Page 61

Chapter 10 B808--016 230 Vac Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B808--016 230 Vac Output

49

Page 62

10.1 Overview The B808-016 230 Vac (16 point) Output Module converts logic signals used within the PLC into 16 independent 230 Vac outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The B808 is capable of 6 A per group of eight and handling 12 A per module. The module uses triac switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads.

10.1.1

Simplified Schematic

FROM PLC

Figure 20 B808--016 Simplified Schematic

50

B808--016 230 Vac Output

GM--DISC--800

Page 63

10.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

10.2.1 OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 AC COMMON AC HOT--GROUP A

Output Connections

OUTPUT 9 OUTPUT 10 OUTPUT 11 OUTPUT 12 OUTPUT 13 OUTPUT 14 OUTPUT 15 OUTPUT 16 AC COMMON AC HOT--GROUP B

Figure 21 B808--016 Terminal Numbering and Output Connections

GM--DISC--800

B808--016 230 Vac Output

51

Page 64

10.3 Specifications B808--016 Specifications Description

230 Vac output

Number of Points

16

Operating Voltage

180 ... 260 Vac continuous / 47 ... 63 Hz

Number of Groups

2

Outputs/group

8

ON Current

Maximum/point

2 A continuous

Surge Current

50 A (max) 1 cycle

Maximum/group

6A

Maximum/module

12 A

ON Voltage Drop

1.3 V @ 2.0A

Maximum OFF

Leakage Current

8 mA @ 230 Vac

Maximum Response Time

OFF ® ON

8.3 ms @ 60 Hz

ON ® OFF

8.3 ms @ 60 Hz

Applied dv/dt Power Required

52

100 V/ms +5 V

76 mA

+4.3 V

480 mA

--5 V

0 mA

Terminal Connector

AS--8534--000

Fusing

1 / group, Type 3 AB, 8 A (normal blow)

B808--016 230 Vac Output

GM--DISC--800

Page 65

Chapter 11 B809--016 230 Vac Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B809--016 230 Vac Input

53

Page 66

11.1 Overview The B809-016 230 Vac (16 point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC. The module allows for up to 16 inputs in two groups of eight. These inputs can be received from push buttons, limit and proximity switches, as well as other 230 Vac sources.

11.1.1

Simplified Schematic

TO PLC

Figure 22 B809--016 Simplified Schematic

54

B809--016 230 Vac Input

GM--DISC--800

Page 67

11.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

11.2.1

Input Connections

Figure 23 B809--016 Terminal Numbering and Input Connections

GM--DISC--800

B809--016 230 Vac Input

55

Page 68

11.3 Specifications B809--016 Specifications Description

230 Vac input

Number of Points

16

Operating Voltage

160 ... 260 Vac / 47 ... 63 Hz

Number of Groups

2

Outputs / Group Maximum Input Voltage

8 Continuous

260 Vac 300 Vac for 10 s

Surge

400 Vac for 1 cycle

ON Conditions

160 ... 260 Vac (Source Impedance =1 kW)

ON Current

8.5 mA (typical) @ 230 Vac

OFF Conditions

0 ... 90 Vac (Source Impedance =0 W))

Peak inrush for 260VRMS (Rs=0) applied @ peak

1.7 A max

Maximum Response Time

OFF ® ON

5 ms (3 ms typical)

ON ® OFF

18 ms (12 ms typical)

+5 V

42 mA

+4.3 V

1 mA

--5 V

15 mA

Space Required

1 slot

Weight

2.38 lbs (1.08 kg)

Power Required

Dimensions Terminal Connector

AS--8534--000

Note: The B809- -016 input module is electrically compatible with the B808- -016 output module.

56

B809--016 230 Vac Input

GM--DISC--800

Page 69

Chapter 12 B810--008 115 Vac Isolated Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B810--008 115 Vac Isolated Output

57

Page 70

12.1 Overview The B810-008 115 Vac (eight-point) Output Module converts logic signals used within the PLC into eight independent 115 Vac outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The B808 is capable of 6 A/group of eight and handling 12 A/module. The module uses eight triac switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads.

12.1.1

Simplified Schematic 15 20

1

FROM PLC

2

Figure 24 B810--008 Simplified Schematic

Zero- -cross threshold switching is incorporated into each output circuit. Upon controller command, outputs switch ON at the first line voltage zero- -crossing, and switch OFF at the first load current zero- -crossing. Output status indicators are provided for each output circuit. These neon indicators will be ON when a load is connected and the output is ON, or when there is no connected load. These indicators are isolated from the triac output and require a separate lamp supply which is fused at 1/4 A. Blown fuse indicators are also provided for each output circuit. These indicators light (ON) when the corresponding fuse has blown. 58

B810--008 115 Vac Isolated Output