Page 141

28.1 Overview The B840-108 Relay Output Module converts signals from the 800 Series Ourbus to eight independent relay outputs. Each output is capable of driving relays, pilot lamps, or other loads up to 2 A. The module utilizes eight high-reliability mercury-wetted relays to control the loads. Each of the eight outputs is electrically isolated from the I/O bus and from the other seven outputs by the relay coil. These outputs are capable of switching 100 VA maximum instantaneous power associated with ac or dc loads. Such devices may range from relays and pilot lamps to multiplexed low level analog signals. Each output has an RC snubber to protect the mercury wetted contacts from arcing caused by rapid rate of rise of applied voltage from inductive loads upon instantaneous opening of the contacts. The output signals can withstand severe voltage transients that may be encountered in industrial environments - i.e., the voltage transients will not propagate through the relay to the Ourbus, thus protecting all other controller system components from damage. All output circuits are also fused to protect against overload currents.

28.1.1

Simplified Schematic

PLC REMOVABLE

Figure 59 B840--108 Simplified Schematic

134 B840--108 Relay Output

GM--DISC--800

Page 142

The module is user-configurable as to setting up for normally-open or normally-closed operation of the relays as described below. You can also optionally configure the RC snubber circuit to remove it when minimal leakage current applications such as data multiplexing are being used. The logic interface chip samples the eight logic level signals simultaneously from the PLC on each scan and holds these samples to drive the appropriate reed relay coil. Assuming a normally-open jumpered configuration, when the relay coil is energized, the reed relay contacts conduct current from the output A terminal to the output B terminal.

GM--DISC--800

B840--108 Relay Output

135

Page 143

28.2 Configuration The B840- -108 Relay Module is initially shipped with all 8 channels jumpered for the normally- -open configuration with all snubber circuits connected. You may wire any of the channels for either normally- -open or normally- -closed operation by transferring a wire jumper from one tab to another on the printed circuit board to change from normally- -open to normally- -closed (see Figure 60). RELAY CHAN.

N.O. W1--E2

N.C. W1--E1

SNUBBER CHAN.

W2--E4

W3--E6

W2--E3

JP1

JP1

JP2

JP2

3

JP3

JP3

W4--E8

4

JP4

JP4

JP5

JP5

JP6

JP6

JP7

JP7

JP8

JP8

W4--E7

4 W5--E10

2

W3--E5

3

W5--E9 5

5 W6--E12

W6--E11 6

6 W7--E14

W7--E13 7

7

8

OUT

1

1

2

IN

W8--E16

W8--E15

8

Figure 60 B840--108 User Configuration

The snubber circuits are disconnected by removing the (JP1- -JP8) appropriate jumper. Refer to the label on the side of the module.

136 B840--108 Relay Output

GM--DISC--800

Page 144

28.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

28.3.1

Terminal Numbering and Output Functions 0--230Vac 0--300Vdc SOURCE

Figure 61 B840--108 Terminal Numbering

Note: Since each output is isolated from the remaining outputs, separate power sources can be used for each load. Each output can be wired for current source or current sink operation. Note: It is possible to have the ACTIVE indicator lit when one or more output channels are working improperly.

GM--DISC--800

B840--108 Relay Output

137

Page 145

28.4 Specifications B840--108 Specifications Description

Reed Relay (NO/NC) output, isolated circuits, sink or source current

Number of Points

8

Operating Voltage

0 ... 300 Vdc max 0 ... 230 Vac max / 47 ... 63 Hz

Number of Groups

8

Outputs/group Maximum Load Current

1 Carrying (unswitched)

3 A max

Switching

2.0 max (0.3 A @ 300 Vdc)

Switching Capability

100 VA max

Contact Resistance

< 150 mW (including fuse, pc clad, wire, connectors, and contacts).

Open Circuit Impedance (Snubber Circuits Connected)

20 KW + 5 KW capacitive reactance @ 60 Hz

Maximum Response Time

OFF ® ON

6 ms (2 ms typical)

ON ® OFF

6 ms (2 ms typical)

+5 V

67 mA

+4.3 V

400 mA

--5 V

0 mA

Power Required

Relay Life Rating

1 billion operations @ rated load @ 25°C

Terminal Connector

AS--8534--000

Fusing

1 / group, 4 A

138 B840--108 Relay Output

GM--DISC--800

Page 146

Chapter 29 B849--016 48 V ac/dc Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B849--016 48 V ac/dc Input

139

Page 147

29.1 Overview The B849-016 48 V ac/dc true high input module senses OFF and ON input signals from its field circuitry, converting them to logic levels used by a PLC. The module’s 16 input circuits are divided into two groups of eight channels, each group totally isolated from the other. Although both groups use common return wires, none has a definite relationship to system ground unless established in the user’s field circuitry. Since both groups nominally employ independent power return sources, both ac and dc powered field circuits may input to the module at the same time. Note: Reversal of external signal polarity will not cause channel circuit damage as circuit design is indifferent to accidental polarity reversal.

29.1.1

Simple Block Diagram

TO PLC

Figure 62 B849--016 Simplified Block Diagram

140 B849--016 48 V ac/dc Input

GM--DISC--800

Page 148

When the user’s ac/dc powered field circuit goes ON, as the result of a limit for example, it presents the field power voltage at the modules appropriate input channel. When the input voltage meets or exceeds the module’s guaranteed ON threshold, the resulting voltage turns the channel monitor lamp ON, current flows through the bridge rectifier and subsequently the opto- -isolator (OPTO- -ISOL) circuit. Given a nominal 48 V field power supply and 1000 W maximum input source impedance, the module’s channel monitor lamps will indicate ON and OFF when input voltages are 41 Vac/39 Vdc for the high level ON; and 15 Vac/20 Vdc for the low level OFF respectively. The optical energy goes to the communications board (COMM BOARD) where the OURBUS output register is set to represent the field circuit’s ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the controller. Total scan time by the controller may be as long as 250 mS. You should not attempt to monitor events with a repetition rate greater than 1 / s without analyzing your system, program, and scan time. Note: It is possible to have the ACTIVE indicator lit with one or more input channels working improperly.

GM--DISC--800

B849--016 48 V ac/dc Input

141

Page 149

29.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

29.2.1

Terminal Numbering and Input Functions

+

48 V ac/dc --

+

48 V ac/dc --

Figure 63 B849--016 Terminal Numbering

Note: To use both input groups with a single power supply, jump terminals #9 and #19.

142 B849--016 48 V ac/dc Input

GM--DISC--800

Page 150

29.3 Specifications B849--016 Specifications Description

48 Vac/dc input

Number of Points

16

Operating Voltage

41 ... 53 Vac / 47 ... 63 Hz 39 ... 58 Vdc

Number of Groups

2

Inputs/group

8

Maximum Input Voltage

Continuous

53 Vac / 58 Vdc 63 Vac / 70 Vdc (for 10 s maximum) 110 Vpk (for 10 ms max)

ON Conditions

ON Conditions

> 41 Vac or 39 Vdc w/Inp Source Impedance of 1 K maximum input current 7.5 mA + 2 mA

OFF Conditions

< 15 Vac / 20 Vdc < 53 Vac w/Inp Source Impedance > 25 k < 58 Vdc w/Inp Source Impedance > 50 k

ON Current

GM--DISC--800

8 mA (max), 4.5 mA (minimum)

Maximum Response Time

OFF ® ON

6 ms

ON ® OFF

18 ms

Power Required

+5 V

40 mA

+4.3 V

1 mA

--5 V

15 mA

External Power Supply

48 Vac/dc, 300 mA

Terminal Connector

AS--8534--000

B849--016 48 V ac/dc Input

143