Page 161

Figure 68 B855--016 Typical Field Circuit Connections

B855--016 Intrinsically Safe 12 Vdc Input

GM--DISC--800

Page 162

Step 7

Referring to Figure 68, connect field side wiring to proper pins on the field connector. Note: The external 12 Vdc (+ 5%) power supply for the module should be a minimum of 1.0 A.

GM--DISC--800

Step 8

Insert the module into the housing, firmly but carefully, seating the edge connector in the backplane.

Step 9

Secure module to housing using captive slotted mounting screws at the top and bottom of the module front panel.

B855--016 Intrinsically Safe 12 Vdc Input

157

Page 163

31.3 Specifications B855--016 Specifications Description

12 Vdc intrinsically safe input (true low)

Number of Points

16, isolated

Operating Voltage

11.4 ... 12.6 Vdc

Number of Groups

1

Inputs/Group

16

Maximum Input Voltage

Continuous

12 Vdc (+5%)

Surge

500 Vdc for 3 ms

ON State Conditions

100 W or less total impedance (3.9 mA @ 12 Vdc)

OFF State Conditions

An open circuit, no less than 100,000 W (75 mA) approx. 8.95 V present on + lead

Maximum Response Time

OFF ... ON

1 ms

ON ... OFF

5 ms

+5 V

80 mA

+4.3 V

1.5 mA

--5 V

0 mA

Power Required

Leakage Current

< 1.5 mA

Wattage Rating on the Module

1.8 W

Maximum Input Voltage @ Source Inputs

Not to exceed 500 Vdc for 3 mS to user source terminals

Module Supply Voltage In

11.4 ... 12.6 Vdc, 0.5 A max load working, *80 mA inrush current *Minimum power supply recommended is 1.0 A

Maximum Impedance Limitations

Group

L Inductance

C Capacitance

A&B

80 mH

1.0 mf

C

300 mH

3.0 mf

D

700 mH

8.0 mf

Note: These are Factory Mutual requirements. Please consult with your vendors regarding field devices, wiring, and barriers to ensure compliance. Terminal Connector

AS--8535--000

Factory Mutual FM 3610

Requires use of key pins and MD--8741--000 barrier strip included with the module

158 B855--016 Intrinsically Safe 12 Vdc Input

GM--DISC--800

Page 164

Chapter 32 B863--032 Monitored 24 Vdc Input

GM--DISC--800

V

Overview

V

Field Connections

V

Quick Start Test

V

Specifications

B863--032 Monitored 24 Vdc Input

159

Page 165

32.1 Overview The B863-032 Monitored dc Input Module (B863) is a 32 point, 24 Vdc, true high, 800 Series, module capable of determining the state of switches, relays, solenoids, lamps, proximity switches, and other 24 Vdc powered devices. In addition, the B863 monitors itself to insure its ability to detect high or low states at its inputs. This feature is designed to provide an extra margin of reliability in safety shutdown systems. This is accomplished with a module resident diagnostic test. The diagnostics verify the module’s functionality by momentarily forcing all inputs to a low state followed by a high state. This forcing function is transparent to the input source.

32.1.1

Simplified Schematic

Figure 69 B863--032 Simplified Schematic

160 B863--032 Monitored 24 Vdc Input

GM--DISC--800

Page 166

This diagnostic test is performed at a rate of 1/s, and takes less than 1 ms. The inability of an input to detect a low or high state during diagnostics, results in the reporting of a fault to the controller, and the flashing of the ACTIVE LED. Digital filtering is performed on all inputs to reduce the occurrence of nuisance faults. Communication between the module and the controller consists of four words. Two words contain the State of each input, and the other two words contain the Fault Status of each input. Within the State words, a high, or one indicates a ON condition. Within the Fault Status words, a high, or one indicates a fault at the respective input.

GM--DISC--800

B863--032 Monitored 24 Vdc Input

161

Page 167

32.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

32.2.1

Input Connections

+ 24 Vdc --

Figure 70 B863--032 Terminal Numbering and Input Connections

162 B863--032 Monitored 24 Vdc Input

GM--DISC--800

Page 168

32.3 Quick Start Test This test configures the module as follows: B863 (4 register binary). Step 1

Stop the controller.

Step 2

Determine which channel and slot location are being used for this module and insert the module. Note: Remove the keying tabs on the AS- -8535- -000 high density connector prior to installing module.

Step 3

Wire +24 Vdc external power supply to terminal 18, and connect common to terminal 20 on a AS- -8535- -000 high density connector. Do not connect any other field wiring to the connector.

Step 4

Turn ON the external 24 Vdc power supply. The Field Power light will come ON.

Step 5

I/O Map the module as a B863, four register inputs 30001 ... 30004 binary. Recall that the first two registers are used for real inputs, and the last two registers are error flags.

Step 6

Start the controller.

Step 7

Confirm that the module’s active light is illuminated. Note: Active on steady = OK. Active blinking = Check the 24 Vdc external power supply voltage and wiring.

Step 8

View the B863 I/O mapped registers, 30001 ... 30004 on the reference screen in binary format.

Step 9

Verify that all the points are zero. Note: The first two registers, 30001 and 30002 are real inputs. Open inputs to the module reads 0. The second two registers, 30003 and 30004 are error flags. A value of 1 in any of these error flag points indicates a faulty input.

Step 10 GM--DISC--800

Turn OFF the external 24 Vdc power supply, and all error flag points change to 1. B863--032 Monitored 24 Vdc Input

163

Page 169

Step 11

Turn ON the external 24 Vdc power supply, and all error flag points change back to 0.

Step 12

To test an input, connect a wire from the +24 Vdc point on the connector terminal 18, and touch the other end of the wire to terminal 1. Bit 1 in 30001 goes from 0 to 1. The error flag for input 1 is found at bit 1 in register 30003. When the input is functional this reads 0.

32.3.1

Application Example The B863 module not only reads 24 Vdc inputs, but it allows you to monitor the health of the input circuits through the use of the input error flags. In the following example, networks allow you to monitor the error flag inputs for maintenance and troubleshooting. If the B863 module is I/O mapped as 30001 ... 30004, then registers 30001 and 30002 are the real world inputs, and 30003 and 30004 become the Error Flag Inputs. In Figure 71, registers 30003 and 30004 are compared to registers 40011 and 40012. 30003 40010 CMPR 2

00010 00020

30003 = ERROR FLAG INPUT REGISTER MATRIX A (30003, 30004) 40010 = POINTER REGISTER FOR MATRIX B (40011, 40012) 2 = NUMBER OF REGISTERS IN EACH MATRIX TO BE COMPARED Figure 71 B863--032 Network One

Note: 40011 and 40012 must be initialized to zero. If a miscompare is detected then output 10 goes ON and 40010 will contain the bit with the error as shown in Figure 72. These error bits are stored in an error table through the R®T function block. The MBIT function block sets the same bit in matrix B so the input at fault is not placed into the error table on every scan.

164 B863--032 Monitored 24 Vdc Input

GM--DISC--800

Page 170

40010 00010

40100 R®T 10

40010 = CONTAINS THE BIT WITH THE ERROR 40100 = POINTER TO A TABLE BEGINNING AT 40101 WHERE THE ERROR BIT WILL BE STORED 10 = LENGTH OF THE TABLE

40010 00010 00020

40011 MBIT 2

40010 = CONTAINS THE BIT WITH THE ERROR 40011 = FIRST REGISTER IN TABLE 2= NUMBER OF REGISTERS IN TABLE

Figure 72 B863--032 Network Two

The following table shows how a failure of input 15 would look in the error table. Figure 73 shows matrix A input registers (30003 and 30004) and how a failure of input 15 or bit 15 looks. When the error is corrected, the error table and pointer should be cleared to 0. B863--032 Input 15 Error Table Register

Data

40100

0001 ¬ Pointer to Table

40101

0015 ¬ Fault with Input Bit 15

40102

0000

40103

0000

...

...

40110

0000

BIT 1 BIT 16 30003 (Input Register) = 0000 0000 0000 0010

BIT 17 BIT 32 30004 (Input Register) = 0000 0000 0000 0000 Figure 73 B863--032 Error Location

GM--DISC--800

B863--032 Monitored 24 Vdc Input

165