Page 151

Chapter 30 B853--016 115 Vac/125 Vdc Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B853--016 115 Vac/125 Vdc Input

145

Page 152

30.1 Overview The B853-016 115 Vac/125 Vdc True High input module senses OFF and ON input signals from its field circuitry, converting them to logic levels used by a Modicon PLC. The module’s 16 input circuits are divided into two groups of eight channels, each group being totally isolated from the other. Although both groups use common return wires, none has a definite relationship to system ground unless established in the user’s field circuitry. Since both groups nominally employ independent power return sources, both ac and dc powered field circuits may input to the module at the same time. Note: Reversal of external signal polarity will not cause channel circuit damage as circuit design is indifferent to accidental polarity reversal.

30.1.1

Simple Block Diagram

TO P C

Figure 64 B853--016 Simplified Block Diagram

146 B853--016 115 Vac/125 Vdc Input

GM--DISC--800

Page 153

When the user’s ac/dc powered field circuit goes ON - as the result of a limit switch, for example - it presents the field power voltage at the modules appropriate input channel. When the input voltage meets or exceeds the module’s guaranteed ON threshold, the resulting voltage turns the channel monitor lamp ON, current flows through the bridge rectifier and subsequently the opto- -isolator (OPTO- -ISOL) circuit. Given a nominal 115 Vac/125 Vdc field power supply and a kW maximum input source impedance, the module’s channel monitor lamps will indicate ON and OFF when input voltages are 80 Vac/85 Vdc for the high level ON; and 35 Vac/40 Vdc for the low level OFF respectively. The optical energy goes to the communications board (COMM BOARD) where the OURBUS output register is set to represent the field circuit’s ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the controller. Total scan time may be as long as 250 ms. The user should not attempt to monitor events with a repetition rate greater than 1/s without analyzing his actual system, program, and scan time. Note: It is possible to have the ACTIVE indicator lit with one or more input channels working improperly.

GM--DISC--800

B853--016 115 Vac/125 Vdc Input

147

Page 154

30.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

30.2.1

Terminal Numbering and Input Functions

+

+

115 Vac 125 Vdc

115 Vac 125 Vdc

--

--

Figure 65 B853--016 Terminal Numbering

Note: To use both input groups with a single power supply, jump terminals #9 and #19.

148 B853--016 115 Vac/125 Vdc Input

GM--DISC--800

Page 155

30.3 Specifications B853--016 Specifications Description

115 Vac/125 Vdc input

Number of Points

16

Operating Voltage

80 ... 130 Vac/47 ... 63 Hz; 85 ... 150 Vdc

Number of Groups

2

Inputs/group Maximum Input Voltage

8 Continuous

130 Vac/150 Vdc

Surge

150 Vac/180 Vdc for 10 s; 280 V peak for 10 ms

ON Conditions

> 80 Vac or 85 Vdc; w/Inp Source Impedance of 1 k maximum input current 9 mA + 2 mA

OFF Conditions

< 35 Vac/40 Vdc; < 130 Vac w/Inp Source Impedance > 40 K; < 150 Vdc w/Inp Source Impedance > 80 k

ON Current Maximum Response Time Power Required

Terminal Connector

GM--DISC--800

7 mA (max), 4.5 mA (min) OFF ® ON

6 ms

OFF ® ON

18 ms

+5 V

40 mA

+4.3 V

1 mA

--5 V

15 mA AS--8534--000

B853--016 115 Vac/125 Vdc Input

149

Page 156

Chapter 31 B855--016 Intrinsically Safe 12 Vdc Input

GM--DISC--800

V

Overview

V

Installation

V

Specifications

B855--016 Intrinsically Safe 12 Vdc Input

151

Page 157

31.1 Overview The B855-016 Intrinsically Safe (fully isolated) Input Module accepts 16 switch closures or low impedance discrete inputs less than 100 W and operates in any 800 Series I/O slot. The B855 module monitors hazardous area contact closures. The B855 can operate in either continuously or intermittently hazardous environments containing acetylene, hydrogen, ethylene or methane gases; metal, coal or grain dust, and fibers. The B855 module meets Factory Mutual Standard FM 3610 for Intrinsically Safe Connections to Field Side Associated Apparatus. The B855 module has 16 discrete inputs. The inputs work in the range 11.4 ... 12.6 Vdc, True Low.

152 B855--016 Intrinsically Safe 12 Vdc Input

GM--DISC--800

Page 158

31.2 Installation Procedure

How to Install a B855 Installation of your B855 module involves: unpacking the module, wiring the field connector, installing key pins, and mounting the module into the housing.

Step 1

Remove the module from its shipping box and check for damage. If damaged, contact your salesman or distributor for correct procedure.

Step 2

Ensure power to housing is OFF.

Step 3

Designate the housing slot for this module.

Step 4

Locate required connector assembly (Modicon Part number AS- -8535- -000). This assembly consists of two 20- -pin connectors.

Step 5

Referring to Figure 66, connect field side wiring to proper pins on the field connector. You must wire the hazardous area connections, pins 9 ... 40, separately from the safe area connections. Wire the dc source to the safe area connections, pins 1 and 2. Caution: You must use the MD-8741-000Intrinsically Safe Barrier Strip to meet Factory Mutual’s requirements.

Step 6

Referring to Figure 67, remove the two Phillips head screws from the top 20- -pin connector of the AS- -8535- -000. Take the intrinsically safe barrier strip out of the white bag attached to the handle of the module. Place the intrinsically safe barrier strip on the left side of the top 20- -pin connector between pins 3, and 8. Make sure the raised edge of the intrinsically safe barrier strip is facing away from the black wiring duct. Insert this sub- -assembly inside the black wire duct while aligning the two screw holes. Insert the two Phillips head screws and tighten them down. Note: You must use key pins (shipped with this module) to meet Factory Mutual’s requirements.

GM--DISC--800

B855--016 Intrinsically Safe 12 Vdc Input

153

Page 159

RETURN

1 2 3 4

5 6 7 8

9 10 11 12

13 14 15 16

Figure 66 B855--016 Hazardous Area and Safe Area Wiring

154 B855--016 Intrinsically Safe 12 Vdc Input

GM--DISC--800

Page 160

RAISED EDGE

INTRINSICALLY SAFE BARRIER STRIP MD--8714--000

RETAINING SCREW

TOP 20--PIN CONNECTOR

INTRINSICALLY SAFE BARRIER STRIP MD--8714--000

TOP 20--PIN CONNECTOR

Figure 67 B855--016 Intrinsically Safe Barrier Strip

GM--DISC--800

B855--016 Intrinsically Safe 12 Vdc Input

155