Manual · AEG
Modicon 800 Series Discrete I/O Modules User Guide
Manual241 pagesPDF 12 MB
User guide for the Modicon 800 Series discrete I/O modules (B802 through B882), with wiring and specifications for each module.
Covers · 29 models
The models it covers
Summary
What is in it
User guide for the Modicon 800 Series discrete I/O modules used with 984 controllers. A general chapter covers the system interface, I/O map configuration, grounding, installation, a quick start test and generic specifications. Each following chapter covers one module, such as the B804-116 115 Vac output, B805-016 and B807-132 115 Vac inputs, B814-108 relay output, B824-016 and B825-016 24 Vdc modules, B828-016 5 V TTL output and B865-001 register input, with a schematic, field connections and specifications.
Its parts
- 800 Series I/O Modules
- B802-008 115 Vac Output
- B803-008 115 Vac Input
- B804-116 115 Vac Output
- B804-148 48 Vac Output
- B805-016 115 Vac Input
- B806-032 115 Vac Output
- B806-124 24 Vac Output
- B807-132 115 Vac Input
- B808-016 230 Vac Output
- B809-016 230 Vac Input
- B810-008 115 Vac Isolated Output
- B814-108 Relay Output
- B817-116 and B817-216 115/230 Vac Isolated Input
- B820-008 10 ... 60 Vdc Output (True High)
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
The Modicon 800 Series Discrete I/O Modules User Guide (GM-DISC-800 Rev. C, AEG Schneider Automation, April 1995). It covers the whole 800 Series discrete line, including the B802-008, B803-008, B804-116, B804-148, B805-016, B807-132, B814-108, B824-016, B825-016, B828-016 and B865-001 modules, each with its own chapter. It explains installation, field wiring, I/O mapping, a quick start test and the specifications of each module.
- Document
- Modicon 800 Series Discrete I/O Modules User Guide, GM-DISC-800 Rev. C, April 1995 p. 2
- Operating temperature
- 0 to 60°C (32 to 140°F) p. 26
- Size and weight
- 2.0 x 10.5 x 8.0 in (50.8 x 266.7 x 203.2 mm), 2.4 lbs (1.1 kg), one I/O slot p. 26
- Field connectors
- AS-8534-000 low density or AS-8535-000 high density, per module p. 25
- Loss of communication
- All I/O points shut off within 300 ms of losing communication with the controller p. 17
- Isolation
- Each point optically isolated from the controller; field to system 2000 VAC for 1 min p. 17, 26
- B807-132 input
- 32 points of 115 Vac input in 4 groups of 8; 80 to 130 Vac, 47 to 63 Hz; connector AS-8535-000 p. 60
- B804-116 output
- 16 triac outputs at 115 Vac, up to 2.0 A per point, 6 A per group of eight, 12 A per module p. 36
- B805-016 input
- 16 inputs at 115 Vac in 2 groups of 8; 6 mA typical ON current at 115 Vac p. 44, 46
- B814-108 relays
- 8 isolated relay outputs, NO or NC; 5 A at 30 Vdc/120 Vac, 4 A at 240 Vac; one 7 A fuse per output p. 77
- B824-016 output
- 16 true high 24 Vdc transistor outputs in 2 groups of 8, 2 A per point, one 8 A fuse per group p. 93, 95
- B825-016 input
- 16 true high 24 Vdc inputs in one group; ON above 21 Vdc or 0.75 of the field supply, whichever is less p. 97, 99
- B828-016 output
- 16 sinking 5 V TTL outputs, up to 75 mA each, from an external 5 Vdc supply p. 110
- B865-001 register input
- 8 channels of 16-bit register input, BCD or binary, 5 V TTL or CMOS; connector AS-8535-000 p. 187, 192
What this manual walks you through
- Installing a module in the 800 Series housing p. 21, 22, 23, 24
- Keying a housing slot with key pins p. 23
- Running the quick start test p. 25
- Setting up the I/O Map for a 984 controller p. 19
- Grounding the housing and shielded field wiring p. 20
- Reading the status indicators p. 18
- Setting B814-108 relay channels for normally open or normally closed p. 75
- Setting the B865-001 polarity and BCD/binary switches p. 189
- Wiring B865-001 strobe pull-up resistors p. 190, 191
- B807-132 input current versus line frequency p. 59
Good to know
- On the B807-132, proximity switches are recommended only at 60 Hz, and leakage through switching devices may cause a false ON. p. 58
- The Active indicator does not show the condition of the individual I/O points. p. 18
- Do not ground a field wiring shield at both the module and the field device. p. 20
- On the B814-108, the maximum load at 48 Vdc is 1 A. p. 77
- B865-001 strobe lines are true low, the opposite of other Modicon I/O modules, so diode polarity may need reversing. p. 191
Questions this manual answers
How many inputs does the B807 have?
The B807-132 has 32 inputs at 115 Vac, in four groups of eight. p. 57, 60
Which terminal connector does the B807 use?
The B807-132 uses the AS-8535-000 terminal connector. p. 60
What is the B807 response time?
6 ms maximum from OFF to ON and 35 ms maximum from ON to OFF. p. 60
What happens to 800 Series I/O if communication with the PLC is lost?
All I/O points shut off within 300 ms and the Active indicator goes off. p. 17
How do I set a B814-108 relay output to normally closed?
The module ships with all eight channels jumpered normally open; move the wire jumper to the NC tab shown in the manual's table for that channel. p. 75
The whole text · 25 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 101-10
- Pages 11 to 2011-20
- Pages 21 to 3021-30
- Pages 31 to 4031-40
- Pages 41 to 5041-50
- Pages 51 to 6051-60
- Pages 61 to 7061-70
- Pages 71 to 8071-80
- Pages 81 to 9081-90
- Pages 91 to 10091-100
- Pages 101 to 110101-110
- Pages 111 to 120111-120
- Pages 121 to 130121-130
- Pages 131 to 140131-140
- Pages 141 to 150141-150
- Pages 151 to 160151-160
- Pages 161 to 170161-170
- Pages 171 to 180171-180
- Pages 181 to 190181-190
- Pages 191 to 200191-200
- Pages 201 to 210201-210
- Pages 211 to 220211-220
- Pages 221 to 230221-230
- Pages 231 to 240231-240
- Page 241241
The file