Page 101

19.1 Overview The Modicon B826-032 24 Vdc True High Output Module consists of a single group of 32 independent outputs. The B826 converts logic signals used within the PLC into 32 independent 24 Vdc outputs. Outputs are capable of driving relays, pilot lamps, and other loads rated at 1/4 A. The outputs share an external supply voltage and are protected against overload currents by a single fuse.

19.1.1

Simplified Schematic

Figure 40 B826--032 Simplified Schematic

92

B826--032 24 Vdc Output (True High)

GM--DISC--800

Page 102

Note: Due to its high density and compact design, the module is specifically designed for use in applications such as driving individual pilot lamps, LED displays, or other noncritical loads.

GM--DISC--800

B826--032 24 Vdc Output (True High)

93

Page 103

19.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

19.2.1

Output Connections

Figure 41 B826--032 Terminal Numbering and Output Connections

Note: If any loads are polarity sensitive, their negative (- -) terminal must be connected to the common bus.

94

B826--032 24 Vdc Output (True High)

GM--DISC--800

Page 104

19.3 Specifications B826--032 Specifications Description

24 Vdc output

Type of Operation

True high

Number of Points

32

Operating Voltage

20.4 ... 28.8 Vdc

Number of Groups

1

Outputs/group

32

On Current

Maximum/point

0.25 A

Maximum/module

8A

Maximum/group

8A

Surge Current

2.5A max for .5 mS

Off State Leakage Current

0.1 mA (typical) @ 24 Vdc 0.75 mA max @ 28.8 Vdc

Maximum Response Time

OFF ® ON

1 ms

ON ® OFF

1 ms

Ripple Voltage

+ 1.2V max

Peak Voltage

32V max for 10 mS

On State Voltage Drop Power Required

GM--DISC--800

0.7 Vdc max +5 V

90 mA

+4.3 V

1 mA

--5 V

0 mA

External Power Supply

24 Vdc, 600 mA max (Excluding field load current) 24 Vdc, 540 mA typical

Terminal Connector

AS--8535--000

Fuse

One/group, 12 A

B826--032 24 Vdc Output (True High)

95

Page 105

Chapter 20 B827--032 24 Vdc Input (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B827--032 24 Vdc Input (True High)

97

Page 106

20.1 Overview The Modicon B827-032 24 Vdc True High Input Module consists of a single group of 32 independent inputs. The B827 senses and converts switched input signals into logic voltage levels used by the PLC. Inputs can be received from push buttons, limit and proximity switches, and other 24 Vdc sources. The B827 provides 32 inputs that share an external supply voltage. Input voltages are sensed by comparing the incoming voltage against a fixed threshold. The threshold is a function of the user- -supplied field voltage.

20.1.1

Simplified Schematic 0.25A

+3V

Figure 42 B827--032 Simplified Schematic

98

B827--032 24 Vdc Input (True High)

GM--DISC--800

Page 107

20.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

20.2.1

Input Connections

Figure 43 B827--032 Terminal Numbering and Input Connections

GM--DISC--800

B827--032 24 Vdc Input (True High)

99

Page 108

20.3 Specifications B827--032 Specifications Description

24 Vdc high density input

Type of Operation

True high

Number of Points

32

Operating Voltage

18 ... 30 Vdc

Number of Groups

1

Outputs/group

32

ON Level Input Voltage

>22.5 Vdc or .75 of Vs, whichever is less

OFF Level Input Voltage

<4.5 Vdc or .25 of Vs, whichever is greater

Input Resistance

On State

8 ... 11 kW

Off State

6 ... 8 kW

Maximum Response Time

OFF ® ON

0.4 ms

ON ® OFF

1 ms

Power Required

+5 V

30 mA

+4.3 V

1 mA

--5 V

0 mA

Supply Voltage

18 ... 30 Vdc continuous 40 Vdc peak for 10 ms surge

Supply Current

60mA max over an 18 ... 30 Vdc range

External Power Supply

Terminal Connector

AS--8535--000

Fuse

0.25 A

100 B827--032 24 Vdc Input (True High)

GM--DISC--800

Page 109

Chapter 21 B828--016 5 V TTL Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B828--016 5 V TTL Output

101

Page 110

21.1 Overview The B828-016 5 V TTL Output Module converts logic signals used within the controller into sixteen independent 5 V TTL outputs. These outputs are compatible with TTL and DTL logic as well as other loads such as LED displays. The module uses sixteen transistor switches which are capable of sinking load currents up to 75 mA supplied from an external 5 Vdc power source.

21.1.1

Simplified Schematic

Figure 44 B828--016 Simplified Schematic

102 B828--016 5 V TTL Output