The text of a manual · part 21 of 25
Modicon 800 Series Discrete I/O Modules User Guide, pages 201 to 210
Pages 201 to 210 of 241
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B804, Modicon B805, Modicon B807, Modicon B824, Modicon B825, Modicon B828, Modicon B865, AEG B804, and 21 more models
Page 201
37.1.1
Simplified Schematic
VARISTER
1CPL3700
Figure 86 B881--108 Simplified Schematic
198 B881--108 Protected 120 Vac Output
GM--DISC--800
Page 202
37.2 Using the Fault Condition Filter You can remove any false or nuisance faults by using a fault condition filter. With the B881- -108, you can choose a 64 ms filter, or a 128 ms filter based on your needs. Refer to Figure 87 for fault filter selection DIP switch settings. The filtered fault is sent to the PLC only when the detected fault exists for more than the selected filter time. Once reported, if output status is on when off is desired, the module turns OFF the faulted point by blowing the point’s fuse. For example, if you use a 64 ms filter and point number two is faulted for more than 64 ms, the fault is sent to the PLC and the module turns OFF point number two by blowing its fuse. To replace blown fuses slide the left side of the module towards the rear of the module. If the output is faulted ON it will blow the fuse. If the output is faulted OFF the module reports its condition but does not blow the fuse. 4--POSITION DIP--SWITCH TOP OF MODULE WHERE:
SWITCHES 1
FUNCTIONS FAULT FILTER SELECTION FOR 64ms FILTER: SW1=L
0 ON DOWN LEFT
1 OFF UP RIGHT
FOR 128 ms FILTER: SW1=R 2,3, AND 4 NOT USED, KEEP TO LEFT
Figure 87 B881--108 DIP--Switch Settings
GM--DISC--800
B881--108 Protected 120 Vac Output
199
Page 203
37.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
37.3.1
Output Connections
Figure 88 B881--108 Terminal Numbering
You can wire the points individually or as a group, because each output is isolated. Individual points are not isolated when wired as a group.
200 B881--108 Protected 120 Vac Output
GM--DISC--800
Page 204
37.4 Quick Start Test This test configures the module as follows: B881 (bi- -directional), and a 64 ms filter. Step 1
Set the four-position DIP switch as follows: (viewing the rear of the module when held vertically): SW1 SW2, 3, and 4
Step 2
Left Left
Selects a 64 ms Filter Not Used (keep to left)
Wire field neutral to terminal 4 (CH1 NEUTRAL) to one side of the field device, wire other side of field device to terminal 6 (CH1 LOAD), then wire your 115 Vac field hot to terminal (CH1 HOT) on a AS- -8535- -000 high density connector. Note: Remove the keying tabs on the AS- -8535- -000 high density connector prior to installing module.
Step 3
Stop the PLC.
Step 4
Determine which channel and slot location are being used for this module and insert the module.
Step 5
I/O Map the module as a B881, inputs 10001 ... 10016, outputs 0001 ... 00016. Note: The B881 is a bi- -directional module that provides eight discrete outputs, and eight discrete inputs. However, the B881 is identified in the I/O Map as a 16 point bi- -directional module, and is allocated 16 discrete inputs and 16 discrete outputs. The B881 uses only the lower order eight input and output points, the higher order of eight inputs and outputs can not be used anywhere.
GM--DISC--800
Step 6
Start the PLC.
Step 7
Confirm that the module’s active light is illuminated.
B881--108 Protected 120 Vac Output
201
Page 205
Active ON OK steady = Active Blinking = An output has an unclear fault detected (output is logically ON, but power is not available at input/output point) Active OFF = Failed diagnostics, loss of internal power, or loss of communication with PLC
Step 8
Apply 115 Vac to channel 1 hot (CH1), and confirm that the red output light is illuminated after turning channel 1 (CH1) ON. ON = Power is available at the output, and the module detects power to the input circuit
37.4.1
Application Example The B881 module, with ability to sense its own output points is an excellent choice for critical operations. The example in Figure 89 shows ladder logic that allows for detection of point errors. This could ultimately be used to control a system if a critical failure occurred. The block move shown in Figure 89 moves the contents of fault register 30001 into 40008, where it can be manipulated. The results of the XOR function of the contents of register 40001 and 40008 are written into register 40008. The compare block then compares 40008 with the output state in 40001; if they do not compare, coil 0001 will energize. Coil 0001 can be tied to an indicator light or safety circuity for system protection. 30001
30001
40001
40008
40008
40007
( )
BLKM 1
XOR 1
CMPR 1
00001
00001 = MISCOMPARE OR FAULT HAS OCCURRED 30001 = FAULT REGISTER ASSIGNED IN I/O MAP 40001 = OUTPUT REGISTER ASSIGNED IN I/O MAP 40007 = POINTER FOR COMPARE BLOCK (POINTS TO 40008) --THE POINTER CONTAINS THE LOCATION OF THE FIRST ERROR BIT SET IN THE FAULT REGISTER.
40008 = XOR RESULTS OF 30001 AND 40001 Figure 89 B881--108 Application Example
202 B881--108 Protected 120 Vac Output
GM--DISC--800
Page 206
37.5 Specifications B881-108 Specifications Description
115 Vac protected output
Number of Points
8
Operating Voltage
80 ... 130 Vac / 47 ... 63 Hz 150 Vac for 10 s 200 Vac for 1 cycle
Number of Groups
8
Outputs/Group ON Current
1 Maximum/point
2 A continuous 30 A for 1 cycle
Maximum/group
2A
Maximum/module
16 A
On State Voltage Drop
1.5 Vac maximum @ 2 A
Surge Current
30 A surge current, 1 cycle/output at a rep rate not to exceed 1 surge cycle/min
Load Current
50 mA minimum
Leakage Current
3.0 mA max @ 130 Vac
Load Inductance
1 H maximum with no external diode suppression
Maximum Response Time
OFF ® ON
9 ms @ 60 Hz
ON ® OFF
9 ms @ 60 Hz
External Power Supply Note: The B881 is powered by a standard 115 Vac field power supply. Module Supply Current In
40 mA maximum (all channels ON) of field side current in addition to load current
Power Required
+5 V
285 mA***
+4.3 V
240 mA
--5 V
0 mA
Terminal Connector
AS--8535--000
Fuse
3.0 A/point, replaceable
*** When all outputs are ON, +5 V = 285 mA maximum. When all outputs are OFF, +5 V = 210 mA maximum.
GM--DISC--800
B881--108 Protected 120 Vac Output
203
Page 207
Chapter 38 B881--508 125 Vdc Output
GM--DISC--800
V
Overview
V
Fault Conditions
V
Field Connections
V
Specifications
B881--508 125 Vdc Output
205
Page 208
38.1 Overview The B881- -508 125 Vdc Output Module has eight isolated outputs. The outputs can serve 125 Vdc voltage relays, pilot lamps, motor starters, solenoids, valves, and any other load rated up to 140 Vdc (the outputs work in the range 5 ... 140 Vdc). Also, the B881 allows current surges within certain time limits. Internal fault flags report currents greater than 30 A, and currents between 5 ... 30 A for a period greater than 500 ms. This shut down mode can only be cleared by resetting the point. Point control within ms provides fast response in critical situations. The B881 conforms to ANSI/IEEE C37.90 1978 duty cycle sequences. In addition to the normal mode of controlling the outputs, the B881 allows the first four points to be independently controlled by external inputs through the field side connector. These external inputs are 24 Vdc active high and can be controlled by a B984 High Speed Logic Solver. When a fault occurs during control by the external inputs, that input must be cycled (turned off) to clear the fault flag.
206 B881--508 125 Vdc Output
GM--DISC--800
Page 209
38.1.1
Simplified Schematic
Figure 90 B881--508 Simplified Schematic
GM--DISC--800
B881--508 125 Vdc Output
207
Page 210
38.2 Fault Conditions Over current shutdown, as well as, current surges greater than 500 ms are detected by the B881. Each point has a fault bit that you can access using your programming panel software. Each bit indicates either: an over current (greater than 30 A), or a current surge between 5 ... 30 A for a period greater than 500 ms Although the B881 is I/O mapped as a 16 point bi- -directional module, only the lower order eight inputs and outputs are used, the higher order of eight inputs and outputs can not be used anywhere (see Figure 91).
Figure 91 B881--508 Fault Flags
208 B881--508 125 Vdc Output
GM--DISC--800