Page 51
An Introduction to Programming
Programming PLC Applications
쎲 Alarm activation delay Ladder Diagram
Instruction List K100 T1
M1 18
18 19 22 23
K300 T2
T1 22
LD OUT LD OUT
M1 T1 T1 T2
K100 K300
When an alarm is triggered (M1 switches to “1”) the 10s delay timer starts. After the 10 seconds T1 then starts timer T2, which is set to 30 seconds, and the siren activation time begins. 쎲 Alarm display (switch on siren and rotating beacon) Ladder Diagram T1
Instruction List
T2
26 27 28 29 30
Y001
26 T1
Y002
29
LD ANI OUT LD OUT
T1 T2 Y001 T1 Y002
The siren is activated after the 10s activation delay (T1) and remains on while timer T2 is running. After the end of the 30s activation period (T2) the siren deactivates. The rotating beacon is also switched on after the 10s delay. The following illustration shows the signal sequence generated by this section of the program: 1
M1 0 1
10 s
T1 0 1
30 s
T2 0 ON
Y1
OFF ON
Y2
OFF t
FX Beginners Manual
3 – 25
Page 52
Programming PLC Applications
An Introduction to Programming
쎲 Resetting all outputs and the relay Ladder Diagram
Instruction List
X001 31
RST
Y000
RST
Y001
RST
Y002
RST
Y003
RST
Y004
RST
Y005
RST
M1
31 32 33 34 35 36 37 38
LDI RST RST RST RST RST RST RST
X001 Y000 Y001 Y002 Y003 Y004 Y005 M1
When the alarm system is switched off with the key-operated switch all the outputs used by the program and the relay M1 are all reset. If an alarm was triggered the interrupted alarm circuit which was released until the system was switched off is displayed.
3 – 26
MITSUBISHI ELECTRIC
Page 53
An Introduction to Programming
Programming PLC Applications
Connection of the PLC The sketch below shows how easy it is to implement this alarm system with a PLC of the FX family. The example shows an FX1N-14MR. S1
S11
S21
S31
S12
S22
S32
S/S 0 V N PE L1
S/S
100-240 VAC
L
N
X1 X0
X3 X2
X5
X7
X4
X6
0 1 2 3 4 5 6 7
MITSUBISHI
IN
POWER RUN ERROR
FX1S-14MR OUT
0 1 2 3 4 5 0V 24V
H0
FX Beginners Manual
E1
Y0 COM0
Y1 COM1
Y2 COM2
H1
Y4 Y3
Y5
14MR -ES/UL
H2
H3
H4
3 – 27
Page 54
Programming PLC Applications
3.6.2
An Introduction to Programming
A rolling shutter gate Task description We want to implement a control system for a warehouse’s rolling shutter gate that will enable easy operation from both outside and inside. Safety facilities must also be integrated in the system.
Warning lamp H1
S7
S3
S1
S5
STOP S6 S0
S2
S4
쎲 Operation – It must be possible to open the gate from outside with the key-operated switch S1 and to close it with pushbutton S5. Inside the hall it should be possible to open the gate with pushbutton S2 and to close it with S4. – An additional time switch must close the gate automatically if it is open for longer than 20 s. – The states “gate in motion” and “gate in undefined position” must be indicated by a blinking warning lamp. 쎲 Safety facilities
3 – 28
–
A Stop button (S0) must be installed that can halt the motion of the gate immediately at any time, stopping the gate in its current position. This Stop switch is not an Emergency OFF function, however! The switch signal is only processed by the PLC and does not switch any external power connections.
–
A photoelectric barrier (S7) must be installed to identify obstacles in the gateway. If it registers an obstacle while the gate is closing the gate must open automatically.
–
Two limit switches must be installed to stop the gate motor when the gate reaches the fully open (S3) and fully closed (S6) positions.
MITSUBISHI ELECTRIC
Page 55
An Introduction to Programming
Programming PLC Applications
Assignment of the input and output signals The task description clearly defines the number of inputs and outputs needed. The gate drive motor is controlled with two outputs. The signals required are assigned to the PLC inputs and outputs as follows: Function
Inputs
Outputs
Timer
Name
Adress
Remarks Break contact (when the switch is operated X0 = “0” and the gate stops)
STOP button
S0
X0
OPEN key-operated switch (outside)
S1
X1
OPEN button (inside)
S2
X2
Upper limit switch (gate open)
S3
X3
CLOSE button (inside)
S4
X4
CLOSE button (outside)
S5
X5
Lower limit switch (gate closed)
S6
X6
Break contact (X6 = “0” when the gate is down and S6 is activated)
Photoelectric barrier
S7
X7
X7 is set to “1” when an obstacle is registered
Warning lamp
H1
Y0, Motor contactor (motor reverse)
K1
Y1
Reverse = OPEN gate
Motor contactor (motor forward)
K2
Y2
Forward = CLOSE gate
Delay for automatic close, T0
Time: 20 seconds
Make contacts Break contact (X2 =”0” when the gate is up and S3 is activated) Make contacts
The program components 쎲 Operation of the rolling shutter gate with the pushbuttons The program must convert the input signals for the operation of the gate into two commands for the drive motor: “Open Gate” and “Close Gate”. Since these are signals from pushbuttons that are only available briefly at the inputs they need to be stored. To do this we use two relays to represent the inputs in the program and set and reset them as required: –
M1: open gate
–
M2: close gate
Ladder Diagram
Instruction List
X001 0
PLS
M100
SET
M1
PLS
M200
SET
M2
X002
M100
M2
4 X004 7 X005
M200 11
0 1 2 4 5 6 7 8 9 11 12 13
LD OR PLS LD ANI SET LD OR PLS LD ANI SET
X001 X002 M100 M100 M2 M1 X004 X005 M200 M200 M1 M2
M1
The signals for opening the gate are processed first: When key-operated switch S1 or button S2 are operated a signal is generated and M001 is set to a signal state of “1” for just one pro-
FX Beginners Manual
3 – 29
Page 56
Programming PLC Applications
An Introduction to Programming gram cycle. This ensures that the gate cannot be blocked if the button sticks or of the operator does not release it. It must be ensured that the drive can only be switched on when it is not already turning in the opposite direction. This is implemented by programming the PLC so that M1 can only be set when M2 is not set. NOTE
The motor direction interlock must also be complemented by an additional interlock with physical contactors outside the PLC (see wiring diagram). A similar approach is used to process the signals from buttons S4 and S5 for closing the gate. Here, M1 is polled for a signal state of “0” to ensure that M1 and M2 cannot both be set at the same time. 쎲 Close gate automatically after 20 seconds Ladder Diagram
Instruction List
X003
K200 T0
14 T0 18
SET
M2
14 15 18 19
LDI OUT LD SET
X003 T0 T0 M2
K200
When the gate is open limit switch S3 activates and input X3 is switched off. (For safety reasons S3 is a break contact.) When this happens timer T0 starts the 20s delay (K200 = 200 x 0.1s = 20s). When the timer reaches 20s relay M2 is set and the gate is closed. 쎲 Stop gate with STOP switch Ladder Diagram
Instruction List
X000 20
RST
M1
RST
M2
20 LDI 21 RST 22 RST
X000 M1 M2
Pressing the STOP button (S0) resets relays M1 and M2, stopping the gate motor. 쎲 Identifying obstacles with the photoelectric barrier Ladder Diagram X007 23
Instruction List
M2 RST
M2
SET
M1
23 24 25 26
LD AND RST SET
X007 M2 M2 M1
If an obstacle is registered by the photoelectric barrier while the gate is closing relay M2 is reset and the close operation is halted. After this relay M1 is set, opening the gate again.
3 – 30
MITSUBISHI ELECTRIC
Page 57
An Introduction to Programming
Programming PLC Applications
쎲 Switching the motor of with the limit switches Ladder Diagram
Instruction List
X003 27
RST
M1
RST
M2
X006 29
27 28 29 30
LDI RST LDI RST
X003 M1 X006 M2
When the gate is open limit switch S3 is activated and input X3 is switched off. This resets relay M1, turning off the motor. When the gate is fully closed S6 is activated, X6 is switched off and M2 is reset, turning off the motor. For safety reasons the limit switches are break contacts. This ensures that the motor is also switched off automatically (or cannot be switched on) if the connection between the switch and the input is interrupted. NOTE
The limit switches must be wired so that they also switch off the motor automatically without support from the PLC (see wiring diagram). 쎲 Controlling the motor Ladder Diagram
Instruction List
M1 31
Y001 M2
33
Y002
31 32 33 34
LD OUT LD OUT
M1 Y001 M2 Y002
At the end of the program the signal states of relays M1 and M2 are transferred to outputs Y001 and Y002. 쎲 Warning lamp: “Gate in Motion” and “Gate in Undefined Position” Ladder Diagram
Instruction List
X003 X006 M8013 35
Y000
35 36 37 38
LD AND AND OUT
X003 X006 M8013 Y000
If neither of the limit switches is activated this means that the gate is being opened or closed or has been stopped in an intermediate position. In all these situations the warning lamp blinks. The blink speed is controlled with special relay M8013, which is automatically set and reset at 1s intervals (see Chapter 4.2).
FX Beginners Manual
3 – 31
Page 58
Programming PLC Applications
An Introduction to Programming
Connection of the PLC
24 V
S1
S0
S2
S3
S4
S5
S6
Photoelectric barrier
Lower limit switch
Close gate (outside)
Close gate (inside)
Upper limit switch
Open gate (inside)
STOP
Open gate (outside)
The rolling shutter gate control system can be implemented with a controller like the FX1N-14MR.
S7
L1 N PE S/S 0 V
S/S
100-240 VAC
L
N
X1
X3
X0
X5
X2
X4
X7 X6
0 1 2 3 4 5 6 7
MITSUBISHI
IN
POWER RUN ERROR
FX1S-14MR OUT
0 1 2 3 4 5 0V 24V
Y0 COM0
Y1 COM1
Y2 COM2
Y4 Y3
Y5
14MR -ES/UL
Interlock by contactor
3 – 32
S3
S6
K1
K2
Deactivation by limit switches
Close gate
K1
Open gate
Warning lamp
H1
K2
MITSUBISHI ELECTRIC
Page 59
Devices in Detail
4
Inputs and Outputs
Devices in Detail The devices in PLCs are used directly in control program instructions. Their signal states can be both read and changed by the PLC program. A device reference has two parts: – the device name and
– the device address.
Example of a device reference (e.g. input 0):
X0 Device name
4.1
Device address
Inputs and Outputs The PLC’s inputs and outputs connect it to the process that it is controlling. When an input is polled by the PLC program the voltage on the input terminal of the controller is measured. Since these inputs are digital they can only have two signal states, ON or OFF. When the voltage at the input terminal reaches 24V the input is on (state “1”). If the voltage is lower than 24V the input evaluates as off (signal state “0”). In MELSEC PLCs the identifier “X” is used for inputs. The same input can be polled as often as necessary in the same program.
NOTE
The PLC cannot change the state of inputs. For example, it is not possible to execute an OUT instruction on an input device. If an output instruction is executed on an output the result of the current operation (the signal state) is applied to the output terminal of the PLC. If it is a relay output the relay closes (all relays have make contacts). If it is a transistor output the transistor makes the connection and activates the connected circuit. The illustration on the left shows an example of how you can connect switches to the inputs and lamps and contactors to the outputs of a MELSEC PLC. X000 X001 X002
Y000 Y001 Y002
The identifier for output devices is “Y”. Outputs can be used in logic operation instructions as well as with output instructions. However, it is important to remember that you can never use an output instruction on the same output more than once (see also chapter 3.4.2).
FX Beginners Manual
4–1
Page 60
Inputs and Outputs
Devices in Detail
The following table provides a general overview of the inputs and outputs of the controllers of the MELSEC FX family. Device
Inputs
Outputs
Device identifier
X
Y
Device type
Bit device
Possible values
0 or 1
Device address format
Octal
Number of devices and addresses (depends on controller base unit type)
FX1S
6 (X00–X05) 8 (X00–X07) 12 (X00–X07, X10, X11, X12, X13) 16 (X00–X07, X10–X17)
4 (Y00–Y03) 6 (Y00–Y05) 8 (Y00–Y07) 14 (Y00–Y07, Y10–Y15)
FX1N
8 (X00–X07) 14 (X00–X07, X10–X15) 24 (X00–X07, X10–X17, X20–X27) 36 (X00–X07, X10–X17, X20–X27, X30–X37, X40, X41, X42, X43) The total number of inputs can be increased to max. 84 (X123) with expansion modules. However, the sum of all inputs and outputs cannot exceed 128.
6 (Y00–Y05) 10 (Y00–Y07, Y10, Y11) 16 (Y00–Y07, Y10–Y17) 24 (Y00–Y07, Y10–Y17, Y20–Y27) The total number of outputs can be increased to max. 64 (Y77) with expansion modules. However, the sum of all inputs and outputs cannot exceed 128.
FX2N
8 (X00–X07) 16 (X00–X07, X10–X17) 24 (X00–X07, X10–X17, X20–X27) 32 (X00–X07, X10–X17, X20–X27, X30–X37) 40 (X00–X07, X10–X17, X20–X27, X30–X37, X40–X47) 64 (X00–X07, X10–X17, X20–X27, X30–X37, X40–X47, X50–X57, X60–X67, X70–X77)
8 (Y00–Y07) 16 (Y00–Y07, Y10–Y17) 24 (Y00–Y07, Y10–Y17, Y20–Y27) 32 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37) 40 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37, Y40–Y47) 64 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37, Y40–Y47, Y50–Y57, Y60–Y67, Y70–Y77)
FX2NC
8 (X00–X07) 16 (X00–X07, X10–X17) 32 (X00–X07, X10–X17, X20–X27, X30–X37) 48 (X00–X07, X10–X17, X20–X27, X30–X37, X40–X47, X50–X57)
8 (Y00–Y07) 16 (Y00–Y07, Y10–Y17) 32 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37) 48 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37, Y40–Y47, X50–X57)
FX3U
8 (X00–X07) 16 (X00–X07, X10–X17) 24 (X00–X07, X10–X17, X20–X27) 32 (X00–X07, X10–X17, X20–X27, X30–X37) 40 (X00–X07, X10–X17, X20–X27, X30–X37, X40–X47)
8 (Y00–Y07) 16 (Y00–Y07, Y10–Y17) 24 (Y00–Y07, Y10–Y17, Y20–Y27) 32 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37) 40 (Y00–Y07, Y10–Y17, Y20–Y27, Y30–Y37, Y40–Y47)
* The total number of inputs can be increased to max. 248 (X367) with expansion modules. However, the sum of all inputs and outputs cannot exceed 256.
4–2