Page 71

12.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

12.2.1

Output Connections 115 Vac

115 Vac

H

N

H

N

H

N

H

N

H

N

H

N

H

N

H

N

Figure 25 B810--008 Terminal Numbering and Output Connections

GM--DISC--800

B810--008 115 Vac Isolated Output

59

Page 72

12.3 Specifications B810--008 Specifications Description

115 Vac isolated output

Number of Points

8

Operating Voltage

80 ... 130 Vac continuous / 47 ... 63 Hz

Number of Groups

8

Outputs / Group

1

ON Current

Maximum OFF

Maximum/point

2 A continuous

Surge Current

50 A (max) 1 cycle

Maximum/group

2A

Maximum/module

12 A

Minimum Load Current

50 mA

Leakage Current

3 mA @ 115 Vac

ON Voltage Drop

1.3V @ 2.0A max

Surge Voltage

150 Vac for 10 s 200 Vac for 1 cycle

Maximum Response Time

OFF ® ON

8.3 ms @ 60 Hz

ON ® OFF

8.3 ms @ 60 Hz dv/dt Power Required

60

100 V/ms Commutating

5 V//ms

+5 V

50 mA

+4.3 V

240 mA

--5 V

0 mA

Terminal Connector

AS--8534--000

Fusing

One/group, Type 3 AG, 3 A (normal blow)

B810--008 115 Vac Isolated Output

GM--DISC--800

Page 73

Chapter 13 B814--108 Relay Output

GM--DISC--800

V

Overview

V

Configuration

V

Field Connections

V

Specifications

B814--108 Relay Output

61

Page 74

13.1 Overview The B814-108 Relay Output Module converts signals from the PLC to eight independent relay outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 5.0 A. Each of the eight outputs is electrically isolated from the I/O bus and from the other seven outputs by the relay coil. The module is designed to withstand the high surge currents typical of industrial loads. The module is user- -configurable as to setting for normally- -open or normally- -closed operation of the relays as described below, and is compatible with other Modicon input modules. Assuming a normally- -open configuration, when the relay coil is energized, the relay contacts will conduct current from output A terminal to output B terminal (see Figure 26).

13.1.1

Simplified Schematic

PLC

Figure 26 B814--108 Simplified Schematic

62

B814--108 Relay Output

GM--DISC--800

Page 75

13.2 Configuration The B814 is initially shipped with all eight channels jumpered for the normally- -open configuration. You may optionally wire any of the channels for normally- -closed operation if desired. This is done by transferring a wire jumper from one tab to another on the printed circuit board. Refer to the label on the side of the module. B814--108 User Configuration Wire/Tab Designations

GM--DISC--800

Channel

N.O.

N.C.

1

W1-E2

W1-E1

2

W2-E4

W2-E3

3

W3-E6

W3-E5

4

W4-E8

W4-E7

5

W5-E10

W5-E9

6

W6-E12

W6-E11

7

W7-E14

W7-E13

8

W8-E16

W8-E15

B814--108 Relay Output

63

Page 76

13.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

13.3.1

Output Connections

Figure 27 B814--108 Typical Circuit Connections for Power Applications

Note: Since each output is isolated from the remaining outputs, separate power sources can be used for each load. Each output can be wired for current source or current sink operations. Note: It is possible to have the ACTIVE indicator lit with one or more output channels working improperly.

64

B814--108 Relay Output

GM--DISC--800

Page 77

13.4 Specifications B814--108 Specifications Description

Relay (NO/NC) output

Number of Points

8

Operating Voltage

0 ... 30 Vdc 0 ... 240 Vac / 47 ... 63 Hz

Number of Groups

8

Outputs/group

1

ON Current

Maximum/point

5 A @ 30 Vdc/120 Vac 4 A @ 240 Vac

Maximum/module

40 A @ 30 Vdc/120 Vac

Switching Capability

960 VA maximum, or 150 W dc maximum

Contact Resistance

< 300 mW (including fuse, wire, connectors, and contacts)

OFF State

Leakage Current

Relay Life Rating Maximum Response Time Power Required

.5 mA (typical) @ 240 Vac/60 Hz 100,000 operations, and 50,000 operations with inductive loads @ 25°C

OFF ® ON

15 ms (6 ms typical)

ON ® OFF

15 ms (6 ms typical)

+5 V

107 mA

+4.3 V

800 mA

--5 V

0 mA

Terminal Connector

AS--8534--000

Fusing

One / output, 7 A

Note: For 48 Vdc operation, the maximum load is 1 A.

GM--DISC--800

B814--108 Relay Output

65

Page 78

Chapter 14 B817--116 and B817--216 115/230 Vac Isolated Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B817--116 and B817--216 115/230 Vac

67

Page 79

14.1 Overview The B817- -116 (115 Vac) and B817- -216 (230 Vac) Isolated Input Modules sense OFF and ON input voltages from its field circuitry, converting them to dc logic levels used in the logic program by a Modicon PLC. The module’s 16 input circuits are individually isolated from one another. As each input circuit uses a neutral return wire, none has a definite relationship to system ground unless established in the user’s field circuitry. The module’s logic circuitry is shielded from radiated signals or interference originating in the field, and its field inputs are optically isolated from the system logic.

14.1.1

Simplified Block Diagram

OBS

TO PLC

Figure 28 B817--116 and B817--216 Simplified Block Diagram

When the voltage exceeds the threshold circuits voltage requirement, current will flow through the threshold switch and opto- -isolator via the precision attenuator and the bridge rectifier. The output pulses coupled through the isolator are averaged so that a steady state dc voltage representation of the inner circuit’s ON-state condition is sensed by the Ourbus chip (OBS) on the logic side of the module. The Ourbus output register is set to represent the field ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the PLC. 68

B817--116 and B817--216 115/230 Vac

GM--DISC--800

Page 80

14.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

14.2.1

Terminal Numbering and Input Functions

Figure 29 B817--116 and B817--216 Terminal Numbering

Figure 30 and Figure 31 shows typical circuitry connected to the user side of the field connector.

GM--DISC--800

B817--116 and B817--216 115/230 Vac

69