Page 51

7.4 Specifications B806--032 Specifications Description

115 Vac output

Number of Points

32

Operating Voltage

80 ... 130 Vac continuous / 47 ... 63 Hz

Number of Groups

2

Outputs/group

16

On Current

Maximum OFF

Maximum/point

1 A continuous

Surge Current

15 A 1 cycle

Maximum/module

16 A

Maximum/group

8A

Minimum Load Current

5A

Leakage Current

2 mA @ 115 Vac

Voltage Drop Maximum Response Time

1.5 V RMS Maximum OFF ® ON

8.3 ms @ 60 Hz

ON ® OFF

8.3 ms @ 60 Hz dv/dt Power Required

Terminal Connector

600 V/ms Commutating

5 V/ms

+5 V

210 mA

+4.3 V

1 mA

--5 V

0 mA AS--8535--000

Note: The B806 is powered by a standard 120 Vac field power supply.

GM--DISC--800

B806--032 115 Vac Output

37

Page 52

Chapter 8 B806--124 24 Vac Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B806--124 24 Vac Output

39

Page 53

8.1 Overview The B806- -124 Output Module (B806) has 32 outputs. The outputs can serve 24 Vac voltage relays, motor starters, solenoids, pilot lamps, valves, and other loads rated up to 1.0 A. The outputs are divided into two groups of 16 discrete points.

8.1.1

Simplified Schematic

SOLID

Figure 15 B806--124 Simplified Schematic

40

B806--124 24 Vac Output

GM--DISC--800

Page 54

8.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

8.2.1

Output Connections

Figure 16 B806--124 Terminal Numbering and Output Connections

GM--DISC--800

B806--124 24 Vac Output

41

Page 55

8.3 Specifications B806--124 Specifications Description

24 Vac output

Number of Points

32

Operating Voltage

20 ... 28 Vac continuous / 47 ... 63 Hz 32 Vac RMS max for 10 s 42 Vac RMS max for 1 cycle

Number of Groups

2

Outputs/group

16

ON Current

Maximum OFF

Maximum/point

1 A continuous

Surge Current

15 A 1 cycle

Maximum/group

8A

Maximum/module

16 A

Minimum Load Current

5 mA

Leakage Current

2 mA

Voltage Drop Maximum Response Time

1.5 V (max) OFF ® ON

8.3 ms @ 60 Hz

ON .® OFF

8.3 ms @ 60 Hz dv/dt Power Required

Terminal Connector

600 V/ms Commutating

5 V/ms

+5 V

210 mA

+4.3 V

1 mA

--5 V

0 mA AS--8535--000

Note: The B806 is powered by standard 24 Vac field power supply.

42

B806--124 24 Vac Output

GM--DISC--800

Page 56

Chapter 9 B807--132 115 Vac Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B807--132 115 Vac Input

43

Page 57

9.1 Overview The B807- -132 115 Vac (32 point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC. These inputs can be received from push buttons, limit and proximity switches, as well as other 115 Vac sources.

9.1.1

Simplified Schematic

Figure 17 B807--132 Simplified Schematic

Note: When using Binary and BCD inputs remember that input 1 is the MSB and input 32 is the LSB.

44

B807--132 115 Vac Input

GM--DISC--800

Page 58

9.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

9.2.1

Input Connections

Figure 18 B807--132 Terminal Numbering and Input Connections

Note:

Pins 1, 20, 21, and 40 have no internal connections.

Note: The module can operate from 47 ... 63 Hz. However, its use with proximity switches is recommended only at 60 Hz nominal line frequency. Leakage current through switching devices connected to the module may cause a false ON condition.

GM--DISC--800

B807--132 115 Vac Input

45

Page 59

9.2.2

Input Current-to-Frequency Relationship 13mA 11.8mA

12 11 9.9mA

10 9

ON REGION

C

8 SINUSOIDAL INPUT CURRENT

7.7mA 7 6.4mA

6 B 5 4 3

1.8 mA

2 1 0

1.5 mA A

OFF REGION 45

50

55

60

65

70Hz

FREQUENCY A.

MAXIMUM ALLOWABLE SINEWAVE LEAKAGE CURRENT (FROM EXTERNAL DEVICE) TO GUARANTEE AN OFF CONDITION (CALCULATED AT 35 Vac) AT B807 TERMINALS

B.

MINIMUM REQUIRED INPUT CURRENT TO GUARANTEE AN ON CONDITION NOTE: THE MODULE IS INTENDED TO BE USED WITH VOLTAGE INPUTS; VOLTAGE INPUTS GREATER THAN 80Vac RMS AT MODULE TERMINALS GUARANTEE AN ON CONDITION

C.

MAXIMUM MODULE INPUT CURRENT AT 130 Vac Figure 19 B807--132 Input Current to Frequency Chart

46

B807--132 115 Vac Input

GM--DISC--800

Page 60

9.3 Specifications B807--132 Specifications Description

115 Vac input

Number of Points

32

Operating Voltage

80 ... 130 Vac continuous / 47 ... 63 Hz

Number of Groups

4

Inputs/group

8

Maximum Input Voltage

150 Vac for 10 s 200 Vac for 1 cycle

ON Condition

80 ... 130 Vac (Source Impedance <1 kW)

OFF Condition

0 ... 35 Vac (Source Impedance =0 W) 0 ... 130 Vac (Source Impedance >90 kW)

ON Current

3.7 mA minimum @ 80 Vac, 50Hz input* 6.4 mA minimum @ 115 Vac, 60Hz input*

Maximum External to Module Leakage Current

1.8 mA to guarantee an OFF condition @ 60Hz

Maximum Response Time

OFF ® ON

6 ms

ON ® OFF

35 ms

+5 V

80 mA

+4.3 V

2 mA

--5 V

0 mA

Power Required

Terminal Connector

AS--8535--000

*Minimum input on current at stated voltage and frequency with less than 10 W source impedance

Note: All voltage and current specifications assume a sine wave form and are specified as RMS voltage and current. Note: Input LED brightness is a function of line voltage applied.

GM--DISC--800

B807--132 115 Vac Input

47