Page 191
The recommended location for the pull- -up resistors at the device end of the circuit; however, they will work at the module end as well. Figure 83 shows a typical circuit set- -up.
Figure 83 B865--001 Pull--up Resistor Connection
35.3.3
Strobe Type Strobe lines for the B865 module are true- -low. The opposite is the case in other Modicon I/O modules. Therefore, when multiple thumb wheel inputs require diode isolation, the polarity of the diodes may have to be reversed.
186 B865--001 Register Input
GM--DISC--800
Page 192
35.4 Specifications B865--001 Specifications Description
TTL register input
Number of Points
8 channels, 16 data lines
Operating Voltage
5 V TTL
Number of Groups
NA
Outputs/Group
NA
Guaranteed Min Levels
High State > 3.5 Vdc Low State < 0.4 Vdc while sinking 16 mA
Strobe Output Power
2 TTL loads @ 5 Vdc
Strobe Width Timing
2 mS + 10%
Data Set--up Time
Within 180 ms after the strobe has gone active (LO), data must have stabilized on the field side inputs
Minimum Data Hold Time Maximum Response Time Power Required
100 ms must be provided by the user OFF ® ON
20 ms
ON ® OFF
20 ms
+5 V
400 mA
+4.3 V
600 mA
--5 V
0 mA
External Supply Field Device Requirements
A +5 Vdc external power supply is required for pull--up resistor VCC Field Device
Output Level
TTL
Low: 0 < 0.8 Vdc @ 1.6 mA High: 1 > 2.4 Vdc @ 40 mA
CMOS
Low: 0 < 1.6 Vdc @ 0.3 mA High: 1 > 3.3 Vdc @ 0.3 mA
Terminal Connector
AS--8535--000
Note: All user field devices must have outputs that feature latched, tri- -state, or open collector, or wired or passive logic. The user must provide 2.2 kW +10% pull- -up resistors for each strobe line.
GM--DISC--800
B865--001 Register Input
187
Page 193
Chapter 36 B881--001 Latched 24 Vdc Input
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B881--001 Latched 24 Vdc Input
189
Page 194
36.1 Overview The B881- -001 True High 24 Vdc 16-channel latched input module senses and converts input signals from its field circuitry to a logic level used by Modicon PLC. The incoming signal causes the module to latch at the occurrence of the ON state and may be considered a latching event. The 24 Vdc, true high latched input module is capable of direct connection to any Modicon, true high dc output module (at proper voltage).
36.1.1
Simplified Block Diagram
Figure 84 B881--001 Simplified Block Diagram
Note: Reversal of external load polarity will not cause circuit failure as the module is fused to protect its circuitry against overload currents and accidental polarity reversal.
190 B881--001 Latched 24 Vdc Input
GM--DISC--800
Page 195
The latching mechanism exists solely to lockout subsequent incoming signals for the time it takes to communicate to the controller that a latching event occurred, receive an acknowledgement, and reset the latch. The latched input module does not affect the users field circuit, drive the controller or communicate information to it other than the fact that a latching event took place. Signals on the 16-channel inputs are compared to a reference voltage nominally set to 75% of the group supply voltage. An input signal of 500 ms minimum pulse width and equal to or exceeding the reference voltage threshold will cause a latched ON state for any given channel. An input signal voltage less than 25% of the group supply voltage will result in a system OFF state. When the module senses and latches on the leading edge of the true high, incoming field signal or data bit (DB), it clocks the D- -type flip- -flop on the low- -to- -high transition, in effect, capturing the latching event. The module’s ON state is communicated to the controller through Shift Register (A) and OBS chip via a handshake mechanism. The logic is then returned to the module from the CPU as an inverted signal through Shift Register (B) where it resets the flip- -flop (latch condition) for that channel only. The reset latch is then available for another, low- -to- -high, event transition. To ensure that the controller has received a latched event, the module actually operates in a user programmed, echoed- -data handshake mode. The handshake mechanism requires four to six scans before a new event can be recognized. Total scan time is software limited to 200 ms maximum and hardware limited to 250 ms maximum. Thus, you should not attempt to record events with a repetition rate greater than one per second unless willing to analyze his actual system and program.
GM--DISC--800
B881--001 Latched 24 Vdc Input
191
Page 196
36.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
36.2.1
Terminal Numbering and Input Functions
INPUT 1
INPUT 9
INPUT 2
INPUT 10
INPUT 3
INPUT 11
INPUT 4
INPUT 12
INPUT 5
INPUT 13
INPUT 6
INPUT 14
INPUT 7
+
INPUT 8
INPUT 15 INPUT 16
--
COMMON COMMON
COMMON 24 Vdc
Figure 85 B881--001 Terminal Numbering
192 B881--001 Latched 24 Vdc Input
GM--DISC--800
Page 197
36.3 Specifications B881--001 Specifications Description
24 Vdc (LATCH) input
Type of Operation
True High
Number of Points
16
Operating Range Voltage
20 ... 28 Vdc
Number of Groups
1
Inputs/group
16
ON Condition
> 75% of group supply voltage for .5 ms/ min event pulse width
ON ® OFF Condition
< 25% of group supply voltage and input reset bit sent back to module
ON ® OFF Condition
< 25% of group supply voltage
Maximum Input Voltage
Continuous
30 Vdc
Inrush
40 Vdc for 10 ms
ON Current
6 mA @ 24 Vdc (typical)
Minimum Pulse Width
0.5 ms
Repetition Rate Power Required
GM--DISC--800
1/s +5 V
30 mA
+4.3 V
1.1 mA
--5 V
0 mA
External Power Supply
24 Vdc (+ 4 Vdc), 310 mA
Terminal Connector
AS--8534--000
Fusing
1/group, .75 A @ 250 Vdc
B881--001 Latched 24 Vdc Input
193
Page 198
Chapter 37 B881--108 Protected 120 Vac Output
GM--DISC--800
V
Overview
V
Using the Fault Condition Filter
V
Field Connections
V
Quick Start Test
V
Specifications
B881--108 Protected 120 Vac Output
195
Page 199
37.1 Overview The B881-108 protected ac output module serves eight isolated 120 Vac relays, solenoids, pilot lamps, and other loads up to 2.0 A. The module has eight isolated discrete outputs. Each point can accept its own neutral and hot ac power connections. Therefore the module can switch multi- -phase or single phase power. The outputs work over the range 80 ... 130 Vac, true high. The module detects triac fault conditions and turns the faulted point off for vital applications. The module compares the output to the input circuit reading. When a miscompare occurs and lasts for more than 64 ms or 128 ms, a fault condition is reported to the PLC. All eight output points may be filtered at either 64 ms or 128 ms. You select the filter times to meet your specific application. Filtering can reduce your occurrence of nuisance faults. Some applications include food processing, chemical processing, painting, and foundry casting. Caution: E- -STOP USAGE - - During normal operation, each of the discrete output points switches OFF the load current synchronously with the ac power frequency at the zero crossing of the load current. This synchronous zero crossing switching provides a reliable, low- -switching energy/low transient method of controlling a broad range of industrial loads without the need for external load snubbers. If an application requires that the load or ac voltage to the module be inter- -rupted by an external switch (E- -stop) at a non- -zero load current, a large voltage transient across the load may result. This abnormal transient may be detected and interpreted as a triac ON condition of a protected OFF output point, resulting in nuisance faults. APPLICATION: ac Power Switched OFF by an Emergency Switch DESCRIPTION: The ac hot and ac neu for each point are not isolated and the applied ac voltage source to the module is open- -circuited (interrupted external to the module via an E switch), while one or more of the output points are ON, powering an inductive load. The interrupt will cause a large voltage transient across the load, which couples back through the point (an external ac power wiring) to all other ac OUT points wired to the same source. This voltage transient is detected by the monitoring circuit, and is interpreted as a 196 B881--108 Protected 120 Vac Output
GM--DISC--800
Page 200
fault condition for OFF points. When ac voltage is re- -applied, any points that have “faulted” will blow their respective line fuses. RECOMMENDATION: Eliminate any external ac power interrupt while outputs are in the ON state, or connect a suitable R/C snubber directly across each reactive load to absorb the turn- -off energy, and limit the voltage transient across the OFF point to less than 50 V peak during the interrupt.
GM--DISC--800
B881--108 Protected 120 Vac Output
197