Modicon installation instructions for the B824-016 24 VDC True High output module, which has sixteen independent outputs in two groups of eight for driving motor starters, relays and other loads. It gives the feature list and general description, optional key pin locations for the 800 Series I/O housing, a simplified schematic, terminal numbering and connections, and electrical, circuit and environmental specifications.
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Installation instructions for the Modicon B824-016, a 16-point 24 VDC true high output module for the Modicon 800 Series I/O housing. It describes the module, optional keying and insertion, terminal wiring, and the electrical and environmental specifications.
- Device
- 24 VDC true high output module, 16 points, for the Modicon 800 Series I/O housing p. 2, 3
- Outputs
- 16 transistor outputs in two groups of eight, 2 Amperes each continuous p. 2, 4
- Working voltage
- 20 to 28 VDC p. 4
- Module current
- 12 Amperes per module, 6 Amperes per group p. 4
- Surge current
- 5 Amperes per output for 10 ms p. 4
- On and off state
- 1.8 VDC drop at 2 Amperes; off-state leakage 1 mA max p. 4, 5
- Response time
- 1 ms max off to on and on to off p. 5
- Fuses
- One 8 Ampere fuse per group p. 5
- Isolation
- 1500 VAC RMS at 60 Hz or 2500 VDC for 60 seconds, between groups, outputs and controller, outputs and cover p. 5
- External supply
- 24 VDC at 175 mA p. 5
- Indicators
- One field-side LED per output; ACTIVE LED lit while the controller and module communicate p. 5
- Environment
- 0 to 60°C operating, -20 to 80°C storage, 0 to 95% humidity non-condensing p. 5
- Dimensions
- 53.3 x 265.9 x 209.6 mm (W x H x D); 2.1 x 10.47 x 8.25 in. p. 5
- Matching input module
- B825-016, 24 VDC True High Input Module p. 5
What this manual walks you through
- Inserting the module in the 800 Series I/O housing p. 3
- Fitting the optional keying pins p. 3
- Terminal numbering and wiring of outputs, commons and 24 VDC supply p. 4
- Reading the output LEDs and ACTIVE lamp p. 2
Good to know
- If communication with the controller fails, the ACTIVE lamp and all outputs go off within 300 milliseconds. p. 2
- Each group of eight outputs is fused against overload currents and polarity reversal. p. 2
- The module can be inserted or removed without disturbing the field wiring; the keying system is optional. p. 3
Questions this manual answers
How much current can each Modicon B824 output carry?
2 Amperes continuous per output, 6 Amperes per group and 12 Amperes per module, with surges of 5 Amperes for 10 ms. p. 4
What happens to the B824 outputs if communication fails?
The ACTIVE lamp and all outputs go off within 300 milliseconds of the failure. p. 2
Which input module is compatible with the B824?
The B825-016, 24 VDC True High Input Module. p. 5
What fuses does the B824 use?
One 8 Ampere fuse per group of eight outputs. p. 5
What voltage range can the B824 outputs switch?
A working voltage of 20 to 28 VDC. p. 4