The text of a manual · part 5 of 25
Modicon 800 Series Discrete I/O Modules User Guide, pages 41 to 50
Pages 41 to 50 of 241
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B804, Modicon B805, Modicon B807, Modicon B824, Modicon B825, Modicon B828, Modicon B865, AEG B804, and 21 more models
Page 41
5.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
5.2.1
Output Connections
Figure 10 B804--148 Terminal Numbering and Output Connections
GM--DISC--800
B804--148 48 Vac Output
27
Page 42
5.3 Specifications B804--148 Specifications Description
48 Vac output
Number of Points
16
Operating Range Voltage
40 ... 56 Vac continuous / 47 ... 63 Hz
Number of Groups
2
Outputs/group
8
ON Current
Maximum/point
2 A continuous
Surge Current
50 A 1 cycle
Maximum/group
6A
Maximum/module
12.0 A
Maximum OFF
3 mA
Leakage Current
3 mA
Voltage Drop
1.5 V @ 2 A
Minimum Load Current
25 mA RMS
Maximum Response Time
OFF ® ON
8.3 ms @ 60 Hz
ON ® OFF
8.3 ms @ 60 Hz dv/dt Power Required
28
100 V/ms Commutating
5 V/ms
+5 V
76 mA
+4.3 V
480 mA
--5 V
0 mA
Terminal Connector
AS--8534--000
Fusing
One / group, 8 A replaceable
B804--148 48 Vac Output
GM--DISC--800
Page 43
Chapter 6 B805--016 115 Vac Input
GM--DISC--800
V
Overview
V
Field Connections
V
Specifications
B805--016 115 Vac Input
29
Page 44
6.1 Overview The B805- -016 115 Vac (16 point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC. The module allows for up to 16 inputs in 2 groups of 8. These inputs can be received from push buttons, limit and proximity switches, as well as other 115 Vac sources.
6.1.1
Simplified Schematic
TO PLC
Figure 11 B805--016 Simplified Schematic
30
B805--016 115 Vac Input
GM--DISC--800
Page 45
6.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
6.2.1
Input Connections
Figure 12 B805--016 Terminal Numbering and Input Connections
GM--DISC--800
B805--016 115 Vac Input
31
Page 46
6.3 Specifications B805--016 Specifications Description
115 Vac input
Number of Points
16
Operating Range
80 ... 130 Vac / 47 ... 63 Hz
Number of Groups
2
Inputs/group
8
Maximum Input Voltage
Continuous
130 Vac
Surge
220 Vac for 1 cycle
ON Conditions
80 ... 130 Vac (Source Impedance =0 W)
OFF Conditions
0 ... 35 Vac (Source Impedance =1 kW) 0 ... 130 Vac (Source Impedance >40 kW)
ON Current
6 mA (typical) @ 115 Vac
OFF Current
1.8 mA (max) @ 35 Vac RMS leakage for input sensors 3.0 mA (Typ) @ 60Vac RMS
ON Condition
Threshold Voltage
60 + 15 V RMS
Maximum Response Time
OFF® ON
6 ms (4 ms typical)
ON ® OFF
18 ms (11 ms typical)
+5 V
40 mA
+4.3 V
1 mA
--5 V
14 mA
Power Required
Terminal Connector
32
B805--016 115 Vac Input
AS--8534--000
GM--DISC--800
Page 47
Chapter 7 B806--032 115 Vac Output
GM--DISC--800
V
Overview
V
Field Connections
V
Fusing Requirements
V
Specifications
B806--032 115 Vac Output
33
Page 48
7.1 Overview The B806- -032 Vac Output Module (B806) has 32 outputs. The outputs can serve 120 Vac voltage relays, motor starters, solenoids, pilot lamps, valves, and other loads rated up to 1.0 A. The outputs are divided into two groups of 16 discrete points.
7.1.1
Simplified Schematic
SOLID
Figure 13 B806--032 Simplified Schematic
34
B806--032 115 Vac Output
GM--DISC--800
Page 49
7.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system /mits module insertion or removal without disturbing the wiring.
7.2.1
Output Connections
Figure 14 B806--032 Terminal Numbering and Output Connections
GM--DISC--800
B806--032 115 Vac Output
35
Page 50
7.3 B806--032 Fusing Guidelines For reasons of safety and equipment performance, Modicon strongly recommends external fusing on each individual output point according to the following rating: Fuse Rating
Very Fast Acting
2A
Example Type
Little Fuse
3 AB
Note: A minimum voltage rating of 250 V is required for safe fuse operation. Voltage ratings can be found along with current ratings on the fuse end cap. Warning! Failure to fuse these output modules, or to follow the recommended fuse ratings, could cause unpredictable results in module performance and/or damage to this and other equipment. Observe fusing guidelines.
36
B806--032 115 Vac Output
GM--DISC--800