Page 61
Devices in Detail
4.2
Relays
Relays In your PLC programs you will often need to store intermediate binary results (a signal state of “0” or “1”) temporarily for future reference. The PLC has special memory cells available for this purpose known as “auxiliary relays”, or “relays” for short (device identifier: "M"). You can store the binary result of an operation in a relay, for example with an OUT instruction, and then use the result in future operations. Relays help to make programs easier to read and also reduce the number of program steps: You can store the results of operations that need to be used more than once in a relay and then poll it is often as you like in the rest of the program.
M1
M1 Poll for signal state “1” (relay set)
M1 Poll for signal state “0” (has the relay been reset?)
In addition to normal relays the FX controllers also have retentive or “latched” relays. The normal unlatched relays are all reset to a signal state of “0” when the PLC power supply is switched off, and this is also their standard state when the controller is switched on. In contrast to this, latched relays retain their current states when the power is switched off and on again. Relay types
Device
Unlatched relays
Device identifier
M
Device type
Bit device
Possible values für a device
0 or 1
Device address format
Number of devices and addresses
햲 햳
4.2.1
Latched relays
Decimal FX1S
384 (M0–M383)
128 (M384–M511)
FX1N
384 (M0–M383)
1152 (M384–M1535)
FX2N FX2NC
500 (M0–M499)���
FX3U
500 (M0–M499)���
524 (M500–M1023)��� 2048 (M1024–M3071) 524 (M500–M1023)��� 6656 (M1024–M7679)
You can also configure these relays as latched relays with the PLC parameters. You can also configure these relays as unlatched relays with the PLC parameters.
Special relays In addition to the relays that you can switch on and off with the PLC program there is also another class of relays known as special or diagnostic relays. These relays use the address range starting with M8000. Some contain information on system status and others can be used to influence program execution. The following table shows a few examples of the many special relays available.
FX Beginners Manual
4–3
Page 62
Timers
4.3
Devices in Detail
Special relay
Function
Program processing options
M8000
When the PLC is in RUN mode this relay is always set to “1”.
M8001
When the PLC is in Run mode this relay is always set to “0”.
M8002
Initialisation pulse (following activation of RUN mode this relay is set to “1” for the duration of one program cycle.
M8004
PLC error
M8005
Low battery voltage
M8013
Clock signal pulse: 1 second
M8031
Clear all devices (except data registers D) that are not registered as battery-latched.
M8034
Disable outputs – the PLC outputs remain off but program execution continues.
Poll signal state
Poll signal state Set signal state.
Timers When you are controlling processes you will often want to program a specific delay before starting and stopping certain operations. In hard-wired controllers this is achieved with timer relays. In PLCs this is achieved with programmable internal timers. Timers are really just counters that count the PLCs internal clock signals (e.g. 0.1s pulses). When the counter value reaches the setpoint value the timer’s output is switched on. All timers function as make delay switches and are activated with a “1” signal. To start and reset timers you program them in the same way as outputs. You can poll the outputs of timers as often as you like in your program. Instruction List
Ladder Diagram
K123 T200
X0 0 T200 4
Y0
0 1 4 5
LD OUT LD OUT
X0 T200 T200 Y0
K123
In the above example timer T200 is started when input X0 is switched on. The setpoint value is 123 x 10ms = 1.23 s, so T200 switches on output Y0 after a delay of 1.23 s. The signal sequence generated by the following program example is as follows:
1,23 s X0
T200
The timer continues to count the internal 10ms pulses as long as X0 remains on. When the setpoint value is reached the output of T200 is switched on.
If input X0 or the power supply of the PLC are switched off the timer is reset and its output is also switched off.
Y0 You can also specify the timer setpoint value indirectly with a decimal value stored in a data register. See Chapter 4.6.1 for details.
4–4
MITSUBISHI ELECTRIC
Page 63
Devices in Detail
Timers
Retentive timers In addition to the normal timers described above the controllers of the FX1N, FX2N, FX2NC and FX3U series also have retentive timers that retain their current time counter value even if the device controlling them is switched off. The current timer counter value is stored in a memory that is retained even in the event of a power failure. Example of a program using a retentive timer: Instruction List
Ladder Diagram
X1
K345 T250
0 T250
Y1
4
0 1 4 5 6 7
LD OUT LD OUT LD RST
X0 T250 T250 Y1 X2 T250
K345
X2 6
RST T250
Timer T250 is started when input X0 is switched on. The setpoint value is 345 x 0.1 s = 34.5s. When the setpoint value is reached T250 switches output Y1 on. Input X2 resets the timer and switches its output off..
t1 X1 t2 t1 + t2 = 34,5 s When X1 is on the timer counts the internal 100ms pulses. When X1 is switched off the current time counter value is retained. The timer’s output is switched on when the current value reaches the setpoint value of the timer.
T250
Y1
A separate instruction must be programmed to reset the timer since it is not reset by switching off input X1 or the PLC’s power. Input X2 resets timer T250 and switches off its output..
X2
FX Beginners Manual
4–5
Page 64
Timers
Devices in Detail
Timers in the base units of the MELSEC FX family Timer types
Device
Normal Timers
Device identifier
T
Device type (for setting and polling)
Bit device
Retentive Timers
Possible values (timer output)
0 or 1
Device address format
Decimal
Timer setpoint value entry
As a decimal integer constant. The setpoint can be set either directly in the instruction or indirectly in a data register.
FX1S
FX1N
Number of devices and addresses FX2N FX2NC
FX3U
100 ms (Range 0.1 to 3276.7 s)
63 (T0–T62), 10 ms (Range 0.01 to 327.67 s)
31 (T32–T62)*, 1 ms (Bereich 0.001 to 32.767 s)
1 (T63), 100 ms (Range 0.1 to 3276.7 s)
200 (T0–T199)
6 (T250–T255)
10 ms (Range 0.01 to 327.67 s)
46 (T200–T245), 1 ms (Range 0.001 to 32.767 s)
4 (T246–T249), 100 ms (Range 0.1 to 3276.7 s)
200 (T0–T199)
6 (T250–T255)
10 ms (Range 0.01 to 327.67 s)
46 (T200–T245), 1 ms (Range 0.001 to 32.767 s), 4 (T246–T249)
100 ms (Range 0.1 to 3276.7 s)
200 (T0–T199)
6 (T250–T255)
10 ms (Range 0.01 to 327.67 s)
46 (T200–T245)
1 ms (Range 0.001 to 32.767 s)
256 (T256–T511)
4 (T246–T249)
* These timers are only available when special relay M8028 is set. The total number of 100ms timers is then reduced to 32 (T0 – T31).
4–6
MITSUBISHI ELECTRIC
Page 65
Devices in Detail
4.4
Counters
Counters The programmers of the FX family also have internal counters that you can use for programming counting operations. Counters count signal pulses that are applied to their inputs by the program. The counter output is switched on when the current counter value reaches the setpoint value defined by the program. Like timers, counter outputs can also be polled as often as you like in the program. Example of a program using a counter: Ladder Diagram
Instruction List
X0 RST C0
0 X1
K10 C0
3
0 1 3 4 7 8
LD RST LD OUT LD OUT
X0 C0 X1 C0 C0 Y0
K10
C0 7
Y0
Whenever input X1 is switched on the value of counter C0 is incremented by 1. Output Y0 is set when X1 has been switched on and off ten times (the counter setpoint is K10). The signal sequence generated by this program is as follows: First the counter is reset with input X0 and a RST instruction. This resets the counter value to 0 and switches off the counter output.
X0
X1
0
1
2
3
4
5
6
7
8
9
10
Once the counter value has reached the setpoint value any additional pulses on input X1 no longer have any effect on the counter.
Y0
There are two kinds of counters, 16-bit counters and 32-bit counters. As their names indicate, they can count up to either 16-bit or 32-bit values and they use 16 bits and 32 bits, respectively, to store their setpoint values. The following table shows the key features of these counters.
FX Beginners Manual
4–7
Page 66
Counters
Devices in Detail
Feature
16 Bit Counters
32 Bit Counters
Count direction
Incrementing
Incrementing and decrementing (the direction is specified by switching a special relay on or off)
Setpoint value range
1 to 32767
-2 147 483 648 to 2 147 483 647
Setpoint value entry
Directly as a decimal constant (K) in the instruction, or indirectly in a data register
Directly as a decimal constant (K) in the instruction or indirectly in a pair of data registers
Counts to a maximum of 32,767, after which the counter value no longer changes.
Ring counter: After reaching 2,147,483,647 the next incrementing value is -2,147483,648. (When counting backwards the jump is from -2,147483,648 to 2,147,483,647)
Counter output
Once the setpoint value has been reached the output remains on.
When incrementing the output remains on once the setpoint value has been reached. When decrementing the output is reset (switched off) once the value drops below the setpoint value.
Resetting
An RST instruction is used to delete the current value of the counter and turn off its output.
Counter overflow behaviour
In addition to normal counters the controllers of the MELSEC FX family also have high-speed counters. These are 32-bit counters that can process high-speed external counter signals read on inputs X0 to X7. In combination with some special instructions it is very easy to use these counters to automate positioning tasks and other functions. High-speed counters use an interrupt principle: The PLC program is interrupted and responds immediately to the counter signal. For a detailed description of high-speed counters please refer to the Programming Manual for the MELSEC FX family. Counter overview Counter types
Device
Normal counters
Device identifier Device type (for setting and polling)
Bit device
Possible device values (counter output)
0 or 1
Device address format
Decimal
Counter setpoint value entry
As a decimal integer constant. The setpoint can be set either directly in the instruction or indirectly in a data register (two data registers for 32-bit counters).
FX1S
FX1N Number of devices and addresses FX2N FX2NC
FX3U
16 bit counter
16 (C0–C15)
16 (C16–C31)
32 bit counter, - 32 bit high-speed counter, 21 (C235–C255)
16 bit counter
16 (C0–C15)
184 (C16–C199)
32 bit counter
20 (C200–C219)
15 (C220–C234)
32 bit high-speed counter, 21 (C235–C255)
16 bit counter
100 (C0–C99)���
100 (C100–C199)���
32 bit counter
20 (C200–C219)���
햲 햳
15 (C220–C234)���
���
32 bit high-speed counter
21 (C235–C255)
16 bit counter
100 (C0–C99)���
32 bit counter
20 (C200–C219)���
32 bit high-speed counter
4–8
Retentive counters
C
100 (C100–C199)��� 15 (C220–C234)���
���
21 (C235–C255)
The current counter values of retentive counters are retained when the power supply is switched off. You can set the PLC parameters to configure whether the current values of these counters should be retained when the power supply is switched off.
MITSUBISHI ELECTRIC
Page 67
Devices in Detail
4.5
Registers
Registers The PLC’s relays are used to store the results of operations temporarily. However, relays can only store values of On/Off or 1/0, which means that they are not suitable for storing measurements or the results of calculations. Values like this can be stored in the “registers” of the controllers of the FX family. Registers are 16 bits or one word wide (see Chapter 3.2). You can create “double word” registers capable of storing 32-bit values by combining two consecutive data registers.
1 sign bit
15 data bits
Register: 16 bit 2 14 2 13 2 12 2 11 2 10 2 9 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0
0: = positive value 1: = negative value
31 data bits
1 sign bit Double word register: 32 bit ... 2 30 2 29 2 28
... 22 21 20
0: = positive value 1: = negative value
A normal register can store values from 0000H – FFFFH (-32,768 – 32,767). Double-word registers can store values from 00000000H – FFFFFFFFH (-2,147,483,648 – 2,147,483,647). The controllers of the FX family have a large number of instructions for using and manipulating registers. You can write and read values to and from registers, copy the contents of registers, compare them and perform math functions on their contents (see chapter 5).
4.5.1
Data registers Data registers can be used as memory in your PLC programs. A value that the program writes to a data register remains stored there until the program overwrites it with another value. When you use instructions for manipulating 32-bit data you only need to specify the address of a 16-bit register. The more significant part of the 32-bit data is automatically written to the next consecutive register. For example, if you specify register D0 to store a 32-bit value D0 will contain bits 0 through 15 and D1 will contain bits 16 through 31.
FX Beginners Manual
4–9
Page 68
Registers
Devices in Detail
What happens when the PLC is switched off or stopped In addition to the normal registers whose contents are lost when the PLC is stopped or the power supply is turned off, the FX PLCs also have latched registers, whose contents are retained in these situations. NOTE
When special relay M8033 is set the contents of the unlatched data registers are also not cleared when the PLC is stopped. Data register overview Data register types
Device
Normal registers
Device identifier
D
Device type (for setting and polling)
Word device (two registers can be combined to store double-word values)
Possible device values
16 bit registers: 0000H to FFFFH (-32768 to 32767) 32 bit register: 00000000H to FFFFFFFFH (-2 147 483 648 to 2 147 483 647)
Device address format
Decimal
Number of devices and addresses
햲 햳
4.5.2
Latched registers
FX1S
128 (D0–D127)
128 (D128–D255)
FX1N
128 (D0–D127)
7872 (D128–D7999)
FX2N FX2NC
200 (D0–D199)���
FX3U
200 (D0–D199)���
312 (D200–D511)��� 7488 (D512–D7999) 524 (M500–M1023)��� 6656 (M1024–M7679)
You can also configure these registers as latched registers with the PLC parameters. You can also configure these registers as unlatched registers with the PLC parameters.
Special registers Just like the special relays (Chapter 4.2.1) starting at address M8000 the FX controllers also have special or diagnostic registers, whose addresses start at D8000. Often there is also a direct connection between the special relays and special registers. For example, special relay M8005 shows that the voltage of the PLC’s battery is too low, and the corresponding voltage value is stored in special register D8005. The following table shows a small selection of the available special registers as examples. Special register
Function
D8004
Error relay address (shows which error relays are set)
D8005
Battery voltage (e.g. the value “36” means 3.6V)
D8010
Current program cycle time
D8013–D8019
Time and date of the integrated real-time clock
D8030
Value read from potentiometer VR1 (0 – 255)
D8031
Value read from potentiometer VR2 (0 – 255)
Program processing optionsm
Read register contents
Read register contents Change register contents Read register contents (FX1S and FX1N only)
Registers with externally modifiable contents The controllers of the FX1S and FX1N series have two integrated potentiometers with which you can adjust the contents of special registers D8030 and D8031 in the range from 0 to 255 (see Chapter 4.6.1). These potentiometers can be used for a variety of purposes – for example to adjust setpoint values for timers and counters without having to connect a programming unit to the controller.
4 – 10
MITSUBISHI ELECTRIC
Page 69
Devices in Detail
4.5.3
Programming Tips for Timers and Counters
File registers The contents of file registers are also not lost when the power supply is switched off. File registers can thus be used for storing values that you need to transfer to data registers when the PLC is switched on, so that they can be used by the program for calculations, comparisons or as setpoints for timers. File registers have the same structure as data registers. In fact, they are data registers – they consist of blocks of 500 addresses each in the range from D1000 to D7999. Device
File registers
Device identifier
D
Device type (for setting and polling)
Word device (two registers can be combined to store double-word values)
Possible device values
16 bit register: 0000H to FFFFH (-32768 to 32767) 32 bit register: 00000000H to FFFFFFFFH (-2 147 483 648 to 2 147 483 647)
Device address format
Decimal FX1S
Number of devices and addresses
1500 (D1000–D2499) A maximum of 3 blocks of 500 file registers each can be defined in the PLC parameters.
FX1N FX2N FX2NC
7000 (D1000–D7999) A maximum of 14 blocks of 500 file registers each can be defined in the PLC parameters.
FX3U
For a detailed description of the file registers see the Programming Manual for the MELSEC FX family.
4.6
Programming Tips for Timers and Counters
4.6.1
Specifying timer and counter setpoints indirectly The usual way to specify timer and counter setpoint values is directly, in an output instruction: Ladder Diagram
X17 0 M50 4
Instruction List
K500 T31 K34 C0
0 1 4 5
LD OUT LD OUT
X17 T31 M50 C0
K500 K34
In the example above T31 is a 100ms timer. The constant K500 sets the delay to 500 x 0.1s = 50s. The setpoint for counter C0 is also set directly, to a value of 34 with the constant K34. The advantage of specifying setpoints like this is that you don’t have to concern yourself with the setpoint value once you have set it. The values you use in the program are always valid, even after power failures and directly after switching the controller on. However, there is also a disadvantage: If you want to change the setpoint you need to edit the program. This applies particularly for timer setpoint values, which are often adjusted during controller configuration and program tests. You can also store setpoint values for timers and counters in data registers and have the program read them from the registers. It is then possible to change the values quickly with a pro-
FX Beginners Manual
4 – 11
Page 70
Programming Tips for Timers and Counters
Devices in Detail gramming unit if necessary, or to specify setpoint values with switches on a control console or a HMI control panel. The following listing shows an example of how to specify setpoint values indirectly: Instruction List
Ladder Diagram M15 0
MOV D100 D131
X17 6
D131 T31
M8002 10
MOV K34 D5
M50 16
0 1 6 7 10 11 16 17
LD MOV LD OUT LD MOV LD OUT
M15 D100 T31 M8002 K34 M50 C0
D131 X17 D131 D5 D5
D5 C0
–
When relay M15 is one the contents of data register D100 are copied to D131. This register contains the setpoint value for T131. You could use a programming or control unit to adjust the contents of D100.
–
The special relay M8002 is only set for a single program cycle directly after the PLC is switched on. This is used to copy the constant value of 34 to data register D5, which is then used as the setpoint value for counter C0.
You don’t have to write program instructions to copy the setpoint values to the data registers. You could also use a programming unit to set them before the program is started, for example.
E
WARNING: If you use normal registers the setpoint values will be lost when the power supply is switched off and when the RUN/STOP switch is set to the STOP position. If this happens hazardous conditions may be created next time the power is switched on and/or when the PLC is started again, because all the setpoints will have a value of “0”.
If you don’t configure your program to copy the values automatically you should always use latched data registers for storing the setpoint values for timers and counters. Also, remember that even the contents of these registers will also be lost when the PLC is switched off if the backup battery is empty.
4 – 12
MITSUBISHI ELECTRIC