Page 31

Chapter 3 B803--008 115 Vac Input

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B803--008 115 Vac Input

17

Page 32

3.1 Overview The B803- -008 115 Vac (8 point) Input Module senses and converts switched input signals into logic voltage levels used by the PLC into 8 independent 115 Vac outputs. The module allows for up to eight independently sensed inputs. These inputs can be received from push buttons, limit and proximity switches, as well as other 115 Vac sources.

3.1.1

Simplified Schematic

TO PLC

Figure 5 B803--008 Simplified Schematic

18

B803--008 115 Vac Input

GM--DISC--800

Page 33

3.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

3.2.1

Output Connections

INPUT 1 HOT

COMMON

NEUTRAL 1

INPUT 5 HOT

COMMON

NEUTRAL 5

INPUT 2

INPUT 6

NEUTRAL 2

NEUTRAL 6

NOT USED

NOT USED

NOT USED

NOT USED

INPUT 3

INPUT 7

NEUTRAL 3

NEUTRAL 7

INPUT 4

INPUT 8

NEUTRAL 4

NEUTRAL 8

Figure 6 B803--008 Terminal Numbering and Input Connections

GM--DISC--800

B803--008 115 Vac Input

19

Page 34

3.3 Specifications B803--008 Specifications Description

115 Vac isolated input

Number of Points

8

Operating Range Voltage

80 ... 130 Vac / 47 ... 63 Hz

Number of Groups

8

Inputs / Group Maximum Input Voltage

1 Continuous

130 Vac

Surge

220 Vac for 1 cycle

ON Condition

80 ... 130 Vac (Source Impedance < 1kW)

OFF Condition

Maximum / Module

0 ... 35 Vac (Source Impedance = 0 W) 0 ... 130 Vac (Source Impedance > 40kW)

”ON” Condition

Threshold Voltage

60 + 15VRMS

ON Current Maximum Response Time Power Required

Terminal Connector

20

B803--008 115 Vac Input

7 mA (typical) @ 115 Vac OFF ® ON

6 ms (4 ms typical)

ON ® OFF

18 ms (12 ms typical)

+5 V

27 mA

+4.3 V

1 mA

--5 V

2 mA AS--8534--000

GM--DISC--800

Page 35

Chapter 4 B804--116 115 Vac Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B804--116 115 Vac Output

21

Page 36

4.1 Overview The B804- -116 115 Vac (16 point) Output Module converts logic signals used in the PLC into 16 independent 115 Vac outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The B804 is capable of handling a total continuous current of 6 A/group of eight points and 12 A/module. The module uses triac switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads.

4.1.1

Simplified Schematic

FROM PLC

Figure 7 B804--116 Simplified Schematic

The module’s 16 outputs are separated into two groups of eight outputs each.

22

B804--116 115 Vac Output

GM--DISC--800

Page 37

4.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

4.2.1

Output Connections

Figure 8 B804--116 Terminal Numbering and Output Connections

GM--DISC--800

B804--116 115 Vac Output

23

Page 38

4.3 Specifications B804--116 Specifications Description

115 Vac output

Number of Points

16

Operating Voltage

80 ... 130 Vac continuous / 47 ... 63 Hz

Number of Groups

2

Outputs / Group

8

ON Current

Maximum OFF

Maximum / Point

2 A continuous

Surge Current

50 A 1 cycle

Maximum / Group

6A

Maximum / Module

12.0 A

Minimum Load Current

25 mA (B804-116)

Minimum Load Current

50 mA (B804-016)

Leakage Current

3 mA @ 115 Vac

Voltage Drop Maximum Response Time

1.5 V @ 2.0 A OFF ® ON

8.3 ms @ 60 Hz

ON ® OFF

8.3 ms @ 60 Hz dv/dt Power Required

24

100 V/ms +5 V

76 mA

+4.3 V

480 mA

--5 V

0 mA

Terminal Connector

AS--8534--000

Fusing

Type 3AB, 8 A (normal blow)

B804--116 115 Vac Output

GM--DISC--800

Page 39

Chapter 5 B804--148 48 Vac Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B804--148 48 Vac Output

25

Page 40

5.1 Overview The B804- -148 48 Vac (16 point) Output Module converts logic signals used within the PLC into 16 independent 48 Vac outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The module has 16 outputs, divided into two groups of eight discrete points.

5.1.1

Simplified Schematic

FROM PLC

Figure 9 B804--148 Simplified Schematic

26

B804--148 48 Vac Output

GM--DISC--800