Page 171
32.4 Specifications B863--032 Specifications Description
24 Vdc high density monitored input
Type of Operation
True high
Number of Points
32
Operating Range Voltage
18 ... 30 Vdc true high, 24 Vdc nominal
Number of Groups
2
Inputs/group
16
On State Conditions
18 Vdc minimum @ the input, 30 Vdc maximum @ the input, typical on state current: 4 mA
Off State Conditions
6 Vdc maximum @ the input, typical OFF state current: 1 mA
Maximum Response Time
OFF ® ON
10 ms
ON ® OFF
10 ms
Power Required
+5 V
250 mA
+4.3 V
0 mA
--5 V
0 mA
Operating Current
20 mA of field power plus point input channel
Operating Voltage
18 ... 30 Vdc true high, 24 Vdc nominal
External Power Supply Terminal Connector
166 B863--032 Monitored 24 Vdc Input
AS--8535--000
GM--DISC--800
Page 172
Chapter 33 B863--132 24 Vdc Input
GM--DISC--800
V
Overview
V
Switch Settings
V
Field Connections
V
Configuration
V
Specifications
B863--132 24 Vdc Input
167
Page 173
33.1 Overview The B863- -132 24 Vdc (32-point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC. This module senses and reports broken wire faults. The module is designed for safety applications whereby it monitors essential field wiring. This module satisfies applications where connectivity diagnostics are important to the process. A logic side LED indicates the logic state that is written into the state table.
33.1.1
Simplified Schematic 6.2 kW EXTERNAL RESISTOR (BROKEN WIRE DETECTION)
6 mA
Figure 74 B863--132 Simplified Schematic
168 B863--132 24 Vdc Input
GM--DISC--800
Page 174
33.2 Switch Settings A four-position DIP switch (see Figure 75) located on the rear of the module is used to select broken wire testing. Each individual switch relates to one of the four groups of eight input points. For example, DIP- -Switch position #1 when set to OFF senses for broken wire faults for group 1 and so on; when set to ON no fault is reported. Caution: Only Binary should be used when operating module in line test mode. Do not use BCD. LINE TEST SWITCH FOUR-POSITION DIP SWITCH TOP OF MODULE
1 2 3 4
PCB
1 ON LEFT UP
0 OFF RIGHT DOWN
SWITCHES SW1=0 =1
FUNCTIONS GROUP 1, LINE TEST GROUP1, NO TEST
SW2=0 =1
GROUP 2, LINE TEST GROUP2, NO TEST
SW3=0 =1
GROUP 3, LINE TEST GROUP3, NO TEST
SW4=0 =1
GROUP 4, LINE TEST GROUP4, NO TEST
Figure 75 Line Test DIP--Switch Settings
Note: When using binary and BCD inputs remember that input 1 is the MSB and input 32 is the LSB.
GM--DISC--800
B863--132 24 Vdc Input
169
Page 175
33.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring. Refer to Figure 76 for input connections.
6.2 kW EXTERNAL RESISTOR (BROKEN WIRE DETECTION)
Figure 76 B863--132 Terminal Numbering and Input Connections
170 B863--132 24 Vdc Input
GM--DISC--800
Page 176
33.4 Configuration This module appears as a B863 module when configured. This means the module requires four 16-bit words (1x registers), see Figure 77. The first two words contains the state of the input points. The second two words contain the condition of the field wiring. If a broken wire is detected on input point, then a one is displayed in input register (1x + 32) at its position. When the fault is fixed, a zero appears in the bit. A one indicates a detected fault, whereas, a zero indicates normal operation of that input point. MSB
LSB
1x + 0
12345678
9 10 11 12 13 14 15 16
1 ... 16 input data
1x + 16
12345678
9 10 11 12 13 14 15 16
17 ... 32 input data
1x + 32
12345678
9 10 11 12 13 14 15 16
1 ... 16 fault detection
1x + 48
12345678
9 10 11 12 13 14 15 16
17 ... 32 fault detection
Figure 77 B863--132 Data Registers
GM--DISC--800
B863--132 24 Vdc Input
171
Page 177
33.5 Specifications B863--132 Specifications Description
24 Vdc input
Number of Points
32
Number of Groups
4
Inputs/Group
8
Working Voltage
0 ... 30 Vdc
Reference Voltage
19.2 ... 30 Vdc
Reference Current
9 ... 15 mA/group
Threshold Voltage
11 ... 15 Vdc
External Resistor
(broken wire detect) 6.2 kW +10%, 1 external resistor/input point, resistor across contactor for nominally operated 24 Vdc system
Input Current Transition Time
Low state
1.8 ... 3 mA
High state
5.75 ... 7.1 mA
ON
V in = 20 Vdc 200 ms minimum V in = 30 Vdc 25 ms minimum
OFF
V in = 20 Vdc 100 ms maximum V in = 30 Vdc 250 ms maximum
Maximum Response Time
OFF® ON, ON ® OFF
2 ms, contact opening or closing, 100 ms maximum fault detection time
Power Required
+5 V
350 mA
+4.3 V
10 mA
--5 V
0 mA (not used)
Terminal Connector
172 B863--132 24 Vdc Input
AS--8535--000
GM--DISC--800
Page 178
Chapter 34 B864--001 Register Output
GM--DISC--800
V
Overview
V
Switch Settings
V
Field Connections
V
Specifcations
B864--001 Register Output
173
Page 179
34.1 Overview The B864- -001 Register Output Module provides a 5 V TTL or CMOS-compatible interface between a PLC and peripheral field devices. The B864 register output module operates in either BCD or binary mode. The desired mode is operator selectable, with the 16- -bit output either having BCD values in the range 0000 ... 9999 or binary output in the range 0000 ... FFFF hex. The B864 is an eight-channel register output module with eight 16-bit registers. A channel is defined as a 16-bit data path. The channels can be configured as eight BCD or eight binary registers via the appropriate switch setting. The module is organized in a group strobe arrangement with the 16 data lines associated at a given moment with one of the eight strobe lines. Each strobe line addresses one of the devices on the data bus and enables it to transmit data to a given peripheral device to the exclusion of the other devices. The data lines are routed to all devices. The B864 is operated in module select mode. In module select mode, all eight data registers are transferred in a single Ourbus cycle.
174 B864--001 Register Output
GM--DISC--800
Page 180
34.1.1
Simplified Block Diagram
PLC
Figure 78 B864--001 Simplified Block Diagram
GM--DISC--800
B864--001 Register Output
175