Page 41

5.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

5.2.1

Output Connections

Figure 10 B804--148 Terminal Numbering and Output Connections

GM--DISC--800

B804--148 48 Vac Output

27

Page 42

5.3 Specifications B804--148 Specifications Description

48 Vac output

Number of Points

16

Operating Range Voltage

40 ... 56 Vac continuous / 47 ... 63 Hz

Number of Groups

2

Outputs/group

8

ON Current

Maximum/point

2 A continuous

Surge Current

50 A 1 cycle

Maximum/group

6A

Maximum/module

12.0 A

Maximum OFF

3 mA

Leakage Current

3 mA

Voltage Drop

1.5 V @ 2 A

Minimum Load Current

25 mA RMS

Maximum Response Time

OFF ® ON

8.3 ms @ 60 Hz

ON ® OFF

8.3 ms @ 60 Hz dv/dt Power Required

28

100 V/ms Commutating

5 V/ms

+5 V

76 mA

+4.3 V

480 mA

--5 V

0 mA

Terminal Connector

AS--8534--000

Fusing

One / group, 8 A replaceable

B804--148 48 Vac Output

GM--DISC--800

Page 43

Chapter 6 B805--016 115 Vac Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B805--016 115 Vac Input

29

Page 44

6.1 Overview The B805- -016 115 Vac (16 point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC. The module allows for up to 16 inputs in 2 groups of 8. These inputs can be received from push buttons, limit and proximity switches, as well as other 115 Vac sources.

6.1.1

Simplified Schematic

TO PLC

Figure 11 B805--016 Simplified Schematic

30

B805--016 115 Vac Input

GM--DISC--800

Page 45

6.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

6.2.1

Input Connections

Figure 12 B805--016 Terminal Numbering and Input Connections

GM--DISC--800

B805--016 115 Vac Input

31

Page 46

6.3 Specifications B805--016 Specifications Description

115 Vac input

Number of Points

16

Operating Range

80 ... 130 Vac / 47 ... 63 Hz

Number of Groups

2

Inputs/group

8

Maximum Input Voltage

Continuous

130 Vac

Surge

220 Vac for 1 cycle

ON Conditions

80 ... 130 Vac (Source Impedance =0 W)

OFF Conditions

0 ... 35 Vac (Source Impedance =1 kW) 0 ... 130 Vac (Source Impedance >40 kW)

ON Current

6 mA (typical) @ 115 Vac

OFF Current

1.8 mA (max) @ 35 Vac RMS leakage for input sensors 3.0 mA (Typ) @ 60Vac RMS

ON Condition

Threshold Voltage

60 + 15 V RMS

Maximum Response Time

OFF® ON

6 ms (4 ms typical)

ON ® OFF

18 ms (11 ms typical)

+5 V

40 mA

+4.3 V

1 mA

--5 V

14 mA

Power Required

Terminal Connector

32

B805--016 115 Vac Input

AS--8534--000

GM--DISC--800

Page 47

Chapter 7 B806--032 115 Vac Output

GM--DISC--800

V

Overview

V

Field Connections

V

Fusing Requirements

V

Specifications

B806--032 115 Vac Output

33

Page 48

7.1 Overview The B806- -032 Vac Output Module (B806) has 32 outputs. The outputs can serve 120 Vac voltage relays, motor starters, solenoids, pilot lamps, valves, and other loads rated up to 1.0 A. The outputs are divided into two groups of 16 discrete points.

7.1.1

Simplified Schematic

SOLID

Figure 13 B806--032 Simplified Schematic

34

B806--032 115 Vac Output

GM--DISC--800

Page 49

7.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system /mits module insertion or removal without disturbing the wiring.

7.2.1

Output Connections

Figure 14 B806--032 Terminal Numbering and Output Connections

GM--DISC--800

B806--032 115 Vac Output

35

Page 50

7.3 B806--032 Fusing Guidelines For reasons of safety and equipment performance, Modicon strongly recommends external fusing on each individual output point according to the following rating: Fuse Rating

Very Fast Acting

2A

Example Type

Little Fuse

3 AB

Note: A minimum voltage rating of 250 V is required for safe fuse operation. Voltage ratings can be found along with current ratings on the fuse end cap. Warning! Failure to fuse these output modules, or to follow the recommended fuse ratings, could cause unpredictable results in module performance and/or damage to this and other equipment. Observe fusing guidelines.

36

B806--032 115 Vac Output

GM--DISC--800