Page 91

Maximum Input Voltage

Continuous

10 ... 60 Vdc

Maximum Response Time

OFF ® ON

2.5 ms min, 11 ms max

ON ® OFF

2.5 ms min, 11 ms max

+5 V

27 mA

+4.3 V

1 mA

--5 V

10 mA

Power Required

External Supply

10 ... 60 Vdc (Excluding Input Current)

External Supply Current/group

2 mA (max) @ 10 Vdc 5 mA (max) @ 24 Vdc 10 mA (max) @ 48 Vdc 12 mA (max) @ 60 Vdc

Terminal Connector

GM--DISC--800

AS--8534--000

B821--108 10 ... 60 Vdc Input (True High)

81

Page 92

Chapter 17 B824--016 24 Vdc Output (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B824--016 24 Vdc Output (True High)

83

Page 93

17.1 Overview The Modicon B824-016 24 Vdc True High Output Module consists of sixteen independent outputs divided into two groups of eight. The B824 converts signals used within the PLC into 16 independent outputs. Outputs are capable of driving motor starters, relays, and a variety of other loads. There are 16 transistor switches which are used to control loads connected to external power source. The module’s 16 outputs are in two groups, eight outputs per group. Each group is fused to protect the outputs from overload currents and polarity reversal.

17.1.1

Simplified Schematic

Figure 36 B824--016 Simplified Schematic

84

B824--016 24 Vdc Output (True High)

GM--DISC--800

Page 94

17.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

17.2.1

Output Connections

R

R

Figure 37 B824--016 Terminal Numbering and Output Connections

GM--DISC--800

B824--016 24 Vdc Output (True High)

85

Page 95

17.3 Specifications B824--016 Specifications Description

24 Vdc output

Type of Operation

True high

Number of Points

16

Operating Voltage

20 ... 28 Vdc

Number of Groups

2

Outputs/group

8

On Current

86

Maximum/point

2 A continuous

Maximum Surge

5 A for 10 ms

Maximum/group

6A

Maximum/module

12 A

ON State

Voltage Drop

1.8 Vdc @ 2 A

OFF State

Leakage Current

1 mA (max) @ 24 Vdc

Maximum Response Time

OFF ® ON

1 ms

ON ® OFF

1 ms

Power Required

+5 V

32 mA

+4.3 V

260 mA

--5 V

0 mA

External Power Supply

24Vdc +4 V, 175 mA -- Polarity Protected (Excluding field load current)

Terminal Connector

AS--8534--000

Fusing

One / group, 8 A

B824--016 24 Vdc Output (True High)

GM--DISC--800

Page 96

Chapter 18 B825--016 24 Vdc Input (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B825--016 24 Vdc Input (True High)

87

Page 97

18.1 Overview The Modicon B825- -016 24 Vdc True High Input Module consists of a single group of 16 independent inputs. The B825 senses and converts switched input signals into logic voltage levels used by the PLC. The module provides 16 inputs that share an external power supply. Inputs can be received from push buttons, limit and proximity switches, and other 24 Vdc sources. Input voltages are sensed by comparing the incoming voltage against a fixed threshold. The threshold is a function of the user-supplied field voltage.

18.1.1

Simplified Schematic

Figure 38 B825--016 Simplified Schematic

88

B825--016 24 Vdc Input (True High)

GM--DISC--800

Page 98

18.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

18.2.1

Input Connections

-+

Figure 39 B825--016 Terminal Numbering and Input Connections

GM--DISC--800

B825--016 24 Vdc Input (True High)

89

Page 99

18.3 Specifications B825--016 Specifications Description

24 Vdc input

Type of Operation

True high

Number of Points

16

Operating Voltage

20 ... 28 Vdc

Number of Groups

1

Inputs/group

16

Maximum Input Voltage

Continuous

30 Vdc

Surge

500 Vdc for 3 ms

ON Conditions

> 21 Vdc or .75 of Vs, whichever is less. 1,000 W max resistance to common. Input indicator ON.

OFF Conditions

< 5 Vdc or .25 of Vs, whichever is greater. 25,000 W resistance to common. Input indicator OFF.

ON Current Maximum Response Time

Power Required

90

6 mA (typical) @ 24 Vdc OFF ® O N

11 ms (2.5 ms typical)

ON ® OF F

11 ms (2.5 ms typical)

+5 V

27 mA

+4.3 V

1.2 mA

--5 V

15 mA

External Power Supply

24Vdc +4 V@ 200 mA max (Vs)

Terminal Connector

AS--8534--000

B825--016 24 Vdc Input (True High)

GM--DISC--800

Page 100

Chapter 19 B826--032 24 Vdc Output (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B826--032 24 Vdc Output (True High)

91