Page 181

34.2 Switch Settings Two toggle switches are located at the top of the module and are used to determine the type of communication with external devices. Both switches are user selectable. 1.

Bin/BCD Switch

This toggle switch determines whether the output data is to be interpreted by the target devices as a BCD or a binary value. 2.

Strobes Active Hi/Lo Switch

This toggle switch allows you to select true- -hi or true- -lo for strobing output data. Note: The relation between the I/O Map selection, the BCD/Binary switch setting, and the results at the output are summarized:

Switch and Traffic Cop Relationship I/O Map Selection

B864 Switch Setting

Result

Binary

BCD

BCD

Binary

Binary

Binary

BCD

BCD

Erroneous

BCD

Binary

BCD

176 B864--001 Register Output

GM--DISC--800

Page 182

34.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

34.3.1

Terminal Numbering and Output Functions

Figure 79 B864--001 Terminal Numbering

GM--DISC--800

B864--001 Register Output

177

Page 183

34.3.2

Pull--up Resistor Connection You must install pull- -up resistors at the active device end to use the B864 output module. The value of the pull- -up resistor depends upon the number of devices that are attached to the data bus as explained below. Each output meets 0.4 V maximum at 16 ma for a logic low and 3.3 V minimum at 16 mA for a logic high. If the current limit has been exceeded, you should adjust the pull- -up resistor values within specification; otherwise, spurious results may be obtained. Figure 80 indicates how the resistors are connected at the device end. For a single device consisting of 16 data lines, 16 1 k resistors are required, or, one 1 k resistor/data line. As additional devices are added to the data bus, the value of the pull- -up resistor must be increased by 1 k. In other words, if two devices are used, the pull- -up resistor must be 2 k, three devices require a 3 k pull- -up, and so on, with the maximum number of 8 devices requiring 8 k of pull- -up for each data line.

178 B864--001 Register Output

GM--DISC--800

Page 184

B864 Module

Figure 80 B864--001 Pull--up Resistor Connection

Note: Increase pull- -up resistor value by 1 k for each additional device.

GM--DISC--800

B864--001 Register Output

179

Page 185

34.4 Specifications B864--001 Specifications Description

TTL register output

Number of Points

8 channels, 16 data lines

Operating Voltage

5 V TTL

Number of Groups

N/A

Outputs/group

N/A

Guaranteed Min Levels

High State > 3.5 Vdc Low State < 0.4 Vdc while sinking 16 mA

Strobe Output Power

Two TTL loads @ 5 Vdc

Strobe Width Timing

200 ms + 10%

Module Throughput Power Required

11.3 ms +5 V

100 mA

+4.3 V

100 mA

--5 V

0 mA

External Supply

A +5 Vdc external power supply is required for pull-up resistor VCC

Field Device Requirements

Output Level TTL

Low: 0 < 0.8 Vdc @ 1.6 mA High: 1 > 2.4 Vdc @ 40 mA

CMOS

Low: 0 < 1.6 Vdc @ 0.3 mA High: 1 > 3.3 Vdc @ 0.3 mA

Terminal Connector

AS--8535--000

Note: All user field devices must have outputs that feature latched, tri- -state, or open collector logic. The user must provide 1 kW +10% pull- -up resistors for each strobe line.

180 B864--001 Register Output

GM--DISC--800

Page 186

Chapter 35 B865--001 Register Input

GM--DISC--800

V

Overview

V

Switch Settings

V

Field Connections

V

Specifications

B865--001 Register Input

181

Page 187

35.1 Overview The B865-001 Register Input Module provides a 5 V TTL or CMOS-compatible interface between peripheral field devices and a PLC. The B865 is an eight-channel register module with eight 16-bit registers. A channel is defined as a 16-bit data path. The module can operate in either BCD or binary mode. The desired mode is user-selectable, with the parallel 16- -bit input having BCD values in the range 0000 ... 9999 and the binary input in the range 0000 ... FFFF. The B865 operates in module select mode, which updates the controller with eight input registers of new data samples on one scan period. The module select feature ensures data integrity by sampling and comparing data from the user device twice during each channel’s active strobe period. If the samples are equal, the data is accepted for further processing. If the samples are not equal, the old data is sent to the controller. If a channel has three consecutive no-compares, a 16- -bit word containing all zeros is routed to the PLC.

182 B865--001 Register Input

GM--DISC--800

Page 188

35.1.1

Simplified Block Diagram

PLC

Figure 81 B865--001 Simplified Block Diagram

The B865 operates with a 16-bit data path. Data is routed in from a device by means of a strobe line associated with each device. The data lines are common to all devices while the strobe performs the addressing function. The DC (Data Changing) signal from the field device is used for slowly changing data such as thumb wheel switches and prevents erroneous information from being transferred to the PLC. This input need only be used for slowly changing data that may cause the capture of erroneous information. The DC input connection is made on terminal 18 of the module’s field side wiring strip.

GM--DISC--800

B865--001 Register Input

183

Page 189

35.2 Switch Settings Two toggle switches are located at the top of the module and are used to determine the type of communication with external devices. Both switches are user selectable. 1.

Data Polarity Switch

This toggle switch allows you to select true- -hi or true- -lo input data. 2.

Bin/BCD Switch

This toggle switch determines whether the input data is to be interpreted by the controller as a BCD or a binary value. Note: The relation between the I/O Map selection, the BCD/binary switch setting, and the results at the output are summarized:

Switch and I/O Map Relationship I/O Map Selection

B865 Switch Setting

Result

Binary

BCD

BCD

Binary

Binary

Binary

BCD

BCD

Erroneous

BCD

Binary

BCD

184 B865--001 Register Input

GM--DISC--800

Page 190

35.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

35.3.1

Terminal Numbering and Input Functions

DATA CHANGE (DC)

Figure 82 B865--001 Terminal Numbering

35.3.2

Pull--up Resistor Connection You must provide resistive pull- -ups of 2.2 kW +10% for each strobe line. This is required on ACTIVE devices only. Thumb wheel switches for example,do not require the addition of pull- -up resistors.

GM--DISC--800

B865--001 Register Input

185