Page 101
19.1 Overview The Modicon B826-032 24 Vdc True High Output Module consists of a single group of 32 independent outputs. The B826 converts logic signals used within the PLC into 32 independent 24 Vdc outputs. Outputs are capable of driving relays, pilot lamps, and other loads rated at 1/4 A. The outputs share an external supply voltage and are protected against overload currents by a single fuse.
19.1.1
Simplified Schematic
Figure 40 B826--032 Simplified Schematic
92
B826--032 24 Vdc Output (True High)
GM--DISC--800
Page 102
Note: Due to its high density and compact design, the module is specifically designed for use in applications such as driving individual pilot lamps, LED displays, or other noncritical loads.
GM--DISC--800
B826--032 24 Vdc Output (True High)
93
Page 103
19.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
19.2.1
Output Connections
Figure 41 B826--032 Terminal Numbering and Output Connections
Note: If any loads are polarity sensitive, their negative (- -) terminal must be connected to the common bus.
94
B826--032 24 Vdc Output (True High)
GM--DISC--800
Page 104
19.3 Specifications B826--032 Specifications Description
24 Vdc output
Type of Operation
True high
Number of Points
32
Operating Voltage
20.4 ... 28.8 Vdc
Number of Groups
1
Outputs/group
32
On Current
Maximum/point
0.25 A
Maximum/module
8A
Maximum/group
8A
Surge Current
2.5A max for .5 mS
Off State Leakage Current
0.1 mA (typical) @ 24 Vdc 0.75 mA max @ 28.8 Vdc
Maximum Response Time
OFF ® ON
1 ms
ON ® OFF
1 ms
Ripple Voltage
+ 1.2V max
Peak Voltage
32V max for 10 mS
On State Voltage Drop Power Required
GM--DISC--800
0.7 Vdc max +5 V
90 mA
+4.3 V
1 mA
--5 V
0 mA
External Power Supply
24 Vdc, 600 mA max (Excluding field load current) 24 Vdc, 540 mA typical
Terminal Connector
AS--8535--000
Fuse
One/group, 12 A
B826--032 24 Vdc Output (True High)
95
Page 105
Chapter 20 B827--032 24 Vdc Input (True High)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B827--032 24 Vdc Input (True High)
97
Page 106
20.1 Overview The Modicon B827-032 24 Vdc True High Input Module consists of a single group of 32 independent inputs. The B827 senses and converts switched input signals into logic voltage levels used by the PLC. Inputs can be received from push buttons, limit and proximity switches, and other 24 Vdc sources. The B827 provides 32 inputs that share an external supply voltage. Input voltages are sensed by comparing the incoming voltage against a fixed threshold. The threshold is a function of the user- -supplied field voltage.
20.1.1
Simplified Schematic 0.25A
+3V
Figure 42 B827--032 Simplified Schematic
98
B827--032 24 Vdc Input (True High)
GM--DISC--800
Page 107
20.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
20.2.1
Input Connections
Figure 43 B827--032 Terminal Numbering and Input Connections
GM--DISC--800
B827--032 24 Vdc Input (True High)
99
Page 108
20.3 Specifications B827--032 Specifications Description
24 Vdc high density input
Type of Operation
True high
Number of Points
32
Operating Voltage
18 ... 30 Vdc
Number of Groups
1
Outputs/group
32
ON Level Input Voltage
>22.5 Vdc or .75 of Vs, whichever is less
OFF Level Input Voltage
<4.5 Vdc or .25 of Vs, whichever is greater
Input Resistance
On State
8 ... 11 kW
Off State
6 ... 8 kW
Maximum Response Time
OFF ® ON
0.4 ms
ON ® OFF
1 ms
Power Required
+5 V
30 mA
+4.3 V
1 mA
--5 V
0 mA
Supply Voltage
18 ... 30 Vdc continuous 40 Vdc peak for 10 ms surge
Supply Current
60mA max over an 18 ... 30 Vdc range
External Power Supply
Terminal Connector
AS--8535--000
Fuse
0.25 A
100 B827--032 24 Vdc Input (True High)
GM--DISC--800
Page 109
Chapter 21 B828--016 5 V TTL Output
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B828--016 5 V TTL Output
101
Page 110
21.1 Overview The B828-016 5 V TTL Output Module converts logic signals used within the controller into sixteen independent 5 V TTL outputs. These outputs are compatible with TTL and DTL logic as well as other loads such as LED displays. The module uses sixteen transistor switches which are capable of sinking load currents up to 75 mA supplied from an external 5 Vdc power source.
21.1.1
Simplified Schematic
Figure 44 B828--016 Simplified Schematic
102 B828--016 5 V TTL Output
GM--DISC--800