Page 1 of B824-016/24 VDC, 16 Point, Output Module (True High) Installation Instructions

Manual · Modicon

B824-016/24 VDC, 16 Point, Output Module (True High) Installation Instructions

Manual5 pagesPDF 155 KB

Installation instructions for the Modicon B824-016 24 VDC, 16-point True High output module for the 800 Series I/O housing.

Download the PDF155 KB

Covers · 4 models

The models it covers

Summary

What is in it

Modicon installation instructions for the B824-016 24 VDC True High output module, which has sixteen independent outputs in two groups of eight for driving motor starters, relays and other loads. It gives the feature list and general description, optional key pin locations for the 800 Series I/O housing, a simplified schematic, terminal numbering and connections, and electrical, circuit and environmental specifications.

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Installation instructions for the Modicon B824-016, a 16-point 24 VDC true high output module for the Modicon 800 Series I/O housing. It describes the module, optional keying and insertion, terminal wiring, and the electrical and environmental specifications.

Device
24 VDC true high output module, 16 points, for the Modicon 800 Series I/O housing p. 2, 3
Outputs
16 transistor outputs in two groups of eight, 2 Amperes each continuous p. 2, 4
Working voltage
20 to 28 VDC p. 4
Module current
12 Amperes per module, 6 Amperes per group p. 4
Surge current
5 Amperes per output for 10 ms p. 4
On and off state
1.8 VDC drop at 2 Amperes; off-state leakage 1 mA max p. 4, 5
Response time
1 ms max off to on and on to off p. 5
Fuses
One 8 Ampere fuse per group p. 5
Isolation
1500 VAC RMS at 60 Hz or 2500 VDC for 60 seconds, between groups, outputs and controller, outputs and cover p. 5
External supply
24 VDC at 175 mA p. 5
Indicators
One field-side LED per output; ACTIVE LED lit while the controller and module communicate p. 5
Environment
0 to 60°C operating, -20 to 80°C storage, 0 to 95% humidity non-condensing p. 5
Dimensions
53.3 x 265.9 x 209.6 mm (W x H x D); 2.1 x 10.47 x 8.25 in. p. 5
Matching input module
B825-016, 24 VDC True High Input Module p. 5

What this manual walks you through

  • Inserting the module in the 800 Series I/O housing p. 3
  • Fitting the optional keying pins p. 3
  • Terminal numbering and wiring of outputs, commons and 24 VDC supply p. 4
  • Reading the output LEDs and ACTIVE lamp p. 2

Good to know

  • If communication with the controller fails, the ACTIVE lamp and all outputs go off within 300 milliseconds. p. 2
  • Each group of eight outputs is fused against overload currents and polarity reversal. p. 2
  • The module can be inserted or removed without disturbing the field wiring; the keying system is optional. p. 3

Questions this manual answers

How much current can each Modicon B824 output carry?

2 Amperes continuous per output, 6 Amperes per group and 12 Amperes per module, with surges of 5 Amperes for 10 ms. p. 4

What happens to the B824 outputs if communication fails?

The ACTIVE lamp and all outputs go off within 300 milliseconds of the failure. p. 2

Which input module is compatible with the B824?

The B825-016, 24 VDC True High Input Module. p. 5

What fuses does the B824 use?

One 8 Ampere fuse per group of eight outputs. p. 5

What voltage range can the B824 outputs switch?

A working voltage of 20 to 28 VDC. p. 4

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 51-5

The file

Revision and size

RevisionPI-B824-001 Rev. E
PublisherModicon
Pages5
PDF155 KB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.

The first pages · 3 of 5

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 5
Page 2
Page 2of 5
Page 3
Page 3of 5

More documents · 1

For the same models