Page 111
21.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
21.2.1
Output Connections
Figure 45 B828--016 Terminal Numbering and Output Connections
GM--DISC--800
B828--016 5 V TTL Output
103
Page 112
21.3 Specifications B828--016 Specifications Description
5 V TTL output
Number of Points
16
Operating Voltage
5 V TTL
Number of Groups
1
Outputs / Group
16
ON Level
4.0 Vdc min @ 1mA source, 5 Vdc supply @ 4.75 Vdc
OFF Level
0.4 Vdc max @ 75 mA rated current: sinking 75 mA max., continuous, 100 mA peak (10 ms, 20% duty cycle)
Maximum Response Time
OFF ® ON
1 ms
ON ® OFF
1 ms
Power Required
+5 V
32 mA
+4.3 V
220 mA
--5 V
0 mA
External Power Supply
5.0 +0.25 Vdc 600 mA max outputs ON
Terminal Connector
AS--8534--000
Fusing
One/group, 1.5 A
104 B828--016 5 V TTL Output
GM--DISC--800
Page 113
Chapter 22 B829--116 5 V TTL Input
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B829--116 5 V TTL Input
105
Page 114
22.1 Overview The B829-116 fast response 5 V TTL Input Module converts signals from 16 independent 5 V logic-compatible inputs into signals used by the PLC. Each input is capable of conditioning signals from TTL devices or DTL devices for use by the PLC.
22.1.1
Simplified Schematic
Figure 46 B829--116 Simplified Schematic
106 B829--116 5 V TTL Input
GM--DISC--800
Page 115
22.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
22.2.1
Input Connections
Figure 47 B829--116 Terminal Numbering and Input Connections
GM--DISC--800
B829--116 5 V TTL Input
107
Page 116
22.3 Specifications B829--116 Specifications Description
5 V TTL16-point
Number of Points
16
Operating Voltage
5V
Number of Groups
1
Outputs / Group Input Ratings
16 ON Level
VIH = 2.0 Vdc (minimum) IIL = 0.1 mA (max) @ VIH = 5.5 Vdc V (source) = 5.0 Vdc V (max input) = 8.0 V I (max positive clamp) = 25 mA
OFF Level
VIL = 0.8 Vdc (maximum) IIL = 1.1 mA (maximum) @ V (source) = 5.25 Vdc and VIL = 0.0 V V (max negative input) = --2 Vdc 1 (max negative clamp) = 15 mA
Transient Voltage
100 V for 10 ms
Maximum Response Time
OFF ® ON
1 ms
ON ® OFF
1 ms
Power Required
+5 V
21 mA
+4.3 V
1 mA
--5 V
0 mA
External Power Supply
5.0 +0.25 Vdc, 325 mA all inputs ON
Terminal Connector
AS--8534--000
108 B829--116 5 V TTL Input
GM--DISC--800
Page 117
Chapter 23 B832--016 24 Vdc Output (True Low)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B832--016 24 Vdc Output (True Low)
109
Page 118
23.1 Overview The Modicon B832-016 24 Vdc Output Module (True Low) consists of a single group of 16 independent outputs. The B832 converts signals used within the PLC into 16 independent 24 Vdc outputs. These outputs are capable of driving indicators, relays, and a variety of other loads. There are 16 transistor switches, which are used to control loads connected to an external power source.
23.1.1
Simplified Schematic
Figure 48 B832--016 Simplified Schematic
110
B832--016 24 Vdc Output (True Low)
GM--DISC--800
Page 119
23.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
23.2.1
Output Connections
--
+24 Vdc Supply
Figure 49 B832--016 Terminal Numbering and Output Connections
GM--DISC--800
B832--016 24 Vdc Output (True Low)
111
Page 120
23.3 Specifications B832--016 Specifications Description
24 Vdc output
Type of Operation
True low
Number of Points
16
Operating Voltage
20 ... 28 Vdc
Peak Voltage
33 Vdc for 1 s
Number of Groups
2
Outputs/group On Current
250 mA
Surge Current
1 A for 10 ms
Maximum/group
2A
Maximum/module
4A
Off Current
0.5 mA maximum
On Voltage Drop
0.5 Vdc maximum/output @ 250 mA
Maximum Response Time Power Required
112
8 Maximum/point
OFF ® ON
1 ms
ON ® OFF
1 ms
+5 V
32 mA
+4.3 V
235 mA
--5 V
0 mA
External Power Supply
24 Vdc +4 V, 600 mA maximum (excluding field load current)
Terminal Connector
AS--8534--000
Fusing
1/module, 6 A
B832--016 24 Vdc Output (True Low)
GM--DISC--800