Page 111

21.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

21.2.1

Output Connections

Figure 45 B828--016 Terminal Numbering and Output Connections

GM--DISC--800

B828--016 5 V TTL Output

103

Page 112

21.3 Specifications B828--016 Specifications Description

5 V TTL output

Number of Points

16

Operating Voltage

5 V TTL

Number of Groups

1

Outputs / Group

16

ON Level

4.0 Vdc min @ 1mA source, 5 Vdc supply @ 4.75 Vdc

OFF Level

0.4 Vdc max @ 75 mA rated current: sinking 75 mA max., continuous, 100 mA peak (10 ms, 20% duty cycle)

Maximum Response Time

OFF ® ON

1 ms

ON ® OFF

1 ms

Power Required

+5 V

32 mA

+4.3 V

220 mA

--5 V

0 mA

External Power Supply

5.0 +0.25 Vdc 600 mA max outputs ON

Terminal Connector

AS--8534--000

Fusing

One/group, 1.5 A

104 B828--016 5 V TTL Output

GM--DISC--800

Page 113

Chapter 22 B829--116 5 V TTL Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B829--116 5 V TTL Input

105

Page 114

22.1 Overview The B829-116 fast response 5 V TTL Input Module converts signals from 16 independent 5 V logic-compatible inputs into signals used by the PLC. Each input is capable of conditioning signals from TTL devices or DTL devices for use by the PLC.

22.1.1

Simplified Schematic

Figure 46 B829--116 Simplified Schematic

106 B829--116 5 V TTL Input

GM--DISC--800

Page 115

22.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

22.2.1

Input Connections

Figure 47 B829--116 Terminal Numbering and Input Connections

GM--DISC--800

B829--116 5 V TTL Input

107

Page 116

22.3 Specifications B829--116 Specifications Description

5 V TTL16-point

Number of Points

16

Operating Voltage

5V

Number of Groups

1

Outputs / Group Input Ratings

16 ON Level

VIH = 2.0 Vdc (minimum) IIL = 0.1 mA (max) @ VIH = 5.5 Vdc V (source) = 5.0 Vdc V (max input) = 8.0 V I (max positive clamp) = 25 mA

OFF Level

VIL = 0.8 Vdc (maximum) IIL = 1.1 mA (maximum) @ V (source) = 5.25 Vdc and VIL = 0.0 V V (max negative input) = --2 Vdc 1 (max negative clamp) = 15 mA

Transient Voltage

100 V for 10 ms

Maximum Response Time

OFF ® ON

1 ms

ON ® OFF

1 ms

Power Required

+5 V

21 mA

+4.3 V

1 mA

--5 V

0 mA

External Power Supply

5.0 +0.25 Vdc, 325 mA all inputs ON

Terminal Connector

AS--8534--000

108 B829--116 5 V TTL Input

GM--DISC--800

Page 117

Chapter 23 B832--016 24 Vdc Output (True Low)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B832--016 24 Vdc Output (True Low)

109

Page 118

23.1 Overview The Modicon B832-016 24 Vdc Output Module (True Low) consists of a single group of 16 independent outputs. The B832 converts signals used within the PLC into 16 independent 24 Vdc outputs. These outputs are capable of driving indicators, relays, and a variety of other loads. There are 16 transistor switches, which are used to control loads connected to an external power source.

23.1.1

Simplified Schematic

Figure 48 B832--016 Simplified Schematic

110

B832--016 24 Vdc Output (True Low)

GM--DISC--800

Page 119

23.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

23.2.1

Output Connections

--

+24 Vdc Supply

Figure 49 B832--016 Terminal Numbering and Output Connections

GM--DISC--800

B832--016 24 Vdc Output (True Low)

111

Page 120

23.3 Specifications B832--016 Specifications Description

24 Vdc output

Type of Operation

True low

Number of Points

16

Operating Voltage

20 ... 28 Vdc

Peak Voltage

33 Vdc for 1 s

Number of Groups

2

Outputs/group On Current

250 mA

Surge Current

1 A for 10 ms

Maximum/group

2A

Maximum/module

4A

Off Current

0.5 mA maximum

On Voltage Drop

0.5 Vdc maximum/output @ 250 mA

Maximum Response Time Power Required

112

8 Maximum/point

OFF ® ON

1 ms

ON ® OFF

1 ms

+5 V

32 mA

+4.3 V

235 mA

--5 V

0 mA

External Power Supply

24 Vdc +4 V, 600 mA maximum (excluding field load current)

Terminal Connector

AS--8534--000

Fusing

1/module, 6 A

B832--016 24 Vdc Output (True Low)

GM--DISC--800