Page 21

1.5 Installation Procedure

How to Install an 800 Series I/O Module Installation of your 800 Series module involves: unpacking the module, wiring the field connector, installing key pins in the housing, and mounting the module in the housing.

Step 1

Remove the module from its shipping box and check for damage. If damaged, contact your salesman or distributor for correct replacement procedure.

Step 2

Ensure power to housing is OFF.

Step 3

Designate the housing slot for this module.

Step 4

Locate the required connector assembly. (Modicon Part number AS- -8534- -000 or AS- -8535- -000). This assembly consists of one or two 20- -pin connectors. Note: Remove the keying tabs on the connector prior to installing the module.

6

Step 5

Remove the old duct, if a different connector/cabling duct assembly is already present in the designated housing slot.

Step 6

(Optional Step) If there is a module to the immediate left of the slot designated for the module’s installation, temporarily remove it.

Step 6

As shown in Figure 1, Mount the new field connector/duct assembly to the left of the module’s designated housing slot and secure it to the housing top and bottom using the two Phillips head machine screws provided.

800 Series I/O Modules

GM--DISC--800

Page 22

Figure 1 Cabling Duct/Field Connector Assembly

1.5.1

Field Connection Note: When performing this step, refer to the appropriate chapter in this manual of the 800 Series module you are installing for the appropriate connector type.

Step 7

Connect field side wiring to proper pins on the field connector. Note: Terminals accept either two 141 AWG size wires or one 12 AWG size wire/point.

GM--DISC--800

800 Series I/O Modules

7

Page 23

Caution: Neat and proper workmanship methods by qualified personnel must be employed when making connections to this module. Take extra precautions if you are using stranded wire. Ensure that loose or projecting strands do not short circuit or ground the other terminals. We recommend that you use solid wire. Step 8

Re- -install any module temporarily removed. Note: When performing this step, refer to Appendix A for illustrations of optional key pin patterns for the 800 Series module you are installing. This Appendix contains key pin patterns for all 800 series I/O modules.

Step 9

When using key pins (provided with housing shipment), install them above and below the housing slot selected for this module’s installation. Figure 2 shows this optional mechanical keying system used to match the module type with a particular slot in the housing to ensure proper module replacement. LOOKING AT FRONT OF HOUSING -- OVER MODULE SLOT O

P O

O

P

P

P

When facing housing, place the knurled end of the key pins into the holes indicated by the P. Use a 1/2 in plastic head mallet or equivalent to drive the pin into the housing approximately 1/4 in. NOTE: The keying system is optional.

O O

O

LOOKING AT FRONT OF HOUSING -- UNDER MODULE SLOT Figure 2 Example of Key Pin Location

Step 10 8

Insert module into housing, firmly but carefully, seating the edge connector in the backplane.

800 Series I/O Modules

GM--DISC--800

Page 24

Note: First time installation of a module may be tight.

GM--DISC--800

Step 11

Secure the module to housing using captive slotted mounting screws at the top and bottom of the module front panel.

Step 12

After confirming all modules are properly installed, apply applicable field power and re- -apply power to the programmable controller.

Step 13

I/O Map the module.

Step 14

Start the controller.

Step 15

Confirm that the module’s active light is illuminated.

800 Series I/O Modules

9

Page 25

1.6 Quick Start Test Step 1

Determine which channel and slot location are being used for this module.

Step 2

Wire field device to the appropriate terminals (refer to the individual wiring diagrams/field connector drawings for that particular I/O module) on either the AS- -8534- -000 low density connector, or AS- -8535- -000 high density connector, (refer to the Specification section for your particular I/O module to determine which connector is required.)

Step 3

Stop the PLC.

Step 4

Install the I/O module.

Step 5

I/O Map the module, reference at the desired discrete or register reference.

Step 6

Start the PLC.

Step 7

Confirm that the modules active light is illuminated (may require Step 8 wiring first).

Step 8

To turn an input ON, apply the required power to the appropriate terminals (refer to the individual wiring diagrams/field connector drawings for your particular I/O module), and confirm that the red I/O light is illuminated after turning I/O point ON. To turn an output ON enter the programming screen (P230 or equivalent) and call up the reference and disable this reference ON. Note: Refer to 984 System Manual for specifics on disabling coils. See individual chapters for module specific Quick Starts.

10

800 Series I/O Modules

GM--DISC--800

Page 26

1.7 Generic Specifications Generic Environmental Specifications Operating Operating Isolation

Shock Vibration

Temperature

0 ... 60°C (32 ... 140°F)

Humidity

0 ... 95% (non--condensing) @ 60°C

Temperature

--40 ... 85°C (32 ... 140°F)

Humidity

0 ... 95% (non--condensing) @ 60°C

Field to System

2000 VAC steady state maximum @ 60 Hz for 1 min

Between Groups

2500 VDC for 60 s without breakdown. Leakage current shall not exceed 1.5 mA

Operating

+15 G peak, 11 ms, half--sine wave

Non--operating

+15 G peak, 11 ms, half--sine wave

Operating

0.005 in D.A. Sine, from 10 to crossover frequency (57 ... 62 Hz) 1.0 G from crossover frequency to 50 Hz

Non--operating

0.029 G sq/Hz, 10 ... 50 Hz rolloff @ --8dB/octave from 50 ... 500 Hz

EMI

MIL--STD 461B

RFI

FCC Class A

Surge Withstand Capability

IEEE 472--1974 and ANSI C37.90A--1974

Generic Mechanical Specifications Dimensions (W x H x D)

2.0 x 10.5 x 8.0 in 50.8 x 266.7 x 203.2 mm

Weight

2.4 lbs. (1.1 kg)

Space Required

1 I/O slot

See individual chapters for module specific Specifications.

GM--DISC--800

800 Series I/O Modules

11

Page 27

Chapter 2 B802--008 115 Vac Output

GM--DISC--800

V

Overview

V

Field Connections

V

Specifications

B802--008 115 Vac Output

13

Page 28

2.1 Overview The B802- -008 115 Vac (8 point) Output Module converts logic signals used within the PLC into eight independent 115 Vac outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The B802 is capable of handling a total continuous current of 12 A. The module uses triac switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads.

2.1.1

Simplified Schematic

Figure 3 B802--008 Simplified Schematic

The module’s eight outputs are separated into four groups of two outputs each. An LED indicator lights when an output is ON.

14

B802--008 115 Vac Output

GM--DISC--800

Page 29

2.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.

2.2.1

Output Connections

OUTPUT 1

OUTPUT 5

OUTPUT 2

OUTPUT 6

NEUTRAL GRP 1

NEUTRAL GRP 3

HOT GRP 1 NOT USED NOT USED OUTPUT 3 OUTPUT 4 NEUTRAL GRP 2

HOT GRP 3 NOT USED NOT USED OUTPUT 7 OUTPUT 8 NEUTRAL GRP 4 HOT GRP 4

HOT GRP 2 Figure 4 B802--008 Terminal Numbering and Output Connections

GM--DISC--800

B802--008 115 Vac Output

15

Page 30

2.3 Specifications B802--008 Specifications Description

115 Vac output

Number of Points

8

Operating Voltage

80 ... 130 Vac continuous / 47 ... 63 Hz

Number of Groups

4

Outputs/group

2

ON Current

Maximum/point

2 A continuous

Maximum/module

12.0 A

Surge Current

50 A (max) 1 cycle / circuit

ON Voltage Drop Maximum OFF

Maximum Response Time

1.3 V @ 2.0 A Leakage Current

3 mA @ 115 Vac

Maximum ON Current

50 mA @ 115 Vac

OFF ® ON

8.3 ms @ 60 Hz

ON ® OFF

8.3 ms @ 60 Hz dv/dt Power Required

16

100 V/ms Commutating

5 V/ms

+5 V

76 mA

+4.3 V

240 mA

--5 V

0 mA

Terminal Connector

AS-8534-000

Fusing

One/group, Type 3 AG, 6 A (normal blow)

B802--008 115 Vac Output

GM--DISC--800