Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 18 of 20

I/O Module Type Building Block User's Manual: 11. I/O MODULE TROUBLESHOOTING

Pages 134 to 141 of 158, from I/O Module Type Building Block User's Manual

The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi QG60 and Mitsubishi QX42

Page 134

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

11. I/O MODULE TROUBLESHOOTING This chapter explains possible problems with I/O circuits and their corrective actions.

11

11.1 Input Circuit Troubleshooting This section describes possible problems with input circuits and their corrective actions. Table 11.1 Input Circuit Problems and Corrective Actions Cause • Leakage current of input switch (e.g. drive by non-contact switch).

Corrective action Connect an appropriate resistor so that the voltage across the terminals of the input module will be less than the off voltage.

Example 3

Example 2

Example 1

Condition An input signal does not turn off.

An input signal does not turn off.

• Drive by a limit switch with neon lamp.

It is recommended to use 0.1 to 0.47 F + 47 to 120Ω (1/2W) for the CR constant. • Same as Example 1. • Or make up another independent display circuit.

An input signal does not turn off.

• Leakage current due to line capacity of wiring cable. (Line capacity C of twisted pair wire is approx. 100 pF/m).

• Same as Example 1. • However, leakage current is not generated when the power supply is located in the input equipment side as shown below.

(To the next page)

11 - 1

11 - 1

Page 135

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

Table 11.1 Input Circuit Problems and Corrective Actions (Continued) Condition

Cause

Corrective action

• Drive by switch with LED indicator.

Connect an appropriate resistor so that the current flow within the module will be less than the off current.

Example 4

An input signal does not turn off.

Example 5

An input signal does not turn off.

• Current flow in the opposite direction due to the use of two power supplies DC input

A calculation example of a value for a connected resistor is given on the following page. • Use only one power supply. • Connect a diode so that current flows only in one direction. (Figure below) DC input Diode

Input module

Lamp E2

E1

Input module

Lamp

E2

E1

Example 7

Example 6

E1>E2

An input signal does not turn on (AC input module).

Stepwise distortion as shown below appears to the zero cross voltage of input signal (AC).

False input due to noise

Noise has been taken as input data.

Improve input signal waveform by using the uninterruptible power system etc.

Zero cross voltage

Change the response time setting value.*1 Example 1ms 5ms If this action is not effective, take the following measures. • To prevent excessive noise, avoid installing power cables together with I/O cables. • Take noise reduction measures. (Example: Connect surge absorbers to noise-generating devices such as relays and contactors using the same power supply.)

*1: If excessive noise is periodically generated, setting a shorter response time value may be effective.

11 - 2

11 - 2

11

Page 136

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

<Calculation example of Example 4> Connecting a switch with LED display, in which a maximum 2.33mA leakage current flows when 24VDC is supplied to the QX40.

(1) In this case, the circuit does not satisfy the condition that the OFF current of the QX40 is 1.7mA or less. Connect a resistance as follows.

(2) In order to satisfy the condition that the OFF current of the QX40 is 1.7mA or less, the resistance R, in which a 0.63mA or more current flows, shall be connected. Calculating with the formula,

IR: IZ=Z (Input impedance): R R

IZ IR

Z (Input impedance) =

1.7 0.63

5.6=15.11[k ] the resistance R will be R<15.11kΩ. Consequently, if the resistance R is set to 12kΩ, the electric power W of the resistance R will be calculated in the following formula, W= (Input voltage)2/R=28.82/12000=0.069[W]. (3) Since the resistance requires the electric power which is 3 to 5 times of the power actually consumed, the resistance to be connected to the corresponding terminal shall be 12.0kΩ and 1/4 to 1[W]. (4) The OFF voltage of the QX40 when the resistance R calculated above is connected will be 8.90[V].

1 1 12.0[k ]

1 5.6[k ]

2.33[mA]=8.90[V]

This also satisfies the condition that the OFF voltage of the QX40 is 11V or less.

11 - 3

11 - 3

Page 137

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

11.2 Output Circuit Troubleshooting This section describes possible problems with output circuits and their corrective actions. Table 11.2 Output Circuit Problems and Corrective Actions Condition

Cause

Corrective action

When the

• Load is half-wave rectified inside (in some

• Connect a resistor several tens to hundreds of output is cases, this is true of a solenoid).

kΩ across the load.

off, excessive voltage is

QY22 Output module applied to

[1]

Resistor

Load

Load the load. Example 1

D1

[2]

• When the polarity of the power supply is as shown in [1], C is charged. When the polarity is as shown in [2], the voltage charged in C plus the line voltage are applied across D1. Max. voltage is approx. 2.2E. (If a circuit is used in this way, it does not pose a problem to the output element. But it may cause the diode, which is built into the load, to deteriorate, resulting in a fire, etc.) The load

• Leakage current due to built-in surge

• Connect a resistor across the load.

does not suppressor.

(When the wiring distance from the output

Example 2 turn off. (triac output)

module to the load is long, there may be a QY22 Output module leakage current due to the line capacity.) Load Resistor

Leakage current

Load

(To the next page)

11 - 4

11 - 4

Page 138

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

Table 11.2 Output Circuit Problems and Corrective Actions (Continued) Condition

Example 3

The load does not turn off. (triac output)

Cause

Corrective action

• If the load current is insufficient (lower than 25mA), the triac does not operate, causing the load current to flow into a phototriac as shown below. If an inductive load is connected in this condition, the load may not turn off because surge at the time of off is applied to the phototriac.

• Connect a resistor to both ends of the load so that the load current of approx. 100mA flows and the triac operation is stable. Resistance value ≤ Voltage across the load / 100mA Resistor

Load Surge suppressor

QY22

Phototriac

Control circuit

Load

(Example) When using 100VAC (output voltage), for instance, calculate the resistance value from the formula below. 100VAC / 100mA = 1kΩ Resistance value = 1kΩ

Triac

(To the next page)

11 - 5

11 - 5

Page 139

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

Table 11.2 Output Circuit Problems and Corrective Actions (Continued) Condition When the external power supply turns on, the load turns on for a moment. (transistor output)

Cause

Corrective action

Erroneous output due to the stray capacitance (C) between collector and emitter of photocoupler. There is no erroneous output at normal load. An erroneous output may occur at high sensitivity load (such as solid state relay)

(1) To turn on or off the external power supply, check that the external power supply rising edge must be 10ms or more, and switch the SW1 to the primary side of external power supply.

(2) When switching to the secondary side of the external power supply is required, the external power supply rising edge connected a condenser and a resistor must be slow, and measured 10ms or more. Sink output

Source output

Example 4

(1) If the external power supply is turned on precipitously, Ic current flows due to the stray capacitance (C) between collector and emitter of photocoupler. (2) Ic current flows to the next stage of transistor Tr1 gate and Y0 output turns on by 100 s.

SW: External power supply (24V) at On 10ms or less

Output Y0 Approx.100 s

* The measures are ineffective in the following modules due to the characteristic of the external power supply circuit QY81P QY82P R1: Several tens of ohms Power capacity (external power supply current*1)2 resistance value (3 to 5)*2 C1: several hundreds of microfarads 50V *1 Refer to current consumption of the external power supply for modules used in this manual. *2 Select the power capacity of resistance to be 3 to 5 times larger than the actual power consumption. (Example) R1=40Ω, C1=300 F Use the below expression to calculate a time constant C1 R1=300 10-6 40 =12 10-3s=12ms

(To the next page) 11 - 6

11 - 6

Page 140

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

Table 11.2 Output Circuit Problems and Corrective Actions (Continued) Condition

Cause

Corrective action

The load momentarily turns on when the system is powered off (transistor output).

If an inductive load is connected, the load may turn on from off ([2]) due to back electromotive force at the time of power-off ([1]).

Take one of the following actions. (1) To suppress back electromotive force, connect a diode in parallel with the load where the back electromotive force has been generated. Source output [3]

Sink output [3]

Example 5

(2) Configure another current path by connecting a diode across positive and negative of the external power supply. When the corrective action described in the example 4 is taken at the same time, connect a diode in parallel with C1 and R1.

* The measures are ineffective in the following modules due to the characteristic of the external power supply circuit QY81P QY82P

D1: Reverse voltage VR(VRM) *1, Forward current IF(IFM) *2 *1 Approximately 10 times higher than the rated voltage in the specifications Example: 24 VDC Approximately 200V *2 Two times or more as much as the maximum load current (common) in the specifications Example: 2A/1 common 4A or more

(To the next page) 11 - 7

11 - 7

Page 141

11 I/O MODULE TROUBLESHOOTING

MELSEC-Q

Example 6

Table 11.2 Output Circuit Problems and Corrective Actions (Continued) Condition

Cause

Corrective action

The load operates only by powering on the external power supply. (transistor output)

The polarity to connect the external power supply is reverse. Transistor output module

Connect the external power supply with correct polarity.

Load Y0

Incorrect

Correct

External power supply COM Output element protection diode

If the external power supply is connected with wrong polarity, current may flow across an output element protection diode to the load. If the wire connecting 0V of an external power supply and a common of a load is cut off or disconnected, a current flows to the load that is off due to a parasitic circuit of the output element that is off.

Connect the external power supply and loads correctly. To prevent the condition described on the left, connect a diode to each output terminal as shown below.

Example 7

When an output is turned on, a load connected to the other output is also turned on. (transistor output (source type))

If a current keeps flowing under the above condition, a failure may occur.

11 - 8

11 - 8