Page 71
12.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
12.2.1
Output Connections 115 Vac
115 Vac
H
N
H
N
H
N
H
N
H
N
H
N
H
N
H
N
Figure 25 B810--008 Terminal Numbering and Output Connections
GM--DISC--800
B810--008 115 Vac Isolated Output
59
Page 72
12.3 Specifications B810--008 Specifications Description
115 Vac isolated output
Number of Points
8
Operating Voltage
80 ... 130 Vac continuous / 47 ... 63 Hz
Number of Groups
8
Outputs / Group
1
ON Current
Maximum OFF
Maximum/point
2 A continuous
Surge Current
50 A (max) 1 cycle
Maximum/group
2A
Maximum/module
12 A
Minimum Load Current
50 mA
Leakage Current
3 mA @ 115 Vac
ON Voltage Drop
1.3V @ 2.0A max
Surge Voltage
150 Vac for 10 s 200 Vac for 1 cycle
Maximum Response Time
OFF ® ON
8.3 ms @ 60 Hz
ON ® OFF
8.3 ms @ 60 Hz dv/dt Power Required
60
100 V/ms Commutating
5 V//ms
+5 V
50 mA
+4.3 V
240 mA
--5 V
0 mA
Terminal Connector
AS--8534--000
Fusing
One/group, Type 3 AG, 3 A (normal blow)
B810--008 115 Vac Isolated Output
GM--DISC--800
Page 73
Chapter 13 B814--108 Relay Output
GM--DISC--800
V
Overview
V
Configuration
V
Field Connections
V
Specifications
B814--108 Relay Output
61
Page 74
13.1 Overview The B814-108 Relay Output Module converts signals from the PLC to eight independent relay outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 5.0 A. Each of the eight outputs is electrically isolated from the I/O bus and from the other seven outputs by the relay coil. The module is designed to withstand the high surge currents typical of industrial loads. The module is user- -configurable as to setting for normally- -open or normally- -closed operation of the relays as described below, and is compatible with other Modicon input modules. Assuming a normally- -open configuration, when the relay coil is energized, the relay contacts will conduct current from output A terminal to output B terminal (see Figure 26).
13.1.1
Simplified Schematic
PLC
Figure 26 B814--108 Simplified Schematic
62
B814--108 Relay Output
GM--DISC--800
Page 75
13.2 Configuration The B814 is initially shipped with all eight channels jumpered for the normally- -open configuration. You may optionally wire any of the channels for normally- -closed operation if desired. This is done by transferring a wire jumper from one tab to another on the printed circuit board. Refer to the label on the side of the module. B814--108 User Configuration Wire/Tab Designations
GM--DISC--800
Channel
N.O.
N.C.
1
W1-E2
W1-E1
2
W2-E4
W2-E3
3
W3-E6
W3-E5
4
W4-E8
W4-E7
5
W5-E10
W5-E9
6
W6-E12
W6-E11
7
W7-E14
W7-E13
8
W8-E16
W8-E15
B814--108 Relay Output
63
Page 76
13.3 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
13.3.1
Output Connections
Figure 27 B814--108 Typical Circuit Connections for Power Applications
Note: Since each output is isolated from the remaining outputs, separate power sources can be used for each load. Each output can be wired for current source or current sink operations. Note: It is possible to have the ACTIVE indicator lit with one or more output channels working improperly.
64
B814--108 Relay Output
GM--DISC--800
Page 77
13.4 Specifications B814--108 Specifications Description
Relay (NO/NC) output
Number of Points
8
Operating Voltage
0 ... 30 Vdc 0 ... 240 Vac / 47 ... 63 Hz
Number of Groups
8
Outputs/group
1
ON Current
Maximum/point
5 A @ 30 Vdc/120 Vac 4 A @ 240 Vac
Maximum/module
40 A @ 30 Vdc/120 Vac
Switching Capability
960 VA maximum, or 150 W dc maximum
Contact Resistance
< 300 mW (including fuse, wire, connectors, and contacts)
OFF State
Leakage Current
Relay Life Rating Maximum Response Time Power Required
.5 mA (typical) @ 240 Vac/60 Hz 100,000 operations, and 50,000 operations with inductive loads @ 25°C
OFF ® ON
15 ms (6 ms typical)
ON ® OFF
15 ms (6 ms typical)
+5 V
107 mA
+4.3 V
800 mA
--5 V
0 mA
Terminal Connector
AS--8534--000
Fusing
One / output, 7 A
Note: For 48 Vdc operation, the maximum load is 1 A.
GM--DISC--800
B814--108 Relay Output
65
Page 78
Chapter 14 B817--116 and B817--216 115/230 Vac Isolated Input
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B817--116 and B817--216 115/230 Vac
67
Page 79
14.1 Overview The B817- -116 (115 Vac) and B817- -216 (230 Vac) Isolated Input Modules sense OFF and ON input voltages from its field circuitry, converting them to dc logic levels used in the logic program by a Modicon PLC. The module’s 16 input circuits are individually isolated from one another. As each input circuit uses a neutral return wire, none has a definite relationship to system ground unless established in the user’s field circuitry. The module’s logic circuitry is shielded from radiated signals or interference originating in the field, and its field inputs are optically isolated from the system logic.
14.1.1
Simplified Block Diagram
OBS
TO PLC
Figure 28 B817--116 and B817--216 Simplified Block Diagram
When the voltage exceeds the threshold circuits voltage requirement, current will flow through the threshold switch and opto- -isolator via the precision attenuator and the bridge rectifier. The output pulses coupled through the isolator are averaged so that a steady state dc voltage representation of the inner circuit’s ON-state condition is sensed by the Ourbus chip (OBS) on the logic side of the module. The Ourbus output register is set to represent the field ON state. As long as the field input status remains true, the module will communicate this status each time it is polled by the PLC. 68
B817--116 and B817--216 115/230 Vac
GM--DISC--800
Page 80
14.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
14.2.1
Terminal Numbering and Input Functions
Figure 29 B817--116 and B817--216 Terminal Numbering
Figure 30 and Figure 31 shows typical circuitry connected to the user side of the field connector.
GM--DISC--800
B817--116 and B817--216 115/230 Vac
69