Page 131

Chapter 26 B837--016 24 V ac/dc Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B837--016 24 V ac/dc Input

123

Page 132

26.1 Overview The B837-016 24 Vac/Vdc True High input module senses OFF and ON input signals from its field circuitry and converts them to logic levels used by a Modicon PLC. The module’s 16 inputs are separated into two groups of eight channels, each group being totally isolated from the other. Although both groups use common return wires, none has a definite relationship to system ground unless established in the user’s field circuitry. Since both groups nominally employ independent power return sources, both ac and dc powered field circuits may input to the module at the same time.

26.1.1

Simple Block Diagram

TO PLC

Figure 55 B837--016 Simplified Block Diagram

When the user’s ac/dc powered field circuit goes ON - - as the result of a limit switch for example - - it presents the field power voltage at the modules appropriate input channel. When the input voltage meets or exceeds the module’s guaranteed ON threshold, the resulting voltage turns the channel monitor lamp ON, current flows through the bridge rectifier and subsequently the opto-isolator (OPTO-ISOL) circuit.

124 B837--016 24 V ac/dc Input

GM--DISC--800

Page 133

Given a nominal 24 V field power supply and 1000 W maximum input source impedance, the module’s channel monitor lamps will indicate ON and OFF when voltages are 20.4 Vac/19.2 Vdc for the high level ON; and 6 Vac/10 Vdc for the low level OFF respectively. The optical energy goes to the communications board (COMM BOARD) where the Ourbus output register is set to represent the field circuit’s ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the controller. Note: Reversal of external signal polarity will not cause channel circuit damage as circuit design is indifferent to accidental polarity reversal.

GM--DISC--800

B837--016 24 V ac/dc Input

125

Page 134

26.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring. Terminal numbering and their corresponding input functions are presented below in Figure 56.

+

+

24 V ac/dc

24 V ac/dc

--

--

Figure 56 B837--016 Terminal Numbering

Note: To use both input groups with a single power supply, jump terminals #9 and #19.

126 B837--016 24 V ac/dc Input

GM--DISC--800

Page 135

26.3 Specifications B837--016 Specifications Description

24 V ac/dc Input

Number of Points

16

Operating Voltage

20.4 ... 27 Vac / 47 ... 63 Hz; 19.2 ... 30 Vdc

Number of Groups

2

Outputs/group

8

Maximum Input Voltage

Continuous

27 Vac / 30 Vdc

Inrush

32 Vac / 36 Vdc for 10 s 58 V peak 10 ms

ON Conditions

> 20.4 Vac or 19.2 Vdc w/Inp Source Impedance of 1 k maximum input current 10 + 2 mA

OFF Conditions

< 6 Vac / 10 Vdc < 27 Vac w/Inp Source Impedance > 15 k < 30 Vdc w/Inp Source Impedance > 30 k

Input ON Current Maximum Response Time Power Required

GM--DISC--800

10 mA max, 5 mA min OFF ® ON

6 ms

ON ® OFF

18 ms

+5 V

40 mA

+4.3 V

1 mA

--5 V

15 mA

External Power Supply

24 Vac/dc, 300 mA

Terminal Connector

AS--8534--000

B837--016 24 V ac/dc Input

127

Page 136

Chapter 27 B838--032 24 Vdc Output (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B838--032 24 Vdc Output (True High)

129

Page 137

27.1 Overview The B838-032 24 Vdc True High Output Module consists of a four groups of eight outputs for a total of 32 outputs. The B838 converts logic signals used within the PLC into 32 24 Vdc outputs. Outputs are capable of driving relays, pilot lamps, and other loads rated at 1/4 A. Each group of eight share an external supply voltage and is fused at 6.3 A. The outputs are designed to withstand the extreme voltage transients often encountered in an industrial environment.

27.1.1

Simplified Schematic

Figure 57 B838--032 Simplified Schematic

130 B838--032 24 Vdc Output (True High)

GM--DISC--800

Page 138

27.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

27.2.1

Output Connections

24 Vdc 24 Vdc

24 Vdc 24 Vdc

Figure 58 B838--032 Terminal Numbering and Output Connections

Note: If any loads are polarity sensitive, their negative (- -) terminal must be connected to the group return terminal.

GM--DISC--800

B838--032 24 Vdc Output (True High)

131

Page 139

27.3 Specifications B838--032 Specifications Description

24 Vdc output

Type of Operation

True high

Number of Points

32

Operating Voltage

20 ... 30 Vdc

Number of Groups

4

Outputs/group

8

Load Voltage

Load Current

Ripple Voltage

4.0 peak to peak @ 10 kHz or less

Peak Voltage

33 V max

ON State Voltage Drop

1.0 Vdc @ 1/2 A @ full power

Continuous Current

0.50 A max / output, 16 A/module maximum

Surge Current

The surge current of the B838 is 2.5 A for 0.5 ms, and should not be exceeded. If a short circuit (momentary or sustained) exists, the FET on the output may fail prior to the group fuse blowing. Modicon recommends one of the following options to protect the outputs: 1) Add external fuses to each output (1 ... 1.5 A fast blow), 2) Add external current limiting resistors to protect the output FET

Lamp Loads up to 5 W

Inductive Load Clamp Voltage

--20 V nominal

Inductive Clamp Current

1/2 A peak, 0.6 Hz up to 3.0 H

Fast Contactor Turn Off

< 60 ms with 3.0 H load

Off State Leakage Current

1 mA max @ 30 Vdc

Maximum Response Time (Resistive Load)

OFF ® ON

1 ms

ON ® OFF

1 ms

Power Required

+5 V

160 mA

+4.3 V

1 mA

--5 V

0 mA

External Power Supply

24 Vdc + 4 V, 125 mA (excluding field load current)

Terminal Connector

AS--8535--000

132 B838--032 24 Vdc Output (True High)

GM--DISC--800

Page 140

Chapter 28 B840--108 Relay Output

GM--DISC--800

V

Overview

V

Configuration

V

Field Connections

V

Specifications

B840--108 Relay Output

133