Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 1 of 1

B824-016/24 VDC, 16 Point, Output Module (True High) Installation Instructions, pages 1 to 5

Pages 1 to 5 of 5

The original document is the PDF (155 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B824, AEG B824, Gould B824 and Schneider B824

Page 1 read from a scan by OCR; it may hold reading errors

B824-016/24 VDC, 16 Point, Output Module (True High) Installation Instructions

PI-B824 - 001 Rev. E aeeegeny wratnidgcessssye:

Lae tte Shhh fs ,

PTIITTER Ge: eae seteany | Tt? <a ae cael weeme- phi. SEEN iiss

Witiacezzeutll raped .

¥ ai a x ie nm

Page 2 read from a scan by OCR; it may hold reading errors

2 i aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaacaaaaamaaammmmmaaiaaa

« Sixteen independent 24 VDC outputs per module, _

« 2 Amperes per output * Circuit isolation of 1500 VAC/2500 VDC

2S |||

¢ True High operation e Field-side status indicators

¢ Front panel ACTIVE lamp e Transient protection

¢ Communication failures automatically detected e Designed for harsh industrial environments e Safe, non-conductive module front permits easy access for test probes

General Description

The MODICON B824-016, 24 VDC True High Output Module consists of sixteen independent outputs divided into two groups of eight.

The B824-016, 24 VDC True High Output Module converts signals used within the programmable controller into sixteen independent outputs. Outputs are capable of driving motor starters, relays, and a variety of other loads. Sixteen transistor switches are used to control loads connected to an external power source.

The module’s sixteen outputs are in two groups, eight outputs per group. Each group is fused to protect the outputs from overload currents and polarity reversal. An optical coupler isolates each output from the controller. The outputs are designed to withstand the extreme voltage transients often encountered in an industrial environment.

Field-side LED’s display each output’s on/off state. The ACTIVE lamp is lit as long as communication exists between the controller and module. If communication fails, the ACTIVE lamp and ail outputs go off within 300 milliseconds of the failure.

im mn

Page 3 read from a scan by OCR; it may hold reading errors

Figure 1-1

Key Pin Locations

Top

Bottom

Figure 1-2

Simplified Schematic

The B824 can be inserted into any location in the MODICON 800 Series I/O Housing. The module slides easily into the housing and does not interfere with any other module. An optional mechanical keying system can be used to match the module type with a particular slot in the housing. This ensures proper module placement. User connections are made to a standard screw terminal strip. The wiring system permits the module insertion or removal without disturbing the field wiring.

The module’s protective case shields logic circuitry from electrical interference and minimizes the possibility of noise being coupled from the user side of the circuitry to adjacent modules. The housing’s backplane provides an earth ground when the module is inserted into the housing.

When facing housing, place the knurled end of the key pins into the holes indicated by the ‘‘X’’. Use a 1/2” plastic head mallet or equivalent to drive the pin into the housing approximately 1/4 of an inch.

NOTE The keying system is optional.

3 *

OPTICAL ISCLATOR |

C ]

»

\

; OUTPUT STATUS INDICATOR a < COMMON

Perea SCHEER I SER TS LS A Ug RG 7

Page 4 read from a scan by OCR; it may hold reading errors

FUNCTION TERMINAL

|

Terminal Numbering and input Connectors, OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7, OUTPUT 8 COMMON (GROUP 1) 24 VDC SUPPLY, OUTPUT 9 OUTPUT 10 OUTPUT 11 OUTPUT 12 OUTPUT 13 OUTPUT 14 OUTPUT 15 _ OUTPUT 16 COMMON {GROUP 2) 24 VDC SUPPLY

SOL

LT \ | WY

GROUP 1 OUTPUTS, =

(|

SOL

LT N |

GROUP 2 OUTPUTS™

{il

I©@@OGOOOOOQOOOOOOOOO

Specifications

Electrical Characteristics Working Voltage 20 to 28 VDC On State Voltage Drop 1.8 VDC at 2 Amperes.

Maximum Module 12 Amperes per module, 6 Amperes per Output group

Maximum Load Current 2 Amperes per output, continuous.

Maximum Surge Current 5 Amperes per output for 10 ms.

Page 5 read from a scan by OCR; it may hold reading errors

Specifications (continued)

9

Electrical Characteristics (continued)

Off State Leakage 1 mA max.

Current

Power Supply Unit +5VDC, -5VDC +4.3VDC Loads 1.6(32mA) O(OmA) 1.2(260mA)

External Power Supply 24 VDC, +4V at 175 mA.

Circuit Characteristics

Topology 16 outputs per module divided into two groups of eight. Isolation Voltage 1500 VAC RMS at 60 Hz. for 60 seconds; 1. Between output 2500 VDC for 60 seconds. groups.

2. Between outputs and controller.

3. Between outputs and cover.

Response Time Off to On, 1 ms max. On to Off, 1 ms max.

Front Panel Indicators One field-side LED per output: illuminates when output is on. One ACTIVE LED: illuminates as long as communication exists between the controller and module.

Fuses One 8 Ampere fuse per group.

Environment

Temperature Operating 0 to 60°C, 20 to 80°C

Storage

Humidity 0 to 95% non-condensing.

Shock 10 G for 11 ms.

Vibration 0.625 G, 50-500 Hz.

Dimensions 2.1 in. x 10.47 in. x 8.25 in.

(W x H x D) (53.3 mm x 265.9 mm x 209.6 mm)

NOTE The B824-016, 24 VDC True High Output Module ts compatible with the B825-016, 24 VDC True High Input Module.

Perea SCHEER I SER TS LS A Ug RG 7