Page 91
Maximum Input Voltage
Continuous
10 ... 60 Vdc
Maximum Response Time
OFF ® ON
2.5 ms min, 11 ms max
ON ® OFF
2.5 ms min, 11 ms max
+5 V
27 mA
+4.3 V
1 mA
--5 V
10 mA
Power Required
External Supply
10 ... 60 Vdc (Excluding Input Current)
External Supply Current/group
2 mA (max) @ 10 Vdc 5 mA (max) @ 24 Vdc 10 mA (max) @ 48 Vdc 12 mA (max) @ 60 Vdc
Terminal Connector
GM--DISC--800
AS--8534--000
B821--108 10 ... 60 Vdc Input (True High)
81
Page 92
Chapter 17 B824--016 24 Vdc Output (True High)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B824--016 24 Vdc Output (True High)
83
Page 93
17.1 Overview The Modicon B824-016 24 Vdc True High Output Module consists of sixteen independent outputs divided into two groups of eight. The B824 converts signals used within the PLC into 16 independent outputs. Outputs are capable of driving motor starters, relays, and a variety of other loads. There are 16 transistor switches which are used to control loads connected to external power source. The module’s 16 outputs are in two groups, eight outputs per group. Each group is fused to protect the outputs from overload currents and polarity reversal.
17.1.1
Simplified Schematic
Figure 36 B824--016 Simplified Schematic
84
B824--016 24 Vdc Output (True High)
GM--DISC--800
Page 94
17.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
17.2.1
Output Connections
R
R
Figure 37 B824--016 Terminal Numbering and Output Connections
GM--DISC--800
B824--016 24 Vdc Output (True High)
85
Page 95
17.3 Specifications B824--016 Specifications Description
24 Vdc output
Type of Operation
True high
Number of Points
16
Operating Voltage
20 ... 28 Vdc
Number of Groups
2
Outputs/group
8
On Current
86
Maximum/point
2 A continuous
Maximum Surge
5 A for 10 ms
Maximum/group
6A
Maximum/module
12 A
ON State
Voltage Drop
1.8 Vdc @ 2 A
OFF State
Leakage Current
1 mA (max) @ 24 Vdc
Maximum Response Time
OFF ® ON
1 ms
ON ® OFF
1 ms
Power Required
+5 V
32 mA
+4.3 V
260 mA
--5 V
0 mA
External Power Supply
24Vdc +4 V, 175 mA -- Polarity Protected (Excluding field load current)
Terminal Connector
AS--8534--000
Fusing
One / group, 8 A
B824--016 24 Vdc Output (True High)
GM--DISC--800
Page 96
Chapter 18 B825--016 24 Vdc Input (True High)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B825--016 24 Vdc Input (True High)
87
Page 97
18.1 Overview The Modicon B825- -016 24 Vdc True High Input Module consists of a single group of 16 independent inputs. The B825 senses and converts switched input signals into logic voltage levels used by the PLC. The module provides 16 inputs that share an external power supply. Inputs can be received from push buttons, limit and proximity switches, and other 24 Vdc sources. Input voltages are sensed by comparing the incoming voltage against a fixed threshold. The threshold is a function of the user-supplied field voltage.
18.1.1
Simplified Schematic
Figure 38 B825--016 Simplified Schematic
88
B825--016 24 Vdc Input (True High)
GM--DISC--800
Page 98
18.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
18.2.1
Input Connections
-+
Figure 39 B825--016 Terminal Numbering and Input Connections
GM--DISC--800
B825--016 24 Vdc Input (True High)
89
Page 99
18.3 Specifications B825--016 Specifications Description
24 Vdc input
Type of Operation
True high
Number of Points
16
Operating Voltage
20 ... 28 Vdc
Number of Groups
1
Inputs/group
16
Maximum Input Voltage
Continuous
30 Vdc
Surge
500 Vdc for 3 ms
ON Conditions
> 21 Vdc or .75 of Vs, whichever is less. 1,000 W max resistance to common. Input indicator ON.
OFF Conditions
< 5 Vdc or .25 of Vs, whichever is greater. 25,000 W resistance to common. Input indicator OFF.
ON Current Maximum Response Time
Power Required
90
6 mA (typical) @ 24 Vdc OFF ® O N
11 ms (2.5 ms typical)
ON ® OF F
11 ms (2.5 ms typical)
+5 V
27 mA
+4.3 V
1.2 mA
--5 V
15 mA
External Power Supply
24Vdc +4 V@ 200 mA max (Vs)
Terminal Connector
AS--8534--000
B825--016 24 Vdc Input (True High)
GM--DISC--800
Page 100
Chapter 19 B826--032 24 Vdc Output (True High)
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B826--032 24 Vdc Output (True High)
91