Page 121
Chapter 24 B833--016 24 Vdc Input (True Low)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B833--016 24 Vdc Input (True Low)
113
Page 122
24.1 Overview The Modicon B833-016 24 Vdc Input Module (True Low) consists of two groups of eight independent inputs. The B833 senses and converts switched input signals into logic voltage levels used by the PLC. Inputs can be received from push buttons, limit and proximity switches, and other 24 Vdc sources. The module provides 16 inputs that share an external power supply. Input voltages are sensed by comparing the incoming voltage against a fixed threshold.
24.1.1
Simplified Schematic
Figure 50 B833--016 Simplified Schematic
114
B833--016 24 Vdc Input (True Low)
GM--DISC--800
Page 123
24.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
24.2.1
Input Connections
Figure 51 B833--016 Terminal Numbering and Input Connections
GM--DISC--800
B833--016 24 Vdc Input (True Low)
115
Page 124
24.3 Specifications B833--016 Specifications
116
Description
24 Vdc true low input
Type of Operation
True low
Number of Points
16
Operating Voltage
20 ... 28 Vdc
Number of Groups
2
Outputs/group
8
Maximum Input Voltage
100 Vdc for 3 ms
ON Conditions
< 2.6 Vdc or .13 of Vs, whichever is greater. 200 W max resistance to common. Input indicator ON.
OFF Conditions
> 21 Vdc or .75 of Vs, whichever is less. 10,000 W min resistance to common. Input indicator OFF.
Maximum Input Voltage
100 V for 3 mS
ON Current
6 mA (typical) @ 24 Vdc
Maximum Response Time
OFF ® ON
11 ms
ON ® OFF
11 ms
Power Required
+5 V
27 mA
+4.3 V
2 mA
--5 V
0 mA
External Power Supply
24 Vdc, + 4 V, 300 mA (Excluding field load current)
Terminal Connector
AS--8534--000
B833--016 24 Vdc Input (True Low)
GM--DISC--800
Page 125
Chapter 25 B836--016 12 ... 250 Vdc Isolated Output
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B836--016 12 ... 250 Vdc Isolated Output
117
Page 126
25.1 Overview The B836-016 12 ... 250 Vdc Isolated Output Module accepts up to 16 signals from a Modicon PLC and converts them to independent outputs. The module’s essential function is to switch one or more field circuits OFF and ON as signalled by the PLC. At any given time, one or more output channel’s signals may be in a true high configuration while one or more of the remaining output channel’s signals are in a true low configuration. The output signals are capable or driving displays, relays, lamps, or any load connected to a 12 ... 250 Vdc user supplied voltage source. Finally, the module is fused against overload currents and protected from accidental polarity reversal. Since all of the16 circuits are the same, describing one circuit’s function describes the module’s function. Data commands from the controller are shipped via OURBUS to the OBS communications chip in the B836 module via Modicon’s standard data interface. The OBS chip directs the signal to the addressed channel which in turn feeds the transistor driver, couples through the ISOGATE and turns the field effect transistor (FET) switch on. Since the circuit is completely floating arrangement, it is equally useful in a true high (sourcing) or true low (sinking) configuration.
118
B836--016 12 ... 250 Vdc Isolated Output
GM--DISC--800
Page 127
25.1.1
Simple Block Diagram
Figure 52 B836--016 Simplified Block Diagram
Caution: Certain large inductive load conditions may require external reverse diodes placed directly across the load for complete circuit protection.
GM--DISC--800
B836--016 12 ... 250 Vdc Isolated Output
119
Page 128
25.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
25.2.1
Terminal Numbering and Output Functions
Figure 53 B836--016 Terminal Numbering
120 B836--016 12 ... 250 Vdc Isolated Output
GM--DISC--800
Page 129
25.2.2
Typical User-side Field Connector Circuitry
Figure 54 B836--016 Typical Field Circuit Connections
GM--DISC--800
B836--016 12 ... 250 Vdc Isolated Output
121
Page 130
25.3 Specifications B836--016 Specifications Description
12 ... 250 Vdc isolated output
Number of Points
16
Operating Voltage
12 ... 250 Vdc
Number of Groups
16
Outputs/group
1
Maximum Load Current
0.75 A (typical) @ 250 Vdc 1 A (typical) @ 125 Vdc 1.5 A (typical) @ 48 Vdc
Surge Current
5.0 A max (for 10 mS @ 1 s repetition rate)
Maximum OFF Leakage Current
1 mA
Maximum Load Current
5 mA
ON State Voltage Drop
3.0V max @ 1.50 A
Maximum Output Current
8.0 A dc total switched current (all channels cumulative)
Minimum Output Current
15.0 mA dc (lower current does not guarantee indicator operation)
Maximum Response Time Power Required
OFF ® ON
1 ms
ON ® OFF
5 ms
+5 V
50 mA
+4.3 V
603 mA
--5 V
0 mA
Terminal Connector
AS--8535--000
Fusing
1/group, 4 A
122 B836--016 12 ... 250 Vdc Isolated Output
GM--DISC--800