may hold reading errors

FX2NC Series Programmable Controllers Discontinued model 8.

ae MITSUBISHI