The text of a manual · part 15 of 25
Modicon 800 Series Discrete I/O Modules User Guide, pages 141 to 150
Pages 141 to 150 of 241
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B804, Modicon B805, Modicon B807, Modicon B824, Modicon B825, Modicon B828, Modicon B865, AEG B804, and 21 more models
Page 141
28.1 Overview The B840-108 Relay Output Module converts signals from the 800 Series Ourbus to eight independent relay outputs. Each output is capable of driving relays, pilot lamps, or other loads up to 2 A. The module utilizes eight high-reliability mercury-wetted relays to control the loads. Each of the eight outputs is electrically isolated from the I/O bus and from the other seven outputs by the relay coil. These outputs are capable of switching 100 VA maximum instantaneous power associated with ac or dc loads. Such devices may range from relays and pilot lamps to multiplexed low level analog signals. Each output has an RC snubber to protect the mercury wetted contacts from arcing caused by rapid rate of rise of applied voltage from inductive loads upon instantaneous opening of the contacts. The output signals can withstand severe voltage transients that may be encountered in industrial environments - i.e., the voltage transients will not propagate through the relay to the Ourbus, thus protecting all other controller system components from damage. All output circuits are also fused to protect against overload currents.
28.1.1
Simplified Schematic
PLC REMOVABLE
Figure 59 B840--108 Simplified Schematic
134 B840--108 Relay Output
GM--DISC--800
Page 142
The module is user-configurable as to setting up for normally-open or normally-closed operation of the relays as described below. You can also optionally configure the RC snubber circuit to remove it when minimal leakage current applications such as data multiplexing are being used. The logic interface chip samples the eight logic level signals simultaneously from the PLC on each scan and holds these samples to drive the appropriate reed relay coil. Assuming a normally-open jumpered configuration, when the relay coil is energized, the reed relay contacts conduct current from the output A terminal to the output B terminal.
GM--DISC--800
B840--108 Relay Output
135
Page 143
28.2 Configuration The B840- -108 Relay Module is initially shipped with all 8 channels jumpered for the normally- -open configuration with all snubber circuits connected. You may wire any of the channels for either normally- -open or normally- -closed operation by transferring a wire jumper from one tab to another on the printed circuit board to change from normally- -open to normally- -closed (see Figure 60). RELAY CHAN.
N.O. W1--E2
N.C. W1--E1
SNUBBER CHAN.
W2--E4
W3--E6
W2--E3
JP1
JP1
JP2
JP2
3
JP3
JP3
W4--E8
4
JP4
JP4
JP5
JP5
JP6
JP6
JP7
JP7
JP8
JP8
W4--E7
4 W5--E10
2
W3--E5
3
W5--E9 5
5 W6--E12
W6--E11 6
6 W7--E14
W7--E13 7
7
8
OUT
1
1
2
IN
W8--E16
W8--E15
8
Figure 60 B840--108 User Configuration
The snubber circuits are disconnected by removing the (JP1- -JP8) appropriate jumper. Refer to the label on the side of the module.
136 B840--108 Relay Output
GM--DISC--800
Page 144
28.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
28.3.1
Terminal Numbering and Output Functions 0--230Vac 0--300Vdc SOURCE
Figure 61 B840--108 Terminal Numbering
Note: Since each output is isolated from the remaining outputs, separate power sources can be used for each load. Each output can be wired for current source or current sink operation. Note: It is possible to have the ACTIVE indicator lit when one or more output channels are working improperly.
GM--DISC--800
B840--108 Relay Output
137
Page 145
28.4 Specifications B840--108 Specifications Description
Reed Relay (NO/NC) output, isolated circuits, sink or source current
Number of Points
8
Operating Voltage
0 ... 300 Vdc max 0 ... 230 Vac max / 47 ... 63 Hz
Number of Groups
8
Outputs/group Maximum Load Current
1 Carrying (unswitched)
3 A max
Switching
2.0 max (0.3 A @ 300 Vdc)
Switching Capability
100 VA max
Contact Resistance
< 150 mW (including fuse, pc clad, wire, connectors, and contacts).
Open Circuit Impedance (Snubber Circuits Connected)
20 KW + 5 KW capacitive reactance @ 60 Hz
Maximum Response Time
OFF ® ON
6 ms (2 ms typical)
ON ® OFF
6 ms (2 ms typical)
+5 V
67 mA
+4.3 V
400 mA
--5 V
0 mA
Power Required
Relay Life Rating
1 billion operations @ rated load @ 25°C
Terminal Connector
AS--8534--000
Fusing
1 / group, 4 A
138 B840--108 Relay Output
GM--DISC--800
Page 146
Chapter 29 B849--016 48 V ac/dc Input
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B849--016 48 V ac/dc Input
139
Page 147
29.1 Overview The B849-016 48 V ac/dc true high input module senses OFF and ON input signals from its field circuitry, converting them to logic levels used by a PLC. The module’s 16 input circuits are divided into two groups of eight channels, each group totally isolated from the other. Although both groups use common return wires, none has a definite relationship to system ground unless established in the user’s field circuitry. Since both groups nominally employ independent power return sources, both ac and dc powered field circuits may input to the module at the same time. Note: Reversal of external signal polarity will not cause channel circuit damage as circuit design is indifferent to accidental polarity reversal.
29.1.1
Simple Block Diagram
TO PLC
Figure 62 B849--016 Simplified Block Diagram
140 B849--016 48 V ac/dc Input
GM--DISC--800
Page 148
When the user’s ac/dc powered field circuit goes ON, as the result of a limit for example, it presents the field power voltage at the modules appropriate input channel. When the input voltage meets or exceeds the module’s guaranteed ON threshold, the resulting voltage turns the channel monitor lamp ON, current flows through the bridge rectifier and subsequently the opto- -isolator (OPTO- -ISOL) circuit. Given a nominal 48 V field power supply and 1000 W maximum input source impedance, the module’s channel monitor lamps will indicate ON and OFF when input voltages are 41 Vac/39 Vdc for the high level ON; and 15 Vac/20 Vdc for the low level OFF respectively. The optical energy goes to the communications board (COMM BOARD) where the OURBUS output register is set to represent the field circuit’s ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the controller. Total scan time by the controller may be as long as 250 mS. You should not attempt to monitor events with a repetition rate greater than 1 / s without analyzing your system, program, and scan time. Note: It is possible to have the ACTIVE indicator lit with one or more input channels working improperly.
GM--DISC--800
B849--016 48 V ac/dc Input
141
Page 149
29.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
29.2.1
Terminal Numbering and Input Functions
+
48 V ac/dc --
+
48 V ac/dc --
Figure 63 B849--016 Terminal Numbering
Note: To use both input groups with a single power supply, jump terminals #9 and #19.
142 B849--016 48 V ac/dc Input
GM--DISC--800
Page 150
29.3 Specifications B849--016 Specifications Description
48 Vac/dc input
Number of Points
16
Operating Voltage
41 ... 53 Vac / 47 ... 63 Hz 39 ... 58 Vdc
Number of Groups
2
Inputs/group
8
Maximum Input Voltage
Continuous
53 Vac / 58 Vdc 63 Vac / 70 Vdc (for 10 s maximum) 110 Vpk (for 10 ms max)
ON Conditions
ON Conditions
> 41 Vac or 39 Vdc w/Inp Source Impedance of 1 K maximum input current 7.5 mA + 2 mA
OFF Conditions
< 15 Vac / 20 Vdc < 53 Vac w/Inp Source Impedance > 25 k < 58 Vdc w/Inp Source Impedance > 50 k
ON Current
GM--DISC--800
8 mA (max), 4.5 mA (minimum)
Maximum Response Time
OFF ® ON
6 ms
ON ® OFF
18 ms
Power Required
+5 V
40 mA
+4.3 V
1 mA
--5 V
15 mA
External Power Supply
48 Vac/dc, 300 mA
Terminal Connector
AS--8534--000
B849--016 48 V ac/dc Input
143