Page 161
Figure 68 B855--016 Typical Field Circuit Connections
B855--016 Intrinsically Safe 12 Vdc Input
GM--DISC--800
Page 162
Step 7
Referring to Figure 68, connect field side wiring to proper pins on the field connector. Note: The external 12 Vdc (+ 5%) power supply for the module should be a minimum of 1.0 A.
GM--DISC--800
Step 8
Insert the module into the housing, firmly but carefully, seating the edge connector in the backplane.
Step 9
Secure module to housing using captive slotted mounting screws at the top and bottom of the module front panel.
B855--016 Intrinsically Safe 12 Vdc Input
157
Page 163
31.3 Specifications B855--016 Specifications Description
12 Vdc intrinsically safe input (true low)
Number of Points
16, isolated
Operating Voltage
11.4 ... 12.6 Vdc
Number of Groups
1
Inputs/Group
16
Maximum Input Voltage
Continuous
12 Vdc (+5%)
Surge
500 Vdc for 3 ms
ON State Conditions
100 W or less total impedance (3.9 mA @ 12 Vdc)
OFF State Conditions
An open circuit, no less than 100,000 W (75 mA) approx. 8.95 V present on + lead
Maximum Response Time
OFF ... ON
1 ms
ON ... OFF
5 ms
+5 V
80 mA
+4.3 V
1.5 mA
--5 V
0 mA
Power Required
Leakage Current
< 1.5 mA
Wattage Rating on the Module
1.8 W
Maximum Input Voltage @ Source Inputs
Not to exceed 500 Vdc for 3 mS to user source terminals
Module Supply Voltage In
11.4 ... 12.6 Vdc, 0.5 A max load working, *80 mA inrush current *Minimum power supply recommended is 1.0 A
Maximum Impedance Limitations
Group
L Inductance
C Capacitance
A&B
80 mH
1.0 mf
C
300 mH
3.0 mf
D
700 mH
8.0 mf
Note: These are Factory Mutual requirements. Please consult with your vendors regarding field devices, wiring, and barriers to ensure compliance. Terminal Connector
AS--8535--000
Factory Mutual FM 3610
Requires use of key pins and MD--8741--000 barrier strip included with the module
158 B855--016 Intrinsically Safe 12 Vdc Input
GM--DISC--800
Page 164
Chapter 32 B863--032 Monitored 24 Vdc Input
GM--DISC--800
V
Overview
V
Field Connections
V
Quick Start Test
V
Specifications
B863--032 Monitored 24 Vdc Input
159
Page 165
32.1 Overview The B863-032 Monitored dc Input Module (B863) is a 32 point, 24 Vdc, true high, 800 Series, module capable of determining the state of switches, relays, solenoids, lamps, proximity switches, and other 24 Vdc powered devices. In addition, the B863 monitors itself to insure its ability to detect high or low states at its inputs. This feature is designed to provide an extra margin of reliability in safety shutdown systems. This is accomplished with a module resident diagnostic test. The diagnostics verify the module’s functionality by momentarily forcing all inputs to a low state followed by a high state. This forcing function is transparent to the input source.
32.1.1
Simplified Schematic
Figure 69 B863--032 Simplified Schematic
160 B863--032 Monitored 24 Vdc Input
GM--DISC--800
Page 166
This diagnostic test is performed at a rate of 1/s, and takes less than 1 ms. The inability of an input to detect a low or high state during diagnostics, results in the reporting of a fault to the controller, and the flashing of the ACTIVE LED. Digital filtering is performed on all inputs to reduce the occurrence of nuisance faults. Communication between the module and the controller consists of four words. Two words contain the State of each input, and the other two words contain the Fault Status of each input. Within the State words, a high, or one indicates a ON condition. Within the Fault Status words, a high, or one indicates a fault at the respective input.
GM--DISC--800
B863--032 Monitored 24 Vdc Input
161
Page 167
32.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
32.2.1
Input Connections
+ 24 Vdc --
Figure 70 B863--032 Terminal Numbering and Input Connections
162 B863--032 Monitored 24 Vdc Input
GM--DISC--800
Page 168
32.3 Quick Start Test This test configures the module as follows: B863 (4 register binary). Step 1
Stop the controller.
Step 2
Determine which channel and slot location are being used for this module and insert the module. Note: Remove the keying tabs on the AS- -8535- -000 high density connector prior to installing module.
Step 3
Wire +24 Vdc external power supply to terminal 18, and connect common to terminal 20 on a AS- -8535- -000 high density connector. Do not connect any other field wiring to the connector.
Step 4
Turn ON the external 24 Vdc power supply. The Field Power light will come ON.
Step 5
I/O Map the module as a B863, four register inputs 30001 ... 30004 binary. Recall that the first two registers are used for real inputs, and the last two registers are error flags.
Step 6
Start the controller.
Step 7
Confirm that the module’s active light is illuminated. Note: Active on steady = OK. Active blinking = Check the 24 Vdc external power supply voltage and wiring.
Step 8
View the B863 I/O mapped registers, 30001 ... 30004 on the reference screen in binary format.
Step 9
Verify that all the points are zero. Note: The first two registers, 30001 and 30002 are real inputs. Open inputs to the module reads 0. The second two registers, 30003 and 30004 are error flags. A value of 1 in any of these error flag points indicates a faulty input.
Step 10 GM--DISC--800
Turn OFF the external 24 Vdc power supply, and all error flag points change to 1. B863--032 Monitored 24 Vdc Input
163
Page 169
Step 11
Turn ON the external 24 Vdc power supply, and all error flag points change back to 0.
Step 12
To test an input, connect a wire from the +24 Vdc point on the connector terminal 18, and touch the other end of the wire to terminal 1. Bit 1 in 30001 goes from 0 to 1. The error flag for input 1 is found at bit 1 in register 30003. When the input is functional this reads 0.
32.3.1
Application Example The B863 module not only reads 24 Vdc inputs, but it allows you to monitor the health of the input circuits through the use of the input error flags. In the following example, networks allow you to monitor the error flag inputs for maintenance and troubleshooting. If the B863 module is I/O mapped as 30001 ... 30004, then registers 30001 and 30002 are the real world inputs, and 30003 and 30004 become the Error Flag Inputs. In Figure 71, registers 30003 and 30004 are compared to registers 40011 and 40012. 30003 40010 CMPR 2
00010 00020
30003 = ERROR FLAG INPUT REGISTER MATRIX A (30003, 30004) 40010 = POINTER REGISTER FOR MATRIX B (40011, 40012) 2 = NUMBER OF REGISTERS IN EACH MATRIX TO BE COMPARED Figure 71 B863--032 Network One
Note: 40011 and 40012 must be initialized to zero. If a miscompare is detected then output 10 goes ON and 40010 will contain the bit with the error as shown in Figure 72. These error bits are stored in an error table through the R®T function block. The MBIT function block sets the same bit in matrix B so the input at fault is not placed into the error table on every scan.
164 B863--032 Monitored 24 Vdc Input
GM--DISC--800
Page 170
40010 00010
40100 R®T 10
40010 = CONTAINS THE BIT WITH THE ERROR 40100 = POINTER TO A TABLE BEGINNING AT 40101 WHERE THE ERROR BIT WILL BE STORED 10 = LENGTH OF THE TABLE
40010 00010 00020
40011 MBIT 2
40010 = CONTAINS THE BIT WITH THE ERROR 40011 = FIRST REGISTER IN TABLE 2= NUMBER OF REGISTERS IN TABLE
Figure 72 B863--032 Network Two
The following table shows how a failure of input 15 would look in the error table. Figure 73 shows matrix A input registers (30003 and 30004) and how a failure of input 15 or bit 15 looks. When the error is corrected, the error table and pointer should be cleared to 0. B863--032 Input 15 Error Table Register
Data
40100
0001 ¬ Pointer to Table
40101
0015 ¬ Fault with Input Bit 15
40102
0000
40103
0000
...
...
40110
0000
BIT 1 BIT 16 30003 (Input Register) = 0000 0000 0000 0010
BIT 17 BIT 32 30004 (Input Register) = 0000 0000 0000 0000 Figure 73 B863--032 Error Location
GM--DISC--800
B863--032 Monitored 24 Vdc Input
165