Page 121

Chapter 24 B833--016 24 Vdc Input (True Low)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B833--016 24 Vdc Input (True Low)

113

Page 122

24.1 Overview The Modicon B833-016 24 Vdc Input Module (True Low) consists of two groups of eight independent inputs. The B833 senses and converts switched input signals into logic voltage levels used by the PLC. Inputs can be received from push buttons, limit and proximity switches, and other 24 Vdc sources. The module provides 16 inputs that share an external power supply. Input voltages are sensed by comparing the incoming voltage against a fixed threshold.

24.1.1

Simplified Schematic

Figure 50 B833--016 Simplified Schematic

114

B833--016 24 Vdc Input (True Low)

GM--DISC--800

Page 123

24.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

24.2.1

Input Connections

Figure 51 B833--016 Terminal Numbering and Input Connections

GM--DISC--800

B833--016 24 Vdc Input (True Low)

115

Page 124

24.3 Specifications B833--016 Specifications

116

Description

24 Vdc true low input

Type of Operation

True low

Number of Points

16

Operating Voltage

20 ... 28 Vdc

Number of Groups

2

Outputs/group

8

Maximum Input Voltage

100 Vdc for 3 ms

ON Conditions

< 2.6 Vdc or .13 of Vs, whichever is greater. 200 W max resistance to common. Input indicator ON.

OFF Conditions

> 21 Vdc or .75 of Vs, whichever is less. 10,000 W min resistance to common. Input indicator OFF.

Maximum Input Voltage

100 V for 3 mS

ON Current

6 mA (typical) @ 24 Vdc

Maximum Response Time

OFF ® ON

11 ms

ON ® OFF

11 ms

Power Required

+5 V

27 mA

+4.3 V

2 mA

--5 V

0 mA

External Power Supply

24 Vdc, + 4 V, 300 mA (Excluding field load current)

Terminal Connector

AS--8534--000

B833--016 24 Vdc Input (True Low)

GM--DISC--800

Page 125

Chapter 25 B836--016 12 ... 250 Vdc Isolated Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B836--016 12 ... 250 Vdc Isolated Output

117

Page 126

25.1 Overview The B836-016 12 ... 250 Vdc Isolated Output Module accepts up to 16 signals from a Modicon PLC and converts them to independent outputs. The module’s essential function is to switch one or more field circuits OFF and ON as signalled by the PLC. At any given time, one or more output channel’s signals may be in a true high configuration while one or more of the remaining output channel’s signals are in a true low configuration. The output signals are capable or driving displays, relays, lamps, or any load connected to a 12 ... 250 Vdc user supplied voltage source. Finally, the module is fused against overload currents and protected from accidental polarity reversal. Since all of the16 circuits are the same, describing one circuit’s function describes the module’s function. Data commands from the controller are shipped via OURBUS to the OBS communications chip in the B836 module via Modicon’s standard data interface. The OBS chip directs the signal to the addressed channel which in turn feeds the transistor driver, couples through the ISOGATE and turns the field effect transistor (FET) switch on. Since the circuit is completely floating arrangement, it is equally useful in a true high (sourcing) or true low (sinking) configuration.

118

B836--016 12 ... 250 Vdc Isolated Output

GM--DISC--800

Page 127

25.1.1

Simple Block Diagram

Figure 52 B836--016 Simplified Block Diagram

Caution: Certain large inductive load conditions may require external reverse diodes placed directly across the load for complete circuit protection.

GM--DISC--800

B836--016 12 ... 250 Vdc Isolated Output

119

Page 128

25.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

25.2.1

Terminal Numbering and Output Functions

Figure 53 B836--016 Terminal Numbering

120 B836--016 12 ... 250 Vdc Isolated Output

GM--DISC--800

Page 129

25.2.2

Typical User-side Field Connector Circuitry

Figure 54 B836--016 Typical Field Circuit Connections

GM--DISC--800

B836--016 12 ... 250 Vdc Isolated Output

121

Page 130

25.3 Specifications B836--016 Specifications Description

12 ... 250 Vdc isolated output

Number of Points

16

Operating Voltage

12 ... 250 Vdc

Number of Groups

16

Outputs/group

1

Maximum Load Current

0.75 A (typical) @ 250 Vdc 1 A (typical) @ 125 Vdc 1.5 A (typical) @ 48 Vdc

Surge Current

5.0 A max (for 10 mS @ 1 s repetition rate)

Maximum OFF Leakage Current

1 mA

Maximum Load Current

5 mA

ON State Voltage Drop

3.0V max @ 1.50 A

Maximum Output Current

8.0 A dc total switched current (all channels cumulative)

Minimum Output Current

15.0 mA dc (lower current does not guarantee indicator operation)

Maximum Response Time Power Required

OFF ® ON

1 ms

ON ® OFF

5 ms

+5 V

50 mA

+4.3 V

603 mA

--5 V

0 mA

Terminal Connector

AS--8535--000

Fusing

1/group, 4 A

122 B836--016 12 ... 250 Vdc Isolated Output

GM--DISC--800