FX2NC (D/UL) Series Programmable Controllers Hardware Manual: 3. Installation notes, pages 49 to 56

Pages 49 to 56 of 140, from FX2NC (D/UL) Series Programmable Controllers Hardware Manual

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi FX2NC-32MT

Page 49

FX2NC Series Programmable Controllers

3.

Installation notes 3.

Installation notes The installation of FX2NC products has been designed to be safe and easy. When the products associated with this manual are used as a system or individually, they must be installed in a suitable enclosure. The enclosure should be selected and installed in accordance to the local and national standards.

3-1

Page 50

FX2NC Series Programmable Controllers

3.1

Installation notes 3.

Product outline Figure 3.1:Features of the FX2NC PC N

M

E

F

D

Extension block

A

H I J G

POWER RUN BATT ERROR X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17

RUN

POWER STOP

Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17

POWER

X0 X1 X2 X3 X4 X5 X6 X7 X0 X1 X2 X3 X4 X5 X6 X7

Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7

A

O

K L Main unit

C

B

3-2

Page 51

FX2NC Series Programmable Controllers

Installation notes 3.

Table 3.1 : Feature table A

Slide lock for extension I/O block

B

Power supply connector (Uses the 24V DC)

C

Din rail clip

D

Backup battery

E

Status indicators (POWER, RUN, BATT, ERROR)

F

Run / Stop switch

G

Programming port

H

Extension connector

I

Output indicators

J

Input indicators

K

Output connector or Output terminal

L

Input connector or Input terminal

M

Function adapter connector

N

Memory board / Real time clock board, connector

O

Input power supply connector, input power supply connector for crossover wiring

3-3

Page 52

FX2NC Series Programmable Controllers

3.2

Installation notes 3.

FX2NC RUN/STOP Control RUN or STOP of the FX2NC can be controlled by: nThe RUN/STOP switch mounted next to the programming port. oA standard input (X000 to X017; X000 to X007 for FX2NC-16M★ units) defined by the system parameters. pRemotely from a personal computer or other programming peripheral. Note:The FX2NC RUN/STOP switch n works in parallel with the RUN-input terminal o. Please refer to table 3.2. During remote operation the FX2NC RUN/STOP status is determined by the most recently operated control. E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal computer the RUN/STOP switch must be switched to STOP then back to RUN to switch the MPU back to RUN mode.

3-4

Page 53

FX2NC Series Programmable Controllers

Installation notes 3.

Table 3.2 : RUN/STOP selection n RUN/STOP o RUN INPUT FX2NC MPU SWITCH

TERMINAL

STATUS

RUN

ON

RUN

RUN

OFF

RUN

STOP

OFF

STOP

STOP

ON

RUN

Figure 3.2:

n Œ

R e m o te STOP

STOP POWER RUN BATT ERROR X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17 pRUN

RUN

STOP

Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 nop RUN no p p p S TO P

RUN o

R e m o te RUN

RUN COM

COM X0 X1 Parameter setting

3-5

Page 54

FX2NC Series Programmable Controllers

3.3

Installation notes 3.

General specifications Table 3.3 :General Specifications Item

Description

Operating Temperature

0 to 55 °C (32 to 131 °F)

Storage Temperature

-20 to 70 °C (-4 to 158 °F)

Operating Humidity

35 to 85% Relative Humidity, No condensation storage Humidity

35 to 90% Relative Humidity, No condensation

Vibration Resistance*1 - Direct Mounting

10 - 57 Hz: 0.075 mm Half Amplitude 57 - 150 Hz: 9.8 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Vibration Resistance*1 - DIN rail Mounting

10 - 57 Hz: 0.035 mm Half Amplitude 57 - 150 Hz: 4.9 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Shock Resistance*1

147m/s2 Acceleration, Action Time: 11 ms 3 times by half-sine pulse in each direction X, Y, and Z

Noise Immunity

1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator

Dielectric Withstand Voltage

500 V AC > 1 min, tested between all points, terminals and ground

Insulation Resistance

5 MΩ > at 500 V DC, tested between all points, terminals and ground

Ground

Class D (100 Ω or less)

Working atmosphere

Free from corrosive or flammable gas and excessive conductive dust

Working altitude

<2000m *2

*1 The criterion is shown in IEC61131-2. *2 Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC. 3-6

Page 55

FX2NC Series Programmable Controllers

PC mounting arrangements To prevent a rise in temperature, mount the units to walls. Never mount them to the floor or ceiling of an enclosure. Single row arrangement Double row arrangement using extension cable FX0N-65EC (650mm (25.59 inches); supplied separately). Figure 3.4 :

A

A

FX2NC CPU

FX2NC-32EX-D/UL

A A

A

A

A A > 50mm(1.97 inches)

FX2NC CPU

FX2NC-CNV-IF

Figure 3.2 :

FX2NC-16EX-D/UL

Figure 3.3 Figure 3.4

FX2NC-16EX-D/UL

3.4

Installation notes 3.

A

FX0N,FX2N Extension blocks

A

Extension cable FX0N-65EC

A

A A > 50mm(1.97 inches)

3-7

Page 56

FX2NC Series Programmable Controllers

Installation notes 3.

Caution • Units should mot be installed in areas subject to the following conditions: excessive or conductive dust, corrosive gas (salt air, Cl2, H2S, SO2, NO2, etc.) or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration. • Take special care not to allow debris to fall inside the unit during installation e.g. cut wires, shavings etc. Once installation is complete remove the protective paper band: to prevent overheating.

3-8