Page 131
Chapter 26 B837--016 24 V ac/dc Input
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B837--016 24 V ac/dc Input
123
Page 132
26.1 Overview The B837-016 24 Vac/Vdc True High input module senses OFF and ON input signals from its field circuitry and converts them to logic levels used by a Modicon PLC. The module’s 16 inputs are separated into two groups of eight channels, each group being totally isolated from the other. Although both groups use common return wires, none has a definite relationship to system ground unless established in the user’s field circuitry. Since both groups nominally employ independent power return sources, both ac and dc powered field circuits may input to the module at the same time.
26.1.1
Simple Block Diagram
TO PLC
Figure 55 B837--016 Simplified Block Diagram
When the user’s ac/dc powered field circuit goes ON - - as the result of a limit switch for example - - it presents the field power voltage at the modules appropriate input channel. When the input voltage meets or exceeds the module’s guaranteed ON threshold, the resulting voltage turns the channel monitor lamp ON, current flows through the bridge rectifier and subsequently the opto-isolator (OPTO-ISOL) circuit.
124 B837--016 24 V ac/dc Input
GM--DISC--800
Page 133
Given a nominal 24 V field power supply and 1000 W maximum input source impedance, the module’s channel monitor lamps will indicate ON and OFF when voltages are 20.4 Vac/19.2 Vdc for the high level ON; and 6 Vac/10 Vdc for the low level OFF respectively. The optical energy goes to the communications board (COMM BOARD) where the Ourbus output register is set to represent the field circuit’s ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the controller. Note: Reversal of external signal polarity will not cause channel circuit damage as circuit design is indifferent to accidental polarity reversal.
GM--DISC--800
B837--016 24 V ac/dc Input
125
Page 134
26.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring. Terminal numbering and their corresponding input functions are presented below in Figure 56.
+
+
24 V ac/dc
24 V ac/dc
--
--
Figure 56 B837--016 Terminal Numbering
Note: To use both input groups with a single power supply, jump terminals #9 and #19.
126 B837--016 24 V ac/dc Input
GM--DISC--800
Page 135
26.3 Specifications B837--016 Specifications Description
24 V ac/dc Input
Number of Points
16
Operating Voltage
20.4 ... 27 Vac / 47 ... 63 Hz; 19.2 ... 30 Vdc
Number of Groups
2
Outputs/group
8
Maximum Input Voltage
Continuous
27 Vac / 30 Vdc
Inrush
32 Vac / 36 Vdc for 10 s 58 V peak 10 ms
ON Conditions
> 20.4 Vac or 19.2 Vdc w/Inp Source Impedance of 1 k maximum input current 10 + 2 mA
OFF Conditions
< 6 Vac / 10 Vdc < 27 Vac w/Inp Source Impedance > 15 k < 30 Vdc w/Inp Source Impedance > 30 k
Input ON Current Maximum Response Time Power Required
GM--DISC--800
10 mA max, 5 mA min OFF ® ON
6 ms
ON ® OFF
18 ms
+5 V
40 mA
+4.3 V
1 mA
--5 V
15 mA
External Power Supply
24 Vac/dc, 300 mA
Terminal Connector
AS--8534--000
B837--016 24 V ac/dc Input
127
Page 136
Chapter 27 B838--032 24 Vdc Output (True High)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B838--032 24 Vdc Output (True High)
129
Page 137
27.1 Overview The B838-032 24 Vdc True High Output Module consists of a four groups of eight outputs for a total of 32 outputs. The B838 converts logic signals used within the PLC into 32 24 Vdc outputs. Outputs are capable of driving relays, pilot lamps, and other loads rated at 1/4 A. Each group of eight share an external supply voltage and is fused at 6.3 A. The outputs are designed to withstand the extreme voltage transients often encountered in an industrial environment.
27.1.1
Simplified Schematic
Figure 57 B838--032 Simplified Schematic
130 B838--032 24 Vdc Output (True High)
GM--DISC--800
Page 138
27.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
27.2.1
Output Connections
24 Vdc 24 Vdc
24 Vdc 24 Vdc
Figure 58 B838--032 Terminal Numbering and Output Connections
Note: If any loads are polarity sensitive, their negative (- -) terminal must be connected to the group return terminal.
GM--DISC--800
B838--032 24 Vdc Output (True High)
131
Page 139
27.3 Specifications B838--032 Specifications Description
24 Vdc output
Type of Operation
True high
Number of Points
32
Operating Voltage
20 ... 30 Vdc
Number of Groups
4
Outputs/group
8
Load Voltage
Load Current
Ripple Voltage
4.0 peak to peak @ 10 kHz or less
Peak Voltage
33 V max
ON State Voltage Drop
1.0 Vdc @ 1/2 A @ full power
Continuous Current
0.50 A max / output, 16 A/module maximum
Surge Current
The surge current of the B838 is 2.5 A for 0.5 ms, and should not be exceeded. If a short circuit (momentary or sustained) exists, the FET on the output may fail prior to the group fuse blowing. Modicon recommends one of the following options to protect the outputs: 1) Add external fuses to each output (1 ... 1.5 A fast blow), 2) Add external current limiting resistors to protect the output FET
Lamp Loads up to 5 W
Inductive Load Clamp Voltage
--20 V nominal
Inductive Clamp Current
1/2 A peak, 0.6 Hz up to 3.0 H
Fast Contactor Turn Off
< 60 ms with 3.0 H load
Off State Leakage Current
1 mA max @ 30 Vdc
Maximum Response Time (Resistive Load)
OFF ® ON
1 ms
ON ® OFF
1 ms
Power Required
+5 V
160 mA
+4.3 V
1 mA
--5 V
0 mA
External Power Supply
24 Vdc + 4 V, 125 mA (excluding field load current)
Terminal Connector
AS--8535--000
132 B838--032 24 Vdc Output (True High)
GM--DISC--800
Page 140
Chapter 28 B840--108 Relay Output
GM--DISC--800
V
Overview
V
Configuration
V
Field Connections
V
Specifications
B840--108 Relay Output