The text of a manual · part 22 of 25
Modicon 800 Series Discrete I/O Modules User Guide, pages 211 to 220
Pages 211 to 220 of 241
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B804, Modicon B805, Modicon B807, Modicon B824, Modicon B825, Modicon B828, Modicon B865, AEG B804, and 21 more models
Page 211
38.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
38.3.1
Output Connections
Figure 92 B881--508 Terminal Numbering
Caution: This module does not provide reverse voltage protection. Check for proper voltage polarity of output wiring.
GM--DISC--800
B881--508 125 Vdc Output
209
Page 212
38.4 Specifications B881--508 Specifications Description
125 Vdc true high output
Number of Points
8
Operating Voltage
5 ... 140 Vdc maximum
Number of Groups
8
Outputs/group
1
Maximum Load Current
5.0 A continuous/channel maximum @ 25°C derated by 0.03 A/°C ... 4.0 A continuous per channel maximum @ 60°C 29.0 A/ module maximum
Pulsed ON Cycle
500 ms maximum for 5 ... 30 A load
Inductance and Maximum Current/Channel
I2L < 25 W* I2LF < 0.5 W**
Wattage
< 24 W, 2.5 W/point maximum
Surge Current
30.0 A 1 cycle (500 ms)/channel maximum
Minimum Load Current
75 mA
Maximum Response Time
OFF ® ON
< 75 ms
ON ® OFF
< 100 ms
Maximum Off State Leakage Current
< 3 mA
On State Voltage Drop Across Module
< 0.75 Vdc @ 4 A Load Current
External Inputs
Response Time
75 mS
Working Voltage Range
19.2 ... 28 Vdc
Maximum Input Range
30 Vdc
Mode of Operation
True High
+5 V
300 mA
+4.3 V
0 mA
--5 V
0 mA
Power Required
External Power Supply
5 ... 140 Vdc field power supply
Terminal Connector
AS--8535--000
*Typical values of Relay Inductance and currents that can be switched safely at 1 s rates using this formula. **For repetitive pulses, use this formula.
Note: Proper fusing of external circuits is required dependant on application.
210 B881--508 125 Vdc Output
GM--DISC--800
Page 213
Chapter 39 B882--032 24 Vdc Diagnostic Output
GM--DISC--800
V
Overview
V
Fault Conditions
V
Field Connections
V
DIP Switch Settings
V
Quick Start Test
V
Application Example
V
Specifications
B882--032 24 Vdc Diagnostic Output
211
Page 214
39.1 Overview The B882- -032 Diagnostic Output Module (B882) serves 32 points that make up four groups of eight outputs. Each group of eight outputs shares an external power supply voltage. The outputs work over the range of 20.0 ... 28.0 Vdc, true high. It is capable of driving 24 Vdc relays, solenoids, pilot lamps, and other loads rated up to 1.0 A. The B882 module also detects field fault conditions and turns the faulted point OFF for vital applications. The B882 Diagnostic dc Output module can detect open load, over current, over voltage, and over temperature conditions.
39.1.1
Simplified Schematic dc POWER dc RETURN
Figure 93 B882--032 Simplified Schematic
You can select the functionality of the Diagnostic dc Output Module. It can be a bi- -directional module (B882) whereby you have 32 discrete outputs and 32 discrete inputs which are fault flags for each respective output. It can also be a uni- -directional module (B818) having 32 discrete outputs without fault flags.
212 B882--032 24 Vdc Diagnostic Output
GM--DISC--800
Page 215
39.2 Fault Conditions Open load, over current, over voltage and over temperature fault conditions are detected by the Diagnostic Output Module.
39.2.1
B882 Mode In the B882 mode when an output fault is detected, the module without controller intervention disarms the faulted output and reports the condition to the controller via discrete input (1x), or input register (3x) points. The point remains disarmed until the user’s logic rearms the point by turning the point back on. To turn the point back on the user’s logic must turn the point off and back on. Note: If the controller attempts to turn a faulted point back on, there must be a 2 ... 5 s delay from the time of a fault to the time of cycling the faulted point on. When this delay is not given, the module ignores the change. When you bring the faulted point low, the fault indicator clears in the 2 ... 5 s. Note: If field power is lost, the module may detect faults. After you re- -apply field power, you must clear all faults. Caution: When a fault is detected, in B882 or B818 mode, the source of the fault should be cleared prior to you restarting the point. Failure to do so may result in damage to the power source, the driven field side device, and eventually the module itself.
39.2.2
B818 Mode In the B818 mode when an output fault is detected, the module without controller intervention disarms the faulted output. Faults are not reported to the controller. To turn the point back on the user’s logic must turn the point off and back on. Note: If the controller attempts to turn a faulted point back on, there must be a 2 ... 5 s delay from the time of a fault to the time of cycling the faulted point on. When this delay is not given, the module ignores the change. When you bring the faulted point low, the fault indicator clears in the 2 ... 5 s.
GM--DISC--800
B882--032 24 Vdc Diagnostic Output
213
Page 216
Caution: If field power is lost, in the B818 mode, the module may detect faults that are not visible to the controller. After you re- -apply field power, you must turn your points OFF then back ON for all ON states.
39.2.3 Open Load
Fault Definitions When the load current is less than, or equal to 100 mA, the output is turned OFF and the fault flag is set. To prevent the fault flag from being set you should place a resistor between the output point and the group return. For example, @ 20 Vdc the minimum load is 200 W, @ 24 Vdc the minimum load is 240 W, and @ 28 Vdc the minimum load is 280 W. When the output is already on and the load exceeds the open load trip level for one to one and a half ms, the output is turned OFF, and the fault flag is set.
Over Current
When the load current exceeds the over current trip level following the switching of a point from off to on, the output is turned OFF, and the fault flag is set. When the output is already on and the current exceeds the over current trip level for one to one and a half ms, the output is turned OFF, and the fault flag is set. Note: The over current trip level has a value of 3.5 A or greater. Over current greater than 12 A may cause point failure.
Over Voltage
If the external voltage supply exceeds the modules rating, the output point turns OFF, and a fault flag may be returned. The point requires cycling, after the external supply returns to the safe operating level. The over voltage trip level has a value of greater than 31 Vdc. There is no time delay.
Over Temperature When the junction temperature of the output transistor reaches 140°C or greater, the output is turned OFF, and the fault flag is set. Caution: Be careful when using the B882. Unused outputs should not be turned ON since their field points are not wired. Turning them ON will cause an open load fault and the active light will blink. The minimum load required is 100 mA.
214 B882--032 24 Vdc Diagnostic Output
GM--DISC--800
Page 217
39.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring. Setting the DIP- -switch allows you to select bi- -directional fault reporting or uni- -directional non- -fault reporting functionality prior to installation. Terminal numbering and their corresponding output functions are presented below in Figure 94.
+24 Vdc
+24 Vdc
--24 Vdc
--24 Vdc
+24 Vdc
+24 Vdc
--24 Vdc
--24 Vdc
Figure 94 B882--032 Terminal Numbering and Output Connections
GM--DISC--800
B882--032 24 Vdc Diagnostic Output
215
Page 218
39.4 DIP Switch Settings The four-position DIP switch is located on the rear of the module. This switch controls the functionality of the module (bi- -directional or uni- -directional). Set switch SW3 for either (B882) bi- -directional fault reporting, or (B818) uni- -directional non- -fault reporting. Refer to Figure 95 for switch settings. Also, refer to the label located on the left side of the module itself. 4--POSITION DIP-- SWITCH TOP OF MODULE
0 ON DOWN LEFT
1 OFF UP RIGHT
SWITCHES 1 and 2
FUNCTIONS NOT USED, KEEP TO LEFT
3
MODULE FUNCTIONALITY FOR BI--DIRECTIONAL SW3 = R (B882) FOR UNI--DIRCTIONAL SW3 = L (B818)
4
NOT USED, KEEP TO LEFT
Figure 95 B882--032 DIP Switch Settings
Note: When you select the bi- -directional module functionality (B882), you have 32 discrete outputs and 32 returned fault flags. When you select the uni- -directional module functionality (B818), you have 32 discrete outputs.
216 B882--032 24 Vdc Diagnostic Output
GM--DISC--800
Page 219
39.5 Quick Start Test This test configures the module as follows: B882 (bi- -directional). Step 1
Set the 4 position DIP- -Switch as follows: (viewing the rear of the module when held vertically) SW1 and SW2
Left
Not Used (keep to left)
SW3
Right
Selects B882 (bi--directional)
SW4
Left
Not Used (keep to left)
Step 2
Determine which channel and slot location are being used for this module.
Step 3
Wire terminals 5,15, 25, 35 to a +24 Vdc Supply, and wire terminals 6, 16, 26, 36 to a - -24 Vdc Supply on a AS- -8535- -000 high density connector. Note: Remove the keying tabs on the AS- -8535- -000 high density connector prior to installing module.
Step 4
Stop the PLC.
Step 5
I/O Map the module as a B882, registers 30001/30002, 40001/40002 binary.
Step 6
Start the PLC.
Step 7
Write FFFF(hex) into registers 40001 and 40002. Note: Ensure that no field devices are connected to these points.
GM--DISC--800
Step 8
Active light should now be blinking.
Step 9
Look at registers 30001 and 30002 in binary format, all bits should be set to a one indicating a returned fault. The fault is present as a result of the open load condition of the outputs. The module is correctly monitoring its output points and is being read properly by the controller.
B882--032 24 Vdc Diagnostic Output
217
Page 220
Note: Active blinking = One or more outputs have sensed a load fault. Active on steady = Points have the minimum load requirements.
39.5.1
Application Example The B882 module, with ability to sense its own output points is an excellent choice for critical operations. The example in Figure 96 shows ladder logic that allows for detection of point errors. This could ultimately be used to control a system if a critical failure occurred. The Block Move shown in Figure 96 moves the contents of registers 30001 and 30002 into 40008 and 40009 where they can be worked. The XOR Block Exclusively OR’s the contents of 40001 and 40002 with 40008 and 40009 then places the results of this XOR in 40008 and 40009. This gives you a value that can be used in the Compare Block, that compares the contents of 40001 and 40002 to the values in 40008 and 40009, and when a miscompare occurs, coil 00001 turns on which can be tied to an indicator light, or safety circuity for system protection. 30001
40001
40001
40008
40008
40007
BLKM 2
XOR 2
CMPR 2
00001
00001 = MISCOMPARE OR FAULT HAS OCCURRED 30001 & 40001 = ASSIGNED IN TRAFFIC COP 40007 = POINTER FOR COMPARE BLOCK -- THE POINTER CONTAINS THE LOCATION OF THE FIRST ERROR BIT SET IN THE FAULT REGISTER 40008 & 40009 = EXCLUSIVE OR REGISTER VALUE Figure 96 B882--032 Application Example
218 B882--032 24 Vdc Diagnostic Output
GM--DISC--800