Page 81

HOT 115 VAC

115 Vac

Figure 30 B817--116 Typical Field Circuit Connections

HOT

Figure 31 B817--216 Typical Field Circuit Connections

70

B817--116 and B817--216 115/230 Vac

GM--DISC--800

Page 82

14.3 Specifications B817--x16 Specifications 115 Vac isolated input (B817-116)

Description

230 Vac isolated input (B817-216) Number of Points

16

Number of Groups

16

Inputs/group Maximum Input Voltage

1 Continuous

130 Vac / 47 ... 63 Hz (B817--116) 260 Vac / 47 ... 63 Hz (B817--216)

Surge

200 Vac for 1 cycle (B817--116) 400 Vac for 1 cycle (B817--216)

ON Conditions

B817--116

>80 Vac (Source Impedance <1 kW)

B817--216

>160 Vac (Source Impedance <1 kW)

OFF Conditions

0 ... 35 Vac (Source Impedance = 0 W) B817--116

0 ... 130 Vac (Source Impedance >40 kW) 0 ... 90 Vac (Source Impedance = 0 W)

Wetting Current Maximum Response Time (Module) Power Required

Terminal Connector

B817--216

0 ... 260 Vac (Source Impedance >80 kW)

B817--116

0 + 4 mA (typical) @115 Vac

B817--216

8.2 + 3 mA (typical) @ 230 Vac

OFF ® ON

6 ms

ON ® OFF

18 ms

+5 V

25 mA

+4.3 V

2 mA

--5 V

8 mA AS--8535--000

Note: Scan time may increase response time when seen in user logic.

GM--DISC--800

B817--116 and B817--216 115/230 Vac

71

Page 83

Chapter 15 B820--008 10 ... 60 Vdc Output (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B820--008 10 ... 60 Vdc Output (True High)

73

Page 84

15.1 Overview The B820-008 10 ... 60 (eight-point) Output Module (True High) converts logic signals used within the PLC into eight independent 10 ... 60 Vdc outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The B820 is capable of handling a total continuous current of 12 A. The module uses transistor switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads.

15.1.1

Simplified Schematic

Figure 32 B820--008 Simplified Schematic

The module’s eight outputs are separated into four groups of two outputs each.

74

B820--008 10 ... 60 Vdc Output (True High)

GM--DISC--800

Page 85

15.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

15.2.1

Output Connections

10 ... 60 Vdc

10 ... 60 Vdc

10 ... 60 Vdc

10 ... 60 Vdc

Figure 33 B820--008 Terminal Numbering and Output Connections

GM--DISC--800

B820--008 10 ... 60 Vdc Output (True High)

75

Page 86

15.3 Specifications B820--008 Specifications Description

10 ... 60 Vdc (true high) output

Number of Points

8

Operating Voltage

10 ... 60 Vdc

Number of Groups

4

Outputs / Group

2

ON State Voltage Drop

1.5 Vdc max @ 2A

ON Current

Maximum/point

2A

Maximum/group

6A

Maximum/module

12.0 A

Surge Current

10 A/channel max for 10 ms at a repetition rate of 0.05%

Peak Voltage

80 Vdc max for 10 ms at a repetition rate of 0.05%

OFF State

Leakage Current

5 mA (max) @ 60 Vdc

Maximum Response Time

OFF ® ON

1 ms (.1 ms typical)

ON ® OFF

1 ms (.1 ms typical)

dv/dt Power Required

200 V/ms +5 V

90 mA

+4.3 V

80 mA

--5 V

0 mA

External Power Supply

10 ... 60 Vdc, 500 mA max./group (Excluding field load current)

76

Terminal Connector

AS--8534--000

Fusing

One/group, 3 AG, 6 A (normal blow)

B820--008 10 ... 60 Vdc Output (True High)

GM--DISC--800

Page 87

Chapter 16 B821--108 10 ... 60 Vdc Input (True High)

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B821--108 10 ... 60 Vdc Input (True High)

77

Page 88

16.1 Overview The B821-108 10 ... 60 Vdc Input Module (True High) senses and converts switched input signals into logic voltage levels used by the PLC. The module allows for up to eight inputs in four groups of two. Each group shares a common reference voltage supply input. These inputs can be received from push buttons, limit and proximity switches, as well as other 10 ... 60 Vdc sources.

16.1.1

Simplified Schematic

Figure 34 B821--108 Simplified Schematic

78

B821--108 10 ... 60 Vdc Input (True High)

GM--DISC--800

Page 89

16.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

16.2.1

Input Connections

10 ... 60 Vdc

10 ... 60 Vdc

10 ... 60 Vdc

10 ... 60 Vdc

Figure 35 B821--108 Terminal Numbering and Input Connections

GM--DISC--800

B821--108 10 ... 60 Vdc Input (True High)

79

Page 90

16.3 Specifications B821--108 Specifications Description

10 ... 60 Vdc input module

Type of Operation

True high

Number of Points

8

Operating Voltage

10 ... 60 Vdc

Number of Groups

4

Inputs/group

2

ON Level

Input Voltage

If the applied input voltage is > 70% of the external power supply, the input to the controller is guaranteed to be in an ON logic state. However, to achieve satisfactory margin, the input voltage should be 75% of the supply voltage. Once the input to the controller is in the ON state, it remains ON as long as the input voltage is > 60% of the power voltage.

Note When designing or selecting a drive circuit for the B821, take into consideration the values listed for input currents that follow.

Inputs Current

Supply Volt (Vdc)

Input Volt Vdc)

Max Input Current (mA)

10

10

10

24

24

15

48

48

25

60 OFF Level

60 Input Voltage

32 If the applied input voltage is < 40% of the supply voltage, the input to the controller is guaranteed to be in an OFF logic state. However, to achieve satisfactory margin, the input voltage should be < 25% of the supply voltage.

Note When designing or selecting a drive circuit for the B821, take into consideration the values listed for source resistance that follow.

Source Resistance

80

Supply Volt (Vdc)

Input Volt (Vdc)

Max Source Resistance (W)

10

10

200

60

60

500

B821--108 10 ... 60 Vdc Input (True High)

GM--DISC--800