Page 171

32.4 Specifications B863--032 Specifications Description

24 Vdc high density monitored input

Type of Operation

True high

Number of Points

32

Operating Range Voltage

18 ... 30 Vdc true high, 24 Vdc nominal

Number of Groups

2

Inputs/group

16

On State Conditions

18 Vdc minimum @ the input, 30 Vdc maximum @ the input, typical on state current: 4 mA

Off State Conditions

6 Vdc maximum @ the input, typical OFF state current: 1 mA

Maximum Response Time

OFF ® ON

10 ms

ON ® OFF

10 ms

Power Required

+5 V

250 mA

+4.3 V

0 mA

--5 V

0 mA

Operating Current

20 mA of field power plus point input channel

Operating Voltage

18 ... 30 Vdc true high, 24 Vdc nominal

External Power Supply Terminal Connector

166 B863--032 Monitored 24 Vdc Input

AS--8535--000

GM--DISC--800

Page 172

Chapter 33 B863--132 24 Vdc Input

GM--DISC--800

V

Overview

V

Switch Settings

V

Field Connections

V

Configuration

V

Specifications

B863--132 24 Vdc Input

167

Page 173

33.1 Overview The B863- -132 24 Vdc (32-point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC. This module senses and reports broken wire faults. The module is designed for safety applications whereby it monitors essential field wiring. This module satisfies applications where connectivity diagnostics are important to the process. A logic side LED indicates the logic state that is written into the state table.

33.1.1

Simplified Schematic 6.2 kW EXTERNAL RESISTOR (BROKEN WIRE DETECTION)

6 mA

Figure 74 B863--132 Simplified Schematic

168 B863--132 24 Vdc Input

GM--DISC--800

Page 174

33.2 Switch Settings A four-position DIP switch (see Figure 75) located on the rear of the module is used to select broken wire testing. Each individual switch relates to one of the four groups of eight input points. For example, DIP- -Switch position #1 when set to OFF senses for broken wire faults for group 1 and so on; when set to ON no fault is reported. Caution: Only Binary should be used when operating module in line test mode. Do not use BCD. LINE TEST SWITCH FOUR-POSITION DIP SWITCH TOP OF MODULE

1 2 3 4

PCB

1 ON LEFT UP

0 OFF RIGHT DOWN

SWITCHES SW1=0 =1

FUNCTIONS GROUP 1, LINE TEST GROUP1, NO TEST

SW2=0 =1

GROUP 2, LINE TEST GROUP2, NO TEST

SW3=0 =1

GROUP 3, LINE TEST GROUP3, NO TEST

SW4=0 =1

GROUP 4, LINE TEST GROUP4, NO TEST

Figure 75 Line Test DIP--Switch Settings

Note: When using binary and BCD inputs remember that input 1 is the MSB and input 32 is the LSB.

GM--DISC--800

B863--132 24 Vdc Input

169

Page 175

33.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring. Refer to Figure 76 for input connections.

6.2 kW EXTERNAL RESISTOR (BROKEN WIRE DETECTION)

Figure 76 B863--132 Terminal Numbering and Input Connections

170 B863--132 24 Vdc Input

GM--DISC--800

Page 176

33.4 Configuration This module appears as a B863 module when configured. This means the module requires four 16-bit words (1x registers), see Figure 77. The first two words contains the state of the input points. The second two words contain the condition of the field wiring. If a broken wire is detected on input point, then a one is displayed in input register (1x + 32) at its position. When the fault is fixed, a zero appears in the bit. A one indicates a detected fault, whereas, a zero indicates normal operation of that input point. MSB

LSB

1x + 0

12345678

9 10 11 12 13 14 15 16

1 ... 16 input data

1x + 16

12345678

9 10 11 12 13 14 15 16

17 ... 32 input data

1x + 32

12345678

9 10 11 12 13 14 15 16

1 ... 16 fault detection

1x + 48

12345678

9 10 11 12 13 14 15 16

17 ... 32 fault detection

Figure 77 B863--132 Data Registers

GM--DISC--800

B863--132 24 Vdc Input

171

Page 177

33.5 Specifications B863--132 Specifications Description

24 Vdc input

Number of Points

32

Number of Groups

4

Inputs/Group

8

Working Voltage

0 ... 30 Vdc

Reference Voltage

19.2 ... 30 Vdc

Reference Current

9 ... 15 mA/group

Threshold Voltage

11 ... 15 Vdc

External Resistor

(broken wire detect) 6.2 kW +10%, 1 external resistor/input point, resistor across contactor for nominally operated 24 Vdc system

Input Current Transition Time

Low state

1.8 ... 3 mA

High state

5.75 ... 7.1 mA

ON

V in = 20 Vdc 200 ms minimum V in = 30 Vdc 25 ms minimum

OFF

V in = 20 Vdc 100 ms maximum V in = 30 Vdc 250 ms maximum

Maximum Response Time

OFF® ON, ON ® OFF

2 ms, contact opening or closing, 100 ms maximum fault detection time

Power Required

+5 V

350 mA

+4.3 V

10 mA

--5 V

0 mA (not used)

Terminal Connector

172 B863--132 24 Vdc Input

AS--8535--000

GM--DISC--800

Page 178

Chapter 34 B864--001 Register Output

GM--DISC--800

V

Overview

V

Switch Settings

V

Field Connections

V

Specifcations

B864--001 Register Output

173

Page 179

34.1 Overview The B864- -001 Register Output Module provides a 5 V TTL or CMOS-compatible interface between a PLC and peripheral field devices. The B864 register output module operates in either BCD or binary mode. The desired mode is operator selectable, with the 16- -bit output either having BCD values in the range 0000 ... 9999 or binary output in the range 0000 ... FFFF hex. The B864 is an eight-channel register output module with eight 16-bit registers. A channel is defined as a 16-bit data path. The channels can be configured as eight BCD or eight binary registers via the appropriate switch setting. The module is organized in a group strobe arrangement with the 16 data lines associated at a given moment with one of the eight strobe lines. Each strobe line addresses one of the devices on the data bus and enables it to transmit data to a given peripheral device to the exclusion of the other devices. The data lines are routed to all devices. The B864 is operated in module select mode. In module select mode, all eight data registers are transferred in a single Ourbus cycle.

174 B864--001 Register Output

GM--DISC--800

Page 180

34.1.1

Simplified Block Diagram

PLC

Figure 78 B864--001 Simplified Block Diagram

GM--DISC--800

B864--001 Register Output

175